Professional Documents
Culture Documents
SURGE ARRESTORE
SURGE ARRESTORE
Index Number: DS-NG-6460-002-020, Rev. 00 Title: Test Form for Surge Arresters Commissioning
Substation:132/13.8KV Contract T&C Contactor:JAL Main Contractor:JAL
OUKDUD No.:4400013322
Page Number: 1 of 1 Serial No: R-341806, Dwg. Ref.: Desegnation:T603 Panel/Bay
Y-341807,B-341808 SA No:=Y605.1+S1
APPROVED
08 MAY 2023
1. Equipment General Data and Information
R-341806,
Serial Number TRIDELATA Manufacturer’s Name
Y-341807,B-341808
2021 Year SB120/SM-A-0 Type
Maximum Continuous
96 120KV Rated Voltage
Operating Voltage
Nominal Discharge
60HZ Frequency 10KA
Current (KA) rms
3. Electrical Tests
3.1. Insulation Test:
Insulation Checked With 5kV for 1 min
Remarks B Phase - Earth. Y Phase - Earth R Phase - Earth
595 GΩ 844 GΩ 798 GΩ
Criteria:
3.1.1. Leakage Current Meter Calibration: