Improvement” with, auto VOC / CO2 controllers and ozone monitors cum cut out switch.
1a) Plate type ozone Generators are provided with the primary aim of achieving
reduction in Volatile Organic Compounds (VOC), hydro carbon gases, and organic
odors, in Indoor Environment. They also serve purpose of propagation of microbial
organisms and micro flora, commonly found in indoor environments, HVAC ducts,
cooling coils and on air filters. VOC reduction is achieved by oxidation of VOC by
ozone. Depletion of microbial colonies is achieved by inhibiting their growth and
propagation.
1b) The aim is to ensure the VOC are kept below the TLV (Threshold Limit Value) for
occupied areas, as recommended by OSHA.
1c) The maximum residual concentration of ozone in the indoor environment will never
allowed to exceed 50 PPB (v/v). PPB is Parts per Billion.
1d) Ozone Generators shall be provided where called for, with number of corona
discharge plates as listed in the schedules.
1e) These plate type Ozone Generators shall be compact, self contained units in SS316
L with all components factory mounted in one neat, compact package.
1f) Parts of the generators in contact with air stream are kept to as minimum as
required.
1g) Components in contact with air stream are enclosed in stainless steel casing 18 G
SS316L thick, with sufficient stamped integral openings to allow adequate flow of
air over the corona discharge plates.
1h) The generator plates shall be mounted on generator head fabricated out of materials
that repel accumulation and formation of sediments by tar, nicotine and grease. This
is an extremely important prerequisite to enhance the operational reliability and
ease of maintenance of the generator plates.
1i) The generators are suitable for mounting in ducts with air flow in horizontal,
vertical or angular directions.
1j) The generator operates effectively with air flow in either direction that is left to
right or vice versa in horizontal ducts, and top to bottom or vice versa in vertical
ducts.
1k) Generators can be electrically interlocked with motor of the air handling unit fan.
This will prevent start of the generator unless the fan motor is energized.
1
1l) Generator is mounted inside the ducts. It will be provided with flange suitable for
mounting on a metal frame, to be installed inside the duct.
1m) Openings in the ducts are made with sheet metal shears or cutters. Metal saw or
grinding machine shall not be used, except to make an initial cut to permit use of
metal shear. This precaution is taken to prevent metal debris from falling into the
ducts.
1n) When mounted on the supply air duct, it is importantly ensured that the chosen
location does not have carry over moisture from cooling coil or humidifier, or any
other moisture emitting device.
1o) Care is taken to ensure the generator is mounted on a straight run of duct with
steady flow of air. Installation on bends, elbows, transition pieces, or close to
dampers is not recommended.
1p) Generation of ozone is only by principles of corona discharge. Multiple numbers of
corona discharge plates used to provide the necessary quantity of ozone. All the
corona discharge plates shall be housed in one common stainless steel enclosure.
1q) Only multiple plate type corona surfaces shall be used for ozone generation.
Production density of ozone per sq inch (or sq cm) of surface area of corona surface
shall be as low as possible. Rate of variation of production of ozone shall follow
approximately the rate of variation of VOC in the indoor environment. This is in
view to ensure residual level of ozone in the indoor environment remains low while
ensuring residual VOC level also remains low.
1r) Annular type of corona or corona tube generator mounted outside the air stream
with ozone tube to the duct shall not be used as they produce very high
concentrations or ozone which is undesirable for IAQ improvement.
1s) Ozone and VOC is detected in the same gaseous stream, and ozone production is in
this stream. To ensure this, ozone generator is of duct mounted type. Portable type
generators that produce ozone outside the HVAC air stream are not acceptable in
IAQ treatment.
1t) Ozone generator does not require any consumable for its operation, except for use
of electricity.
1u) The system does not rely on initial or replacement of filters of any sort to remove
odors and chemicals.
1v) The ozone generators are capable of operating on 220 to 240 Volts, single phase
power supply, 50 Hz. They are properly grounded. Ease of maintenance is
important consideration. They are manufactured to permit easy withdrawals and
refitting on the ducts, with minimum use of tools of hardware to remove or refit the
generators to the ducts.
2
2. 0 TVOC SENSOR, MONITOR & CONTROLLER WITH TEMP & HUMIDITY
DETECTION.
IAQ is a comprehensive index, including room temperature; humidity, fresh air, and
diverse low concentrations air contaminants. Monitoring IAQ is very important to
guarantee healthy life and work.
TVOC is specially used to detect indoor air quality in occupied spaces.
TVOC controller provides RS485 network interface and independent base address to PC
or other control system, so each room of the whole ventilating system can be managed
and controlled intelligently.
• Ambience air quality detection and alert
• Ventilation control
• Air quality monitors
• Odor monitors.
2a) Regulation of IAQ device is automatically controlled by Auto TVOC Sensor and
Microprocessor based Intelligent Generator Controller.
2b) Sensor and Controller is rated for continuous operation.
2c) Sensor is suitable for mounting in space, duct, plenum, or process chamber.
2d) The Sensor is factory calibrated to Isobutylene gas 100 PPM for full span and
controlled clean air for zero span. Factory stamped calibration certificate with date
of calibration shall be provided with each Sensor if required.
2e) The TVOC Sensor is capable of detecting broad range of commonly occurring
TVOC in indoor applications. Each gas sensed is related by the sensor to its
corresponding concentration value to isobutylene.
2f) The sensor provides linear signals, from Clean to High levels of concentration of
the polluting TVOC. The Sensor has LCD displays to provide visual indicating for
the TVOC levels. The sensor provides 0 to 10 VDC Linear output.
2g) In the event of power failure, or if the system is turned off, the Sensor retains the
pre- set sensitivity.
2h) Factory supplied interconnecting cable is provided, for communication between
Sensor and Load Controller.
Features:
Real time monitoring ambience air quality with 0~30ppm complex detection range.
LCD displaying air contaminants with temperature and humidity (optional) at the
same time.
Also as the controller of IAQ including temperature and humidity (optional).
Locale adjustable IAQ: 0~30ppm; Temperature:5~45 Deg Centigrade ; Humidity:5 to
95%RH
RS-485 communication interface, 15KV antistatic protection, independent base
address setting.
Semiconductor sensor inside, 5~7 years long life Low power consumption
Microprocessor control with quickly response.
Providing 1x0~10V analog output and up to 1xrelay dry-contact outputs.
Analog output with two alternatives: linear zed over full range output or PID control
output.
3
The relays can be selected to control IAQ, temperature or humidity (programmable
setting).
Timers of turning-off function from 0.5 to 12 hours for the auxiliary (optional).
Specifications:
4
3.0 MICROPROCESSOR BASED INTELLIGENT OZONE GENERATOR
CONTROLLER
5
OTTPL
4.0 OZONE CONCENTRATION SENSOR, MONITOR AND CUTOUT SWITCH
WITH TEMPERATURE / HUMIDITY DETECTION
4a) Ozone concentration monitor cum sensor is provided for the occupied areas. At least one
Monitor/Sensor is provided for generators in the AHU serving the area.
4b) The monitor shall be installed in a side stream duct and not in the main duct. This is to ensure
the sensor element is not exposed to high velocity of air found typically in all HVAC ducts.
This ensures accuracy of sensor readings, and prolongs life of the sensor element.
4c) The sensor, monitor and all components is mounted in one neat and compact case, suitable
for wall mounting.
4d) The monitor shall have electrical leads to provide an open contact. In the event concentration
of ozone reaches the set alarm value, ‘Normally Open’ changes to ‘Normally Close’ position.
This will be used to electrically cut out the ozone generator, when concentration reaches the
set value.
4e) Additionally, if required it can also be provided an audible alarm, which is activated if the
concentration reaches the set level. Switch shall be provided on the case of the monitor, to
turn off the alarm, at the option of the user.
4f) The alarm can be factory set at 50 PPB. However, it shall be possible to change this setting in
the field to any desired level & also be locked programmable so as to safeguard the system.
4g) The monitor provides a linear 0 to 10 Volts DC output voltage, proportional to concentration
of ozone. This will be interfaced with the BMS to record continuously concentration in PPB
or PPM, and also to produce hard copy printouts. This will also enable shutting down the
ozone generators through the BMS, if the set high level is reached.
4h) The monitor is capable of interfacing with BMS. Necessary transponders to enable this will
be provided by others.
4i) It is also possible to set the high ozone cut out level through the BMS, and to shut down the
ozone generators through BMS, in the event the set alarm is reached; If required.
4j) The monitor is suitable for continuous operation.
4k) Input power source is 24 volts, DC, provided. Suitable adaptor for this is provided with the
Monitor.
FEATURES:
6
OTTPL
SPECIFICATIONS:
Features:
Wall mounted, LCD display, real-time detecting CO2 concentration, temperature and %RH
(humidity detection is optional)
Infrared CO2 sensor inside and supply three detection range to select for almost all application.
15 years lifetime of CO2 sensor
Should also work as transmitter of CO2 or as the controller of CO2, temperature and humidity
Microprocessor control, quick response, high precision.
Analog output with two alternatives : linearized over full range output or PID control output
Locale adjustable range CO2: 0 to 20,000 ppm or 0 to 50,000 ; Temperature: 5 to 45 deg. Cen.
Humidity 5 to 95 % RH.
7
OTTPL
Should have ABC Logic with patented Self Calibration Algorithm to make end users use it for
15 years without calibration amending. That is suitable for where concentrations will drop to
outside ambient conditions (about 400ppm) at least 3 times in a 14 day period
RS-485 communication interface, 15KV antistatic protection, independent base address setting
Specifications: