Transformer Tests (Ir+Wrt+Ttr+Mbt) Tms
Transformer Tests (Ir+Wrt+Ttr+Mbt) Tms
Testing Date
TESTING
L-1
L-2
L-3
Comments:
Transformer S. No. HV/LV H/L (Amp) Make Year of Mfg. Type Temperature
191250 11k/415 78.7/1204.9 PEL 2005 YNd11 32
INSULATION RESISTANCE TEST
HV-G LV-G HV-LV Remarks
15 sec 36.6 MΩ 13.1 MΩ 46.9 MΩ Unsatisfactory
30 sec 36.3 MΩ 12.9 MΩ 47.2 MΩ Unsatisfactory
60 sec 36.1 MΩ 12.7 MΩ 47.1 MΩ Unsatisfactory
WINDING RESISTANCE TEST
Primary Windings (Ω)
Tap Position 1 2 3 4 5 6
R 0.4672 0.4544 0.4431 0.4362 0.4242 0.4144
Y 0.4722 0.4574 0.4450 0.4356 0.4253 0.4172
B 0.4602 0.4500 0.4393 0.4318 0.4261 0.4165
Secondary Windings (mΩ)
Tap Position 3 r-y 7.30 y-b 4.00 b-r 6.84
TRANSFORMER TURNS RATIO TEST
Vector Group
Tap Position Primary Voltage Calculated Remarks
R-N Y-N B-N
1 11550 16.070 16.072 16.070 16.068 Satisfactory
2 11275 15.667 15.677 15.676 15.686 Satisfactory
3 11000 15.270 15.278 15.276 15.303 Satisfactory
4 10725 14.917 14.919 14.917 14.921 Satisfactory
5 10450 14.562 14.564 14.565 14.538 Satisfactory
6 10175 14.139 14.138 14.141 14.155 Satisfactory
MAGNETIC BALANCE TEST
RN YN BN
219.3 V 168.0 V 51.4 V
110.2 V 218.7 V 108.7 V
51.0 V 168.5 V 219.0 V
Oil BDV Result : Earth Pit Result :