PowerAfrica49420.2020.9219990 (1)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

2020 IEEE PES/IAS PowerAfrica

Appropriate Surge Arrester Lead Lengths for


Improved Distribution Transformer Protection –
Kenyan Case Study
Julius Ndirangu
Department of Electrical and Electronic Peter Kimemia, Raphael Ndolo John Nderu, George Irungu
Engineering, Kenya Power and Lighting Company Department of Electrical and Electronic
Jomo Kenyatta University of Nairobi, Kenya Engineering
Agriculture and Technology Jomo Kenyatta University of
Nairobi, Kenya Agriculture and Technology
julzndirangu@gmail.com Nairobi, Kenya

Abstract— Medium voltage power networks are frequently effectiveness. A surge arrester is a device designed to protect
exposed to overvoltages caused by lightning strikes and other electrical apparatus from high transient voltage and to limit
external events. In the Kenyan distribution system, metal oxide the duration and amplitude of follow-current. It achieves this
surge arresters are widely used for surge protection of by providing a low impedance path to the ground for high
secondary distribution transformers. However, lightning strikes voltage travelling waves. It functions as a variable resistor that
are still one of the major causes of secondary transformers limits overvoltages on an electric distribution system. In the
failure in the network. A critical aspect in selection and Kenyan distribution system, metal oxide surge arresters are
application of surge arrestors is the surge arrestor lead length. widely used for surge protection of distribution transformers.
The focus of this paper was calculation of the protective ratios
of surge arresters with current typical lead lengths installed for Surge arresters require connections to the system phase
surge arresters protecting distribution transformers in 11kV conductor and earth. This is achieved through conductors
and 33kV networks in the Kenyan distribution system. known as leads. A Surge arrester lead length is the wire from
Comparison was made with the guidelines of IEEE C62.22 on the top of the protected equipment to its grounded end that is
minimum protective ratios. Recommendations on appropriate parallel to the surge arrester. The total length of the lead wire
surge arrester lead lengths that to guarantee the achievement of is measured from the point at which the arrester line
these minimum protective ratios are given. Recalculations to connection is made to the point where interconnection is made
demonstrate adequacy of the recommendations were also between the arrester ground lead and the protected equipment
carried out. This will lead to improved protection for
ground lead, excluding the arrester length[5]. This is
distribution transformers against surges in the distribution
network.
illustrated in Fig. 1.

Index terms— discharge voltage, lead length, protective


margin, surge arrester

I. INTRODUCTION
Electricity customers continue to demand improvement in
power supply reliability and quality[1]. This is in addition to
safety requirements[2]. To improve reliability of supply,
power utilities must focus on mitigating the effects of
overvoltages in the network, which is one of the causes of
medium and high voltage network service interruptions and
outages. Overvoltages in medium voltage networks may
overstress the dielectric strength of secondary distribution
transformers and other line equipment installed in the
network, causing failures. Such overvoltages may be
generated by external events like lightning strikes or by
internal conditions such as faults, switching, ferroresonance,
load rejection, loss of ground or a combination of such
conditions. In Kenya, lightning strikes are one of the major
causes of distribution transformers failure in the network[3].
This problem is amplified in terminal distribution
transformers[4]. Distribution transformers form the link
between power supply and the consumers and thus needs Fig. 1. Arrester Lead length Illustration
adequate protection to ensure continuous operation. This
underscores the importance of a critical review of the current
surge arrester installation methodology to assess its

978-1-7281-6746-6/20/$31.00 ©2020 IEEE

Authorized licensed use limited to: University of New South Wales. Downloaded on October 18,2020 at 02:18:30 UTC from IEEE Xplore. Restrictions apply.
2020 IEEE PES/IAS PowerAfrica
achieved, according to the minimum recommendations given
in IEEE C62.22[5]. As the steepness of surge current
A critical aspect in selection and application of surge increases, the arrester presents higher residual voltage thus
arrestors is the arrestor lead length. When a lightning strike reducing the protective margin which endangers the life of the
occurs, the discharge current causes a residual voltage across transformer. The protective characteristics of an arrester is a
the terminal of the surge arrester. Similarly, it causes a voltage combination of residual voltage for steep current impulse,
build up in the surge arrester lead due to its inductance. Any residual voltage for lightning impulses, and residual voltage
voltage build up in an arrester lead will add to the arrester for switching impulses. Hence, there are three residual voltage
residual voltage. Since a surge arrester is connected in parallel characteristics that together make up the protective level of the
with the protected equipment, the total arrester residual arrester. These are Front-of-Wave Protective Level, Lightning
voltage will appear across the protected equipment. Arrester Impulse Protective Level and Switching Protective Level. The
residual voltage can be significantly high when one considers respective protective ratios are chopped wave withstand ratio
typical arrester lead lengths that are actually installed in the (CWWR), Full wave withstand ratio (FWWR) and switching
network and faster rates-of-rise of surge currents. The residual surge withstand ratio (SSWR). These three ratios are used to
voltage magnitude is further increased by coiling the leads determine how well an arrester is protecting the intended
since this increases their inductance. Overlooking the impact equipment. The chopped wave withstand (CWW) is generally
of lead lengths contributes to overstating the protective assumed to be 115% of the BIL[5].
margins of surge arrestors during their selection. This leads to
inadequate protection of distribution transformers and other ƒ–‹‘Ψ ൌ ቂቀ
େ୛୛
ቁ െ ͳቃ ‫ͲͲͳݔ‬ (2)
line equipment when the surge arresters are actually installed. ୊୛ୗ୓
In Kenya, the standard construction used for pole mounted
where CWW = Chopped wave withstand(kV) and FWSO =
transformer structures places the surge arresters on top of the
Front of Wave Spark Over voltage (kV)
transformer such that the arrester lead lengths are 2meters for
11kV and approximately 3m for 33kV, on average. Installers ƒ–‹‘Ψ ൌ ቂቀ
୆୍୐
ቁ െ ͳቃ ‫ͲͲͳݔ‬ (3)
also coil the leads to provide spare lengths. The focus of this ୖ୚ା୚ಽ
paper is calculation of the protective ratios of surge arresters where FWWR = Full wave withstand ratio(%), BIL = Basic
with current typical lead lengths installed in distribution Insulation Level (kV) and RV = Residual Voltage at a surge
transformer structures in 11kV and 33kV networks in the current of 10kA(kV), ௅ = Surge arrester lead build up
Kenyan distribution system. Comparison is made with the voltage(kV).
guidelines of IEEE C62.22 on minimum protective ratios.
୆ୗ୐
Recommendations on appropriate surge arrester lead lengths ƒ–‹‘ ൌ ቂቀ ቁ െ ͳቃ ‫ͲͲͳݔ‬ (4)
ୗୗ୔୐
that should be installed to guarantee the achievement of these
minimum protective ratios are given. Recalculations to where SSW = Switching Surge Withstand Ratio(%), BSL =
demonstrate adequacy of the recommendations in improving Basic Surge Withstand Level (kV) and SSPL = Switching
the protective ratios were also carried out. Surge Protective Level (kV). IEEE C62.22 standard states that
the minimum level of protection is 20% for chopped wave
The outline of the paper is as follows: Protective ratios withstand ratio, 20% for full wave withstand ratio, and 15%
based on current typical surge arrester lead lengths used in for switching surge withstand ratio. Switching surge withstand
11kV and 33kV networks in Kenya are presented in section II. ratio (SSWR) is normally calculated for higher voltages and
Recommended mitigation measures to ensure compliance thus was not considered in the calculations[5].
with IEEE C62.22 guidelines and consequent recalculations
done are presented in Section III. Conclusions and B. Impact of Arrester Lead Length on Protective Level
recommendations are summarized in Section IV. The inductance of the lead wire normally used to connect
distribution arresters between line and ground can be assumed
II. PROTECTIVE RATIOS CALCULATION BASED ON CURRENT
to be 1.3123μH/m[6]. The voltage build up on the arrester lead
SURGE ARRESTER LEAD LENGTHS IN KENYA is given by[6].
A. Protective Level of a Surge Arrester ୢ୧
ൌ (5)
Insulation coordination is defined in IEEE C62.22 as the ୢ୲
selection of insulation strength consistent with expected Where E = Voltage build up on arrester (kV), L =
overvoltages to obtain an acceptable risk of failure[5]. The inductance of the arrester lead(μH) and di/dt = rate of rise of
degree of coordination is measured by the protective ratio surge current. Coiling the surge arrester lead increases its
(PR) given by [5] inductance leading to significant increase in the voltage build
୍୬ୱ୳୪ୟ୲୧୭୬୵୧୲୦ୱ୲ୟ୬ୢ୪ୣ୴ୣ୪ up on the arrester. The voltage build up calculated in (5)
”‘–‡ –‹˜‡”ƒ–‹‘ሺሻ ൌ  (1) should be added to the arrester residual voltage when
୚୭୪୲ୟ୥ୣୟ୲୮୰୭୲ୣୡ୲ୣୢୣ୯୳୧୮୫ୣ୬୲
calculating voltages incident to the protected transformer.
Basic Insulation Level (BIL) of equipment is defined as Published arrester residual voltages are normally based on a
the peak voltage of a 1.2/50μs wave which does not cause its standard 8/20μs impulse current wave (8 μs to crest/20μs to
insulation to fail. 1.2/50μs indicates a surge which reaches its half crest on the tail)[7]. However, the highest voltages to
peak value in 1.2μs and decays to half the peak in 50μs[5]. For which the insulation is subjected are rapidly rising steep wave
insulation coordination, protective ratios are calculated at impulses due to lightning. Published lightning data indicates
three separate points within the volt-time regions. These are median of 31.1 kA and 24.3 kA/μs rate of rise for first stroke
switching surge withstand, the full wave withstand and the and median of 12.3 kA and 39.9 kA/μs rate of rise for
chopped wave withstand. The protective ratios must be met or subsequent strokes[8]. A conservative rate of rise value of 20
exceeded if satisfactory insulation coordination is to be kA/μs was used for analysis in this paper.

Authorized licensed use limited to: University of New South Wales. Downloaded on October 18,2020 at 02:18:30 UTC from IEEE Xplore. Restrictions apply.
2020 IEEE PES/IAS PowerAfrica
C. Protective Ratios calculation based on existing Kenyan III. RECOMMENDED MITIGATION MEASURES TO ENSURE
scenario COMPLIANCE WITH IEEE C62.22 GUIDELINES
Currently in the Kenyan system surge arrestors for It is noted that installation of surge arresters on the low
transformer protection are pole mounted. The arrester lead voltage side of transformers does not drastically change the
lengths are usually coiled and have average lengths of 2meters failure rate[9]. Hence, efforts are focussed on appropriate
for 11kV network and 3meters for 33kV network as in Fig1. surge arrester installation on the medium voltage side.
Chopped wave withstand ratio (CWWR), Full wave withstand
One mitigation measure to overcome the challenge of low
ratio (FWWR) and were calculated based on these lengths for
protective ratios in current installations is to reduce the
the two voltage levels. The calculations and results are
arrester lead lengths. In order to reduce the arrester lead length
summarized in Table I.
to ensure compliance with IEEE C62.22 guidelines, this paper
TABLE I. SURGE ARRESTER PROTECTION MARGIN CALCULATIONS
recommends that the surge arresters be mounted on the
WITH EXISTING LEAD LENGTHS IN KENYAN SYSTEM distribution transformer tank. This can be done directly by
transformer manufacturers if the utility specifications are
Nominal System amended to include this requirement. Implementation of this
Parameter Voltages recommendation would lead to reduction of the arrester lead
length to 0.5meters. This is illustrated in Fig. 2.
11kV 33kV
Continuous operating voltage of
arrester (kV) from arrester 9.6 28.8
specifications

Basic Insulation Level(BIL) of


95 200
transformer e(1.2/50 μs, dry) (kV)

di/dt (kA/μs) 20 20

Lead wire voltage build up (kV/m)


26.24 26.24
E=Ldi/dt(kV/m); L= 1.312μH/m

Typical arrester lead lengths


2 3
installed in Kenya (m)
Total Arrester lead voltage ௅ (kV) 52.48 78.72

Residual Voltage(RV) at 10kA(kV)


35.1 105.4
from arrester specification (kV)

Total Voltage incident at the


Transformer Terminal = 87.58 184.12
RV+௅ (kV)
Front of Wave Spark Over voltage Fig. 2. Proposed Arrester Lead length Installation
(FWSO) for10kA(1/2μs)kV - from 35.1 105.4 To achieve the same arrester lead length in existing
arrester specification installations, the structures can be modified on site such that
Chopped Wave Withstand the arresters are installed on a cross-arm immediately above
109.25 230 the transformer. The cost of such a modification would be
(CWW)=115% x BIL(kV)
nominal compared to the overall cost savings. To demonstrate
CWW Ratio (%) from (2) 211.25% 118.22% the impact of these recommendations on increasing
transformer protection, the protective ratios were repeated
FWW Ratio(%) from (3) 8.47% 8.62% using surge arrestor lead lengths of 0.5m. These calculations
were captured in Table II.
IEEE C62.22 minimum
requirements for CWWR and 20% 20% From Table II, with the proposed arrester lead lengths of
FWWR[2] 0.5meters, Chopped wave withstand ratios for 11kV and 33kV
surge arresters are 211% and 118% respectively. Full wave
withstand ratios 11kV and 33kV surge arresters are 97% and
From Table I, with current surge arrester lead lengths of 68.7%. These are well above the required minimum of 20% as
2m for 11kV and 3m for 33kV networks, CWW ratios are per IEEE C62.22 guidelines. From this analysis, it is clear that
satisfied while FWW ratios of the surge arrestors are below the protection of the transformer against surges shall be
the 20% minimum. This means that the 11/0.42kV and significantly improved with surge arrester lead lengths of
33/0.42kV distribution transformers in the network are not 0.5m.
adequately protected against lightning surges. This could be a
major contributing factor to the high rate of failure of
distribution transformers as a result of lightning strikes[3].

Authorized licensed use limited to: University of New South Wales. Downloaded on October 18,2020 at 02:18:30 UTC from IEEE Xplore. Restrictions apply.
2020 IEEE PES/IAS PowerAfrica
TABLE II. SUMMARY OF RECALCULATED PROTECTIVE RATIOS WITH minimum threshold as per IEEE C62.22. This means that at
PROPOSED LEAD LENGTHS
present, the 11/0.42kV and 33/0.42kV distribution
Nominal System transformers are not adequately protected against lightning
Voltages surges in existing installations in the network. It has also been
Parameter shown that the protection of the transformer against surges can
11kV 33kV be significantly improved if the surge arrester lead lengths are
reduced to 0.5meters. In line with the analysis done in this
Continuous operating voltage of paper, and in order to guarantee adequacy of surge protection
arrester (kV) from arrester 9.6 28.8 for 33/0.42kV and 11/0.42kV secondary distribution
specifications transformers by surge arresters, this paper recommends as
follows:
Basic Insulation Level(BIL) of
transformer e(1.2/50 μs, dry) 95 200 i) Kenyan utility specifications be revised to require
(kV) that for all new 11kV and 33kV class distribution
transformers, surge arresters be mounted at the
di/dt (kA/μs) 20 20 transformer tanks and to minimize the arrester lead
Lead wire voltage build up lengths to 0.5meters. Further, the arrester leads
(kV/m) E=Ldi/dt(kV/m) 26.24 26.24 should not be coiled.
L= 1.312μH/m ii) A maintenance program be initiated by the utility to
modify the installation of existing surge arresters so
Proposed arrester lead lengths that they are installed on a cross-arm immediately
0.5 0.5
(M) above the transformers so as to reduce the lead
Total Arrester lead voltage ௅ lengths to 0.5meters and without coils.
13.12 13.12
(kV) REFERENCES
Residual Voltage(RV) at [1] J. G. Ndirangu, J. N. Nderu, and A. M. Muhia, “Power Quality
10kA(kV) from arrester 35.1 105.4 Challenges and Mitigation Measures in Grid Integration of Wind
specification (kV) Energy Conversion Systems,” in 2018 IEEE International Energy
Conference (ENERGYCON), 2018, pp. 1–6.
Total Voltage incident at the [2] J. Ndirangu, P. Kimemia, J. Nderu, R. Ndolo, and G. Irungu,
Transformer Terminal = 48.22 118.52 “Analytical Calculation of Electric and Magnetic Fields Near a
RV+௅ (kV) Proposed 132kV Line with Constrained Right of Way – Kenyan Case
Study,” in 2019 International Conference on High Voltage
Front of Wave Spark Over Engineering and Technology (ICHVET), 2019, pp. 1–6.
voltage (FWSO) [3] C. Ndungu, J. Nderu, L. Ngoo, and P. Hinga, “A Study of the Root
35.1 105.4 Causes of High Failure Rate of Distribution Transformer - A Case
for10kA(1/2μs)kV - from Study,” Int. J. Eng. Sci., pp. 14–18, 2017.
arrester specification [4] J. Muriuki, C. M. Muriithi, and G. N. Nyakoe, “Protection of Terminal
Chopped Wave Withstand Distribution Transformers : A Case Study of Kenya Power,” in 2018
109.25 230 IEEE PES/IAS PowerAfrica, 2018, pp. 408–413.
(CWW)=115% x BIL(kV)
[5] IEEE Power & Energy Society, “IEEE Guide for the Application of
CWW Ratio (%) from (2) Metal-Oxide Surge Arresters for Alternating-Current Systems,” 2009.
211.25% 118.22%
[6] IEEE Committee Report, “Protection of Cable-Connected Distribution
FWW Ratio(%) from (3) Equipment on Underground Systems,” IEEE Trans. Power Appar.
97.01% 68.73% Syst., vol. PAS-89, no. 2, pp. 263–267, 1970.
[7] International Electrotechnical Commission(IEC), “Insulation co-
IEEE C62.22 minimum ordination Part 2: Application guide,” 1996.
requirements for CWWR and 20% 20%
[8] IEEE Power & Energy Society, IEEE Guide for Improving the
FWWR[2] Lightning Performance of Electric Power Overhead Distribution Lines,
vol. 2010, January. 2011.
[9] A. Piantini, J. M. Janiszewski, O. Thaís, D. Carvalho, and P. F. Obase,
IV. CONCLUSION “Lightning-caused Transformer Failures in Distribution Systems,” in
2014 International Conference on Lightning Protection (ICLP), 2014,
The analysis carried out in this paper has shown that with pp. 955–960.
current surge arrester lead lengths of 2meters for 11kV and
3meters for 33kV networks in Kenya, the full wave withstand
protective ratios of the surge arrestors are below the 20%

Authorized licensed use limited to: University of New South Wales. Downloaded on October 18,2020 at 02:18:30 UTC from IEEE Xplore. Restrictions apply.

You might also like