Voltage Regulators - Cat Energy Control System (Cat ECS (SEBU8088-28)
Voltage Regulators - Cat Energy Control System (Cat ECS (SEBU8088-28)
PIP
The Cat Digital Voltage Regulator presents an electrical
shock/electrocution hazard. This hazard will cause serious injury
-
or death.
202 1011
Service by trained personnel only.
4 8
The terminals and heat sinks are live at hazardous voltages when
/ 791
power is applied and for up to 8 minutes after power is removed.
12: 0 7 /
4 7 : 1 6
ECS) Controller S EB 27-0
Integrated Voltage Regulator (IVR) with Cat Energy Control System (Cat
© 2 U808 3:00
The Integrated Voltage Regulator (IVR) provides excitation current to the generator through an Excitation Module (EM). The IVR is controlled by
024 8
the IVR function in the Cat ECS. The IVR function allows the Cat ECS to control the generator voltage, optimize transient performance, and
define startup specification.
Cat
The Excitation Module may interface with any of the following excitation systems:
Self-Excitation (SE)
erp
Internal Excitation (IE)
illa
Permanent Magnet (PMG)
r In
c.
For more information about the IVR, refer to the Cat ECS Software Operations Manual.
Illustration 1 g06640952
Excitation Module 10 (EM10)
(1) Connector P3
(2) Connector P2
(3) Connector P4
https://sis2.cat.com/#/print-preview/service/6cfd925f-2be0-47f6-9bc7-206a5446c3be 1/3
16/7/24, 9:47 a.m. SIS 2.0
Table 1 details the connections to be made between the Cat ECS IVR and Excitation Module.
Table 1
Cat ECS Controller Connections to Excitation Module
Cat ECS Controller J-4 Connector Excitation Module 3-pin Connector
PWM Output number 2 Positive P1 (57) CS+ P3-2
PWM Output number 2 Negative P2 (58) CS- P3-3
Shield NC Shield P3-1
Table 2 provides information on technical specifications of the EM10/10A, EM15/15A, and EM25/25A modules. Selection of the appropriate
module must be determined by the following:
Nominal and maximum generator excitation current at full load (Standby 0.8 PF)
Table 2
Table 3
Note: The X2 and Z1 connections are internally linked within the excitation module. The link provides a point of common connection for the
auxiliary windings where an AREP or IE excitation supply is available. Also, the X2 and Z1 connections may be linked externally to the excitation
module. Only three connections (X1, X2, and Z2) are needed for the EM. Refer to the Cat ECS Software Operations Manual, "Integrated
Voltage Regulator" for excitation module wiring connections.
The voltage regulator knee frequency must be configured for your specific package requirements. The knee frequency for 50 Hz operation will
usually be between 48.0 and 49.8 Hz. The knee frequency for 60 Hz operation will usually be between 58.0 and 59.8 Hz.
Refer to Illustration 2 for an example of under-frequency roll-off (loading) profile. Refer to the "Cat ECS Software Operations Manual", Integrated
Voltage Regulator for more details.
https://sis2.cat.com/#/print-preview/service/6cfd925f-2be0-47f6-9bc7-206a5446c3be 2/3
16/7/24, 9:47 a.m. SIS 2.0
Illustration 2 g03487998
Under-frequency (loading) profile slope1 = 1.0 V/Hz, slope2 = 2.0 V/Hz
PIP-10118791
2024/07/16
12:47:20-03:00
i09623709