Master Instruction
07.2019 MI EVE0102 A-(en)
SRI986 Electro-Pneumatic Positioner
The SRI986 Positioner is for operation of pneumatic valve actuators from control systems and electrical
controllers with electric control signals. It is used to reduce the adverse effects of valve friction, for higher thrust
and shorter positioning time.
FEATURES
• Independent adjustment of stroke range and zero • Stroke 8 to 260 mm (0.3 to 10.2 in) with standard
• Adjustable amplification and damping lever; larger stroke with special lever
• Split range up to 3-fold possible • Explosion protection:
II 2 G Ex ia IIC T6 according to ATEX or intrinsic
• Input signal 0/4 to 20 mA, 0/2 to 10 V
safety acc. to FM, CSA, CU TR, INMETRO
• Supply pressure up to 6 bar (90 psig)
• EMC in accordance with the international
• Low vibration effect in all directions standards and laws
• Mounting according to IEC 534, part 6 (NAMUR) • Modular system of additional equipment
• Rotation adapter for angles up to 120 - Limit switches
- Position transmitter
- Booster
- Connection manifold
CONTENTS PAGE
1 GENERAL..............................................................3
FUNCTION ............................................................4
ADDITIONAL EQUIPMENT ...................................5
2 MOUNTING ...........................................................6
2.1 Dimensions ............................................................6
2.2 Mounting to diaphragm actuators
according to JEC 534-6 .........................................8
2.3 Mounting to rotary actuators ................................10
4 START-UP ...........................................................14
4.1 Setting boost ........................................................14
4.2 Setting zero point and stroke ...............................15
4.3 Setting damping ...................................................15
4.4 Subdivision of input range (Split-range) ..............16
4.5 Determination of rotation angle Uϕ .....................16
4.6 Determination of stroke factor Ux ........................16
4.6.1 Stroke factor ranges of range springs .................17
4.6.2 Characteristics of range springs ..........................17
5 MAINTENANCE..................................................18
5.1 Basic adjustment of single-acting positioner
(pneumatic part)..................................................18
5.2 Basic adjustment of double-acting positioner
(pneumatic part)...................................................19
5.3 Checking and adjusting the I-p converter ............20
5.4 Cleaning throttles ................................................ 22
11 TROUBLESHOOTING..........................................30
Photographs .........................................................31
MI EVE0102 A-(en)
SRI986 GENERAL Page 3
1 GENERAL
The electro-pneumatic positioner is used for direct In addition, the positioning force of the actuator can
operation of pneumatic valve actuators by means of significantly be increased by an output pressure of
electrical controllers or control systems with an analog max. 6 bar.
output signal of 0 to 20 mA or 4 to 20 mA or split ranges. The electro-pneumatic positioner can be mounted on
Positioner and pneumatic actuator form a control loop both diaphragm actuators and rotary actuators.
with the command variable ws (output signal y of the For spring loaded actuators a single-acting positioner
master controller), the correcting variable ys and the is used, whilst for actuators without spring loading a
stroke position xs of the actuator. double-acting positioner is used.
In this manner disturbing influences such as gland The double-acting positioner operates with two oppo-
sing control pressures.
friction and medium forces within the valve are com-
pensated by the positioner.
m a x . 6 b a r
S tro k e
0 /4 - 2 0 m A
T r a n s m itte r V a lv e
Identification
The nameplate of the positioner is located at the side
wall of the housing. Nameplates are in accordance
with selected model. Examples:
Version without explosion protection
S R I 9 8 6
M a d e in F r a n c e b y E c k a r d t S A S , F - 6 8 3 6 0 S o u ltz
I-P S T E L L U N G S R E G L E R / I-P P O S IT IO N E R
S R I
W IR K U N G S W E IS E / M O D E O F A C T IO N : D O P P E L T / D O U B L E E IN F A C H / S IN G L E
E IN G A N G /IN P U T : 0 / 4 - 2 0 m A
Z U L U F T /S U P P L Y : m a x . 6 b a r (9 0 p s i)
R E V .
U m g e b u n g s te m p e r a tu r : s ie h e B e d ie n u n g s a n le itu n g (1 )
A m b ie n t T e m p e r a tu r e : s e e In s tr u c tio n M a n u a l
S R I 9 8 6
S R I9 8 6 I-P P O S IT IO N E R / P O S IT IO N N E U R I-P
IN P U T / E N T R E E : 0 /4 ... 2 0 m A , 2 0 0 W
M a d e in F r a n c e b y E c k a r d t S A S , F - 6 8 3 6 0 S o u ltz
M a d e in F r a n c e b y E c k a r d t S A S , F -6 8 3 6 0 S o u ltz
I-P S T E L L U N G S R E G L E R / I-P P O S IT IO N E R IN T R IN S IC A L L Y S A F E / S E C U R IT E IN T R IN S E Q U E F O R / P O U R :
C L A S S I D IV IS IO N 1 G R O U P S A , B , C , D H A Z A R D O U S L O C A T IO N S
S R I S R I9 8 6 -
M O D E O F A C T IO N / M O D E D ´A C T IO N : S IN G L E / S IM P L E E F F E T R E V .
W IR K U N G S W E IS E / M O D E O F A C T IO N : D O P P E L T / D O U B L E E IN F A C H / S IN G L E D O U B L E / D O U B L E E F F E T
E IN G A N G /IN P U T : 0 / 4 - 2 0 m A IN A C C O R D A N C E W IT H F O X B O R O -E C K A R D T
Z U L U F T /S U P P L Y : m a x . 6 b a r (9 0 p s i) D R A W IN G D O K Z 5 3 4 3 9 6 1 1 9 E N T IT Y M A X . A M B . T E M P .:
R E V .
P T B 0 2 A T E X 2 1 5 3 , T y p A I 6 3 3 V m a x .= 4 0 V I m a x .= 1 5 0 m A C i = 0 L i = 0 F M T 6 : 6 0 °C / C S A : 4 0 °C
II 2 G E E x ia /ib IIB / IIC T 6 / T 4 ; A P P R O V E D W A R N IN G : S U B S T IT U T IO N O F C O M P O N E N T S M A Y IM P A IR IN T R IN S IC S A F E T Y
A V E R T IS S E M E N T : L A S U B S T IT U T IO N D E C O M P O S A N T S P E U T C O M P R O M E T T R E
0 1 0 2 U i = 3 0 V ; Ii = 1 5 0 m A ; C i = 0 n F ; L i = 0 m H ; L A S E C U R IT E IN T R IN S E Q U E
P i ,T e m p e r a tu r k la s s e , U m g e b u n g s te m p e ra tu r : s ie h e B e d ie n u n g s a n le itu n g (1 ) IN T R IN S IC A L L Y S A F E W H E N C O N N E C T E D T O C S A C E R T IF IE D S A F E T Y
P i ,T e m p e r a tu r e C la s s , A m b ie n t T e m p e ra tu re : s e e In s tr u c tio n M a n u a l (2 ) B A R R IE R P E R F O X B O R O -E C K A R D T D R A W IN G D O K Z 5 3 4 3 9 6 1 1 9
MI EVE0102 A-(en)
Page 4 FUNCTION SRI986
Function
The positioner operates according to the force com- Fig. 2: Single-acting electro-pneumatic positioner
parison principle: 5 4 5 5
The input current signal w flows through moving coil 51,
which is located in the field of a permanent magnet 52. 5 3
The resultant force exerts a torque on the balance arm 5 1 5 7
5 2
53.
This leads to a change in the distance between nozzle
54 and cone 55 which results in a change in the back
5 6
pressure at the nozzle. The Venturi 56, which is
Z u lu ft /
supplied with air, converts the back pressure into the
S u p p ly a ir
pressure signal w’ which is fed to the compensator 57.
4 6
An equilibrium of forces is set at balance arm 53 if the
torque produced by moving coil 51 is equal to the 5 8
torque reaction produced by compensator 57. 6 1
At the same time the pressure signal w’ is passed to Z u lu ft /
S u p p ly a ir
the input diaphragm 58. The stroke of the input 4 0
diaphragm is transferred to the flapper lever 40. The
resultant change in the distance between the nozzle 6 3 4 4
59 and the flapper 60 alters the back pressure at the
1 1
nozzle. This pressure acts in a single-acting
positioner on an amplifier 61. Its output pressure y
4 3 4 1
5 9
results in a stroke movement of diaphragm actuator
6 0
with spring resetting (see Fig. 2).
In the double-acting positioner this pressure acts on a 1 3
double-acting amplifier 62 , where opposed output 1 7 4 2
pressures y1 and y2 cause a stroke movement in the
diaphragm actuator without spring resetting (see Fig.
3). Fig. 3: Double-acting electro-pneumatic positioner
The stroke movement is tapped at the actuator spind- 5 4 5 5
le 63 of the feedback lever 11 and transferred to the
stroke factor lever 17. 5 3
The stroke factor lever 17 and the flapper lever 40 are 5 1
5 7
connected by the range spring 43. 5 2
Equilibrium of forces is set at the flapper lever 40 if the
torque produced at the input diaphragm 58 is equal to 5 6
Z u lu ft /
the torque reaction of the range spring 43 produced by
the stroke setting. Thus an actuator setting proportional
S u p p ly a ir 4 7
to the signal input is retained constantly.
A dynamic adaption to the actuator (sensitivity, stability) 4 8
6 2
can be accomplished by the throttling screw 44 and the
damping throttles 46, 47 and 48 in the double-acting
positioner, the stroke range and zero point are set via
the zero screw 41 and the stroke factor screw 42.
4 0 Z u lu ft /
A rising or falling actuator pressure at rising input signal 6 3 S u p p ly
is set in the single acting positioner by means of the 1 1 5 8
changeover plate 13. a ir
4 4
4 3 4 1
5 9
6 0 4 2
1 7
MI EVE0102 A-(en)
SRI986 ADDITIONAL EQUIPMENT Page 5
Additional Equipment
The air output capacity can be significantly increased, By means of a total of five range springs the positioner
and the positioning time shortened to 1/4 to 1/7, by can be matched to nearly all operating situations, such
means of an additional single acting or double acting as up to 4-way (or with 4 to 20 mA up to 3-way) range
volume booster. subdivision, very high and very short strokes and
angles of rotation or special cams. A standard range
Fig. 4: Single-acting positioner with volume booster
spring FES 628/1 is installed. Other range springs are
available (see page 16)
For attachment to rotary actuators and rotary armatures
an attachment kit for rotary movement (Code EBZG-PN,
-NN, -JN, -ZN) is required.
Fig. 7: Housing of the attachment kit
for rotary movement
2 3
If an indication of actuating pressure and supply air The electrical position transmitter assembly (Code E
pressure is desired for single-acting and double-acting or F, see page 26) converts the stroke or angle of
positioners, a connection manifold with gauges (Code rotation into an electrical standard signal 4 to 20 mA.
LEXG-JN, -MN, -RN) can be used. Fig. 9: Positioner with electrical position transmitter
Fig. 6: Connection manifold with gauges assembly
MI EVE0102 A-(en)
Page 6 MOUNTING SRI986
2 MOUNTING
2.1 Dimensions 5 2 4
2.1.1 Positioner
3 9 1 0 5 ,5
1 .5 4 4 .1 5
1 2 ,5 8 0
.4 9 3 .1 5
1 2 ,5
.4 9
1 .9 3
4 9
4 .0 6
1 0 3
m a x . 3 9
2 .0 5
5 2
m in . 4
1 1 4 ,5
4 .5 1
2 .8 3
7 2
3 .1 5
8 0
M 6
1 8 ,5
.7 3
2 4 2 2 2 2
.9 4 .8 7 .8 7
9
.3 5
3
.1 2
6 3
2 .4 8
6 7 8 9 1 0 6 ,7 ,8 3 1 2
1 Screwed gland (line entry) 6 Internal thread G 1/8 for output II (y2)
2 Dummy plug. Can be replaced with 1 (only on double acting positioners)
7 Internal thread G 1/8 for supply air
3 Earth connection 8 Internal thread G 1/8 for output I (y1)
4 Earth connection 9 Feedback lever
5 Terminals (+/–) for signal input (w) 10 Housing cover
Screw on the housing cover in such a way
I Ø = Correcting variable 1 (Output)
that the air vent of the attached device
Ú = Supply air
faces downwards!
II Ø = Correcting variable 2 (Output)
(only on double acting positioners)
1 3 2 6
6 5 ,5
2 .5 8
8 8 9 1
3 .4 6 3 .5 8
Comments see next page.
MI EVE0102 A-(en)
SRI986 MOUNTING Page 7
1 5 2 6
3 .4 3
8 7
1 0 4 1 0 8
4 .0 9 4 .2 5
1 0 4 8 3
4 .0 9 3 .2 7
4 1 3 2
1 Internal thread 1/4-18 NPT for supply air
6 2 Internal thread (not used)
2 8 ,5
1 .1 2
1 0
9 1
8 2
3
4 3 ,5
1 .7 2
6
7
7 0 1 0 2
2 .7 6 4 .0 2
MI EVE0102 A-(en)
Page 8 MOUNTING SRI986
2.2 Attachment kit for diaphragm actu- 2.2.2 Determination of mounting side
ators acc. to DIN IEC 534-6 (NAMUR) Single-acting diaphragm actuators
Check whether the actuator is in the safety position
required by the process.
The attachment kits include the following parts: (Does the actuator open or close with spring force?)
The mounting side is selected from the table below in
EBZG-KN: EBZG-HN: accordance with the direction of action and the requi-
Mounting bracket 10 Mounting bracket 10 red direction of movement of the spindle for an increa-
Feedb. lever EBZG-AN Feedb. lever EBZG-AN 11 sing input signal.
Carrier bolt 12 Carrier bolt 12
U-bolts 14 Mounting screw 19 A c tu a to r c lo s e s C h a n g e o v e r A c tu a to r o p e n s C h a n g e o v e r
w ith s p r in g fo r c e p la te s e ttin g w ith s p r in g fo r c e p la te s e ttin g
2.2.1 Dimensions
The arrow indicates the direction of movement of the
spindle at increasing input signal.
Mounting bracket 10 Code G
4 3
1 .6 9 The direction of action of the input signal can be set on
the changeover plate 13 (see page 31):
N = Normal direction of action (increasing input sig-
nal produces increasing control pressure to the
3 .5 4
9 0
actuator)
1 .6 9
4 3
actuator)
1 1
.4 3
1 0 2 1 0 2
4 .0 2 4 .0 2
Double-acting diaphragm actuators
For double-acting positioners the changeover plate 13
always stays in the “N” setting. The assignment of the
input signal to the direction of movement of the actuator
Feedback lever 11 with compensating spring 16
spindle is determined by the selection of the mounting
Code EBZG-AN
side of the positioner and the piping of the positioner
outputs to the actuator:
2 ,5
.1 0
.7 8
2 0
1 0
The positioner is mounted at the right-hand side.
.3 9
Code EBZG-BN 9 1
3 .5 8
If the actuator spindle is to retract with an increasing
input signal, output y1 is connected at bottom and
output y2 at top of the actuator.
The positioner is mounted at the left-hand side.
C h a n g e o v e r C h a n g e o v e r
p la te s e ttin g p la te s e ttin g
Carrier bolt 12
7 ,8 -0 ,0 5
.3 1 -.0 0 2
M 6
1 0
6 5 .3 9
2 .5 6
2.2.3 Attachment to diaphragm actuators Fig. 10: Attachment to diaphragm actuator with
Attachment of the positioner is made using the attach- cast yokes according to DIN IEC 534-6
ment kit for diaphragm actuators according to DIN (mounting side right) Code G
IEC 534-6 at right or left-hand side of the actuator.
6 3 ,5
2 .5 0
2 .1 9
5 5 ,5
c) Fasten positioner with mounting bracket 10 to the
diaphragm actuator.
1 0 ,4
.4 1
For diaphragm actuators with cast yokes:
Fasten mounting bracket 10 with screw 19 to the
threaded hole in the cast yoke (see Fig. 10). 1 1
This ensures that the feedback lever 11 is hori-
1 0 5 ,5
zontal at 50 % stroke.
4 .1 5
For diaphragm actuators with pillars:
fasten mounting bracket 10 with two U-bolts 14 to
the pillar in such a manner that feedback lever 11
which is loosely attached to the shaft 15 of the
Fig. 11: Attachment to diaphragm actuator with pillars
positioner and the carrier bolt 12 , is horizontal at according to IEC 534-6 (mounting
50 % stroke (see Fig. 11). side right) Code F 6 3 ,5
2 .5 0
d) Set actuator to a 0 % stroke position.
2 0 ... 3 5
Attach feedback lever 11 to shaft 15 of the .7 9 ... 1 .3 8
positioner and carrier bolt 12 in such a manner
that compensating spring 16 is above the carrier
1 .6 9
4 3
bolt 12 when the mounting side is on the right, or
below the carrier bolt 12 when the mounting side 1 4 1 5
5 5 ,5
2 .1 9
is on left (see Fig. 9).
Align and lock carrier bolt. 1 0
1 0 ,4
e) Press stroke factor lever 17 against stop screw .4 1
feedback lever.
f) Connect positioner output y1 to diaphragm actuator
for single-acting diaphragm actuators and connect
outputs y1 and y2 to diaphragm actuator for
double-acting diaphragm actuators. Fig. 12: Take-off point of the positioner
(mounting side left)
g) Set up electrical connections.
h) Connect supply air of min. 1.4 bar to max. 6 bar,
but no more than the maximum permissible
operating pressure of the diaphragm actuator.
i) Fasten housing cover in such a way that air
vent of attached device faces downwards
(see Mark ‘M‘ in Fig. 12).
11
12
M 16
MI EVE0102 A-(en)
Page 10 MOUNTING SRI986
1 4
.5 5
1 3 6 ,5
5 .3 7
M 6 x 1 4 (2 x )
6 2 ,5
2 .4 6
4 ,5
.1 8
D IN 9 1 2
.3 1
.1 6
8
6
.5 3
M 6 x 3 0 (2 x )
D IN 9 1 2 1 3 ,5
1 .1 0 + .0 2
2 8 + 0 ,5
.5 3
2 .3 6 .0 1
6 0 0 ,2
2 .9 5
7 5
5 0
1 .9 7
5
6,
6
.2
6 2 ,5
2 .4 6
M 6 x 1 4 (2 x )
1 7 6 ,5
6 .9 5
D IN 9 1 2
2 .7 6
M 6 x 3 0 (2 x )
7 0
D IN 9 1 2
.2 0
5
6
.2 4
.1 2
4 7
3
1 .8 5
5 4
.3 9
1 0
2 .1 3
6 3
2 .4 8
8 6
3 .3 9
Rotation angle max. 120°;
torque requirement 0.14 Nm
MI EVE0102 A-(en)
SRI986 MOUNTING Page 11
1 1
4 3
1 ,2
.0 5
1 3 6 ,5
5 .3 7
6 2 ,5
2 .4 6
M 6 x 1 4 (2 x )
.0 1
0 ,2
D IN 9 1 2
.5 9
1 5
M 6 1 4 ... 1 5 ,5
1 .1 8
.5 5 ... .6 1
3 0
1 6
.4 7
1 2
M 6 x 3 0 (2 x ) .6 3
D IN 9 1 2
5 0 M 6
1 .9 7
For all versions
Code EBZG-NN
3 .9 0
9 9
.4 7
1 2
2 .5 2
6 4
1 6 H 8
.6 3
1 6 7
6 .5 7
4 3 9 5
1 .6 9 3 .7 4
4 5 0 ,2
6 ,5 1 4 - 6 1 .7 7 .0 1
.2 6 .5 5 - .2 4
Code EBZG-PN
6 4
.4 7
1 2
3 .9 0
9 9
. 8. 8 7 7
2 2 22
6 .5 7
1 6 7
6 .5 7
MI EVE0102 A-(en)
Page 12 MOUNTING SRI986
Z u lu ft / S u p p ly a ir
Z u lu ft / S u p p ly a ir
c) Move actuator into the desired starting position
(rotation angle = 0°).
e) Fasten feedback lever 30 for the rotary actuator
d) Mount cam 24 in accordance with the direction of onto shaft 15 of positioner as shown in Fig. 16.
rotation of the actuator (see Fig. 14).
The linear cam is fastened to the actuator drive Fig. 16: Attaching feedback lever to the positioner
shaft in such a manner that the dimension x 1 5 3 0
or y (Fig. 15) amounts 2 mm, whereas
in case of equal percentage cam the dimension x
is approx. 17.5 mm, and the dimension y is approx.
21.5 mm.
In case of inverse equal percentage cam the
dimension x is approx. 18 mm, and the dimension
y is approx. 23 mm.
When employing equal percentage and the inverse
equal percentage cams, the range spring FES
627/1 must be installed in the positioner.
2 4 2 4
A B A B
% %
e q u a l p e rc e n ta g e in v e r s e e q u a l p e r c e n ta g e 3 2
3 1 3 0
MI EVE0102 A-(en)
SRI986 MOUNTING Page 13
Screw positioner to housing of attachment kit. With h) With single-acting actuators connect positioner out-
the linear cam and the inverse equal percentage put y1 to actuator; with double-acting actuators
cam check whether mark 33 points to the center of connect y1 and y2 to actuator.
the cam follower 32 (see Fig. 18); adjust if Connect chamber in which pressure is to build up
necessary. with an increasing input signal to y1.
With the equal percentage cam check whether the
cam follower lies directly ahead of the start of the i) Connect command variable w (input).
cam lobe; adjust if necessary.
k) Connect supply air of min. 1.4 bar to max. 6 bar
g) Final mounting of feedback lever on shaft of but do not exceed the maximum permissible
positioner is performed at a stroke of 0 %, i.e. a operating pressure of the actuator.
rotation angle of 0°. First loosen 5 mm A/F Allen
screw of feedback lever 30 through hole 34 (see Note !
Fig. 19), then press stroke factor lever 17 against If actuator moves to an end position, the mounting
stop screw 18 (see page 31) and tighten Allen position of cam does not coincide with the direction of
screw firmly. rotation of the actuator.
In this case install the cam 24 in the reverse position.
Fig. 18: Alignment of cam 24
2 4 2 4
I) Attach pointer 35 on the headed screw in such a
manner that 0° is indicated when the rotary
A B actuator is in its starting position (w = 0).
A B
m) Attach the transparent cover plate (see Fig. 20).
3 2 3 3 2 4
lin e a r
A B
% %
35
e q u a l p e rc e n ta g e
Single-acting actuator:
Move changeover plate (page 31, item 13) to ‘U"
setting and reverse cam 24 .
4.2 Setting of zero point and stroke 4.3 Setting the damping
(see page 31) (see page 31)
Before commencing settings press the flapper The air output capacity of the positioner can be reduced
lever 40 several times alternately to the left and by means of the damping throttle 46.
right in order to align the flappers correctly. Double acting positioners are equipped with a damping
a) Set the minimum value of the command variable w throttle 47 for correcting the variable y1 and a damping
(start of stroke). throttle 48 for correcting the variable y2.
In its normal setting the damping throttle is approxi-
b) Turn zero screw 41 until actuator just begins to mately flush with the amplifier housing.
move from its end position.
Note: The air output capacity is reduced by a factor of
In accordance with VDI/VDE 2174 a variation of approximately 2.5 when the damping throttle is turned
the stroke range up to 2 % is permissible in one of completely in.
the two end positions. It is advisable to take A reduction of the air output capacity should only be
advantage of this tolerance for the input signal done for very small actuator volumes since the control
range 0 to 20 mA by elevating the minimum value system would otherwise be too slow.
somewhat above 0 mA (approx. 0.1 mA; max. 0.4
Page 31, single-acting positioner: Setting gain 44
mA). This will ensure that the actuator completely
and damping 46
decompresses if necessary for safety reasons.
c) Set maximum value of the command variable w Page 31, double-acting positioner: Setting gain 44
(end of stroke). and damping 47, 48
corresponds to
curve (1-5) a
c) Loosen hexagon cap screw (A/F 10) of feedback The rotation angle factors Uϕ of the individual range
lever and turn stroke factor lever 17 away from springs are stated in the following table.
stop screw 18 . This applies pretension to range
spring 43 . In this position retighten hexagon cap The rotation angles are also taken into account in the
screw of feedback lever. graph of the range springs (see next page).
g) Set maximum value of command variable w (end For diaphragm actuators(1500 cm2) and actuators of
of stroke). other manufacturers (Io = 117.5 mm1)):
h) Turn stroke factor screw 42 until the actuator x = Io
precisely reaches its end position. Ux =
w Is
Note ! Is = Feedback lever length in mm
With this setting the zero point and stroke range are (for actuator 1500 cm2: Is = 122.5 mm)
mutually dependent. Settings e) to h) must therefore
be repeated as often as necessary until both settings The stroke factor can be used to determine for each
are correct. Furthermore it should be noted that application whether or with which spring the desired
the deflection of the stroke factor lever 17 from the setting can be made.
starting position may not exceed a maximum of 39°, Five different range springs are available for matching
since the stroke factor lever might otherwise hit the to the stroke and input signal range.
housing cover before reaching its end value.
4.6.1 Stroke factor ranges of the range springs d) Connect points determined at a) and c). This re- sults
The stroke factor Ux determined as described above in a straight line.
should lie within the ranges of the respective range
e) If the straight line does not run through the origin,
springs indicated in the following table, as close as
move this parallel here.
possible to the lower value.
f) Use the spring the characteristic line (a) of which is
4.6.2 Characteristics of the range springs located directly below the presently determined
The stroke xo is based on the standard feedback lever characteristic line.
Io=117.5 mm.
Example (shown in graph)
Fig. 23: Feedback lever Split range operation
Valve 1:
Is m in . = w = 0 to 10 mA
7 2 xs = 30 mm (stroke range)
2 .8 3 Io =
1 1 7 ,5
ls = 140 mm
Is m a x . =
4 .6 2
1 4 2
5 .5 9 117,5 . 30s
Xo = 25,2 mm
If another length (ls) is used, the actual stroke xs must 140
be converted to stroke xo
Intersection w = 10 mA with xo = 25.2 mm → S1
117,5 .
xs Selected: Spring 4 (FES 715/1) because the charac-
Xo = (mm) teristic curve based on the beginning of the determi-
ls
ned straight line located directly below.
Selection of measuring spring and setting of
measuring span Valve 2:
Determination of suitable spring for split range: w = 0 to 20 mA
xs = 50 mm (stroke range)
a) Enter desired set point value w for travel start in the
ls = 140 mm
diagram field.
b) Determine xo if Is unequal 117.5 mm. 117,5 . 50s
Xo = 42 mm
140
c) Enter intersection w/xo .
Intersection w = 20 mA with xo = 42 mm → S2
( T r a v e l) Selected: Spring 5 (FES 629/1) because the charac-
teristic curve based on the beginning of the determi-
ned straight line located directly below.
( S e tp o in t)
Lifting up of zero point for 4 ... 20 mA and split range 1) Io = standard feedback effective length
1a, 2a, 3a, 4a, 5a = stroke starting of the respective spring 2) For feedback effective length Is = 117.5 mm and w = 20 mA
1b, 2b, 3b, 4b, 5b = max. stroke 3) Theoretical value
MI EVE0102 A-(en)
Page 18 BASIC ADJUSTMENTS SRI986
5 MAINTENANCE
5.3.1 Removal of I-p converter (see Fig. 30) d) Reinsert the Venturi. Tighten the two screws 74
equally. If the base plate 76 has also been
a) Unscrew housing cover 68. dismantled, take care that the 3 O-rings and the
b) Unscrew shaft 69 with the 5 mm A/F Allen key filter are correctly positioned.
(turn to left), unhook range screw 43 and remove e) Check I-p converter and adjust, if necessary.
stroke factor lever 17.
c) Unscrew 4 cylinder head screws 70 and remove 5.3.4 Insert I-p converter and assemble the device
air vent plate 71. (see Fig. 30)
d) Unscrew the two Allen screws 72 (3 mm A/F) and a) Attach the I-p converter 65. Make sure that the
remove the I-p converter 65. electric lead is located along the bottom of the I-p
converter in the appropriate channel and that both
O-rings are in place.
5.3.2 Check and adjust I-p converter b) Screw on air vent plate 71. Put the electric lead 77
(see Fig. 28) around the shaft of the positioner 69 in such a way
that the functioning of the I-p converter is not
An adapter is required for checking and adjusting the
impaired.
I-p converter which can be done by yourself as shown
in Fig. 26. c) Hook in range spring 43 and screw shaft 69 to
stroke factor lever 17.
The following tools are required:
Screw driver, d) Screw on the housing cover 68 so that the air vent
3 and 5 mm A/F Allen keys, of the attached device faces downwards.
1 test gauge 0 to 1.4 bar,
1 DC signal generator 0 to 20 mA, Note:
Supply air 1.4 ± 0.1 bar. Basic adjustment and re-start-up (see page 14) are
a) Connect the I-p converter to the adapter, Fig. 26 necessary after dismantling the device or after
and wire as shown in Fig. 27. replacing components or modules.
b) Preset supply air 1.4 ± 0.1 bar.
c) The test gauge must read 0.18 to 0.19 bar at
current signal 0 mA. Otherwise set the adjustment
lever 73 so that this value is indicated. If this is not
possible, remove the Venturi 56 (see Fig. 29) and
clean it.
d) Increase the current signal slowly from 0 to 20 mA.
The test gauge reading must change
proportionately to the current signal.
Fig. 26: Test adapter for I-p converter Fig. 27: Test circuit for I-p converter
7 0
2 2 2 .7 5
.8 6
1 9 1 0
.7 4 .3 9 0 ... 1 .4 b a r
I-p c o n v e rte r
M 4 0 ... 2 0 m A w ith
a d a p te r
1 .0 2
2 6
O u tp u t
2 3 ,5
.9 2
1 .9 6
5 0
3
.1 1 S u p p ly a ir
.0 3
1
1 ,8 S u p p ly a ir
.0 7 1 . 4 +- 0 . 1 b a r
h o s e s
c o n n e c tio n s Fig. 29: Removal of the Venturi
8 5
.3 1 .1 9
4 1 ,5
1 .6 3
7 3
7 6
5 6
7 5
7 4
Fig. 30: Removal and reassembly of the I-p converter 65 and the booster 61
6 1 6 9 6 9
6 8 7 0 1 7 7 1 6 5 7 2 7 7
MI EVE0102 A-(en)
Page 22 SAFETY REQUIREMENTS SRI986
7 SAFETY REQUIREMENTS
x = 1 0 0 %
We recommend the following switch amplifiers:
Separating switch amplifier with relay output
Pepperl+Fuchs GmbH Type numbers:
Normal version WE 77 / Ex2
Safety version WE 77 / Ex-SH-03
For further information see P+F documentation.
x = 0 %
8.4 Start-up
X 0 % 1 0 0 %
The switching functions may be freely selected and
set. A
The control vanes may be adjusted as desired in or- B
der to reach the wanted switching behavior.
The illustration here shows the four basic settings
and adjacent the respective switch behavior X 0 % 1 0 0 %
(gray = immersed vane).
A
The examples are based on the following setting:
B
Mounting left=feedback level right; transmission is
selected so that at stroke x from 0 to 100%, the gui-
dance shaft travels through a rotary angle of 180°. X 0 % 1 0 0 %
Illustrated in resting position x = 0%.
A
2-wire technique: If control vane is immersed, the
B
initiator power circuit becomes high-Ohmic.
3-wire technique: If control vane is immersed, the
contact is closed against plus. X 0 % 1 0 0 %
2 3 2 3 8.6 Maintenance
2 4 2 4 No maintenance is required.
1 2 2 5
MI EVE0102 A-(en)
SRI986 LIMIT SWITCH KIT Page 25
5
1 1
1 0
4
1 4
3
2
1 5
5
1
Installation: 1 0
a) Screw on adapter 1:
Unscrew bottom screw 2.
Fit adapter 1, then screw in the
screw again and tighten slightly. 1 3
Hold adjusting device 3 firmly in position
and unscrew top screw 4. Install adapter 1 and 1 2
tighten the screw again. Tighten screws 2 and 4.
b) Screw in the two hexagonal bolts 5 (SW 8):
Long hexagonal bolt on the left,
short hexagonal bolt on the right.
c) Screw mounting plate 9 to the two hexagonal bolts 5
with the two screws 10 (if necessary, adjust the
adjusting devices so that the right-hand mounting
hole is accessible). Be careful to ensure that the e) Secure cable fitting 12
driving pin of the adapter engages in the slot in the and screw plug13 to frame 14
gear segment. with the enclosed nuts. Fit the frame
with the rubber seal facing the positioner
d) Screw the two bolts 11 into the female threads to
and cable fitting 12 at the terminal.
secure the housing cover. When the positioner is
installed, these will be the female threads in the top f) Screw on the housing cover with the air vent
left-hand corner and in the bottom right-hand corner. facing downwards when the device is mounted.
MI EVE0102 A-(en)
Page 26 POSITION TRANSMITTER SRI986
3 1 3 2
9.1 Function
The stroke or rotary angle of an actuator are trans- 6
mitted to the position controller with a built-in electrical
position converter via control lever. The angle setting
is converted proportionately into a voltage with a
potentiometer. This voltage then is converted into the
electric standard signal 4-20 mA. Adaption to the stroke
of the actuator takes place internally. The start and end
of the measuring range are set via 2 push buttons.
1 2
The terminals are suitable for wire cross-sections of up The power supply (Us = 12 to 36 V DC) originates from
to 2.5 mm². the signal circuit in two wire connection.
U S = 1 2 ... 3 6 V The maximum permissible load impedance RBmax
is calculated with the following equation:
1 1 K 1 RBmax = (Us – 12 V) / 0.02 A [Ohm]
K 2
R B Us = Supply voltage in V
1 2 K 3
m A
K 4
A Connected
n s c h l u ß g e r device
ä t in k l.
M e ß u m converter
Position fo rm e r L e(e.g.i t u n recorder,
g s w id e r s ta n d 9.4 Maintenance
( z controller,
. B . S c h r e etc.)
ib e r ) No maintenance is required.
MI EVE0102 A-(en)
SRI986 POSITION TRANSMITTER Page 27
9.5 Setting and Start Up of position Trouble Shooting of the position trans-
transmitter 4-20 mA mitter
The electronic connection of the position transmitter The components of the position transmitter are under
must be assured. Both LEDs are then light up. constant surveillance by the installed micro controller.
Errors are detected and indicated when both LEDs are
Adjusting the start of the measuring range (4 mA) off or both LEDs are parallel flashing at a fast
a) Move the actuator to the starting position. frequency.
b) Press push button S1 "Config Output 4 mA" longer In the event of a fatal error, e.g. potentiometer not
than 2 seconds. During this time LED 1 lights up. connected, an output current of more than 24 mA will
After 2 seconds both LEDs are light up again, the be shown in addition to the error indication given by
value for 4 mA is stored. the LEDs (fast flashing).
Adjusting the end of the measuring range (20 mA) In this case check the following:
a) Move the actuator to the end position. a) If the potentiometer is correctly connected to the
b) Press push button S2 "Config Output 20 mA" electronic board.
longer than 2 seconds. During this time LED 2 b) If the potentiometer is within its working span.
lights up. After 2 seconds both LEDs are light up
again, the value is stored. When both LEDs are off, the supply voltage should be
checked (minimum voltage, polarity).
Random adjustment of the current values at the
end points
a) Move the actuator to the end position, where you
want to adjust the current.
b) Press both buttons simultaneously for about 2
seconds. Then both LEDs are alternating flashing
in a slow frequency.
c) With push button S1 "Config Output 4 mA" the
output current value can be decreased and with
push button S2 "Config Output 20 mA" the output
current value can be increased.
Pressing the buttons for a short moment results in
a small change and pressing the button for a
longer time results in a fast mode for a bigger
change. The value of the current can be freely
decreased between about 3.3 and increased up to
22.5 mA.
d) Without any additional manipulations of the push
buttons, the new value is automatically saved.
After a few seconds, the device returns into the
normal operating mode, indicated by both LEDs
that are then light up again.
MI EVE0102 A-(en)
Page 28 POSITION TRANSMITTER KIT SRI986
4
1 4
3
2
1 5
5
1
Installation:
a) Unscrew lower screw 2 of stroke factor
adjustment facility 3.
b) Position driver plate 1, turning screw 2 again and
tighten gently.
1 3
c) Hold the stroke factor adjustment unit together
manually and remove upper screw 4. 1 2
Swivel in driver plate and return screw.
Tighten screws 2 and 4.
d) Screw in the 2 supports 5 Ø 7 mm as follows:
Longer support left,
shorter support right.
e) Secure converter plate 9 with screws 10 and a lock g) Secure cable screw connection 12 and screw plug
washer 20 (left screw) to the two supports so that the 13 to frame 14 using the nuts supplied. Position the
pin on the driver plate 1 engages into the slot on the frame so that the rubber seal faces towards the
tooth segment. position controller and so that the cable screw
connection 12 is next to the terminals.
f) Screw two supports 11 into the female thread for
securing the cover. In installation position, these are h) Screw on cover 15 so that the ventilation slot is at
the female threads in the top left corner and in the the bottom when the unit is attached.
bottom right corner.
MI EVE0102 A-(en)
SRI986 SAFETY REQUIREMENTS FOR OPTIONS Page 29
10 SAFETY REQUIREMENTS
FOR OPTIONS
Repair and maintenance operations with open housing Regulations for inductive Limit Switch
may only be performed by qualified personnel if any
voltage sources are connected to the device. This device fulfils the requirements stipulated in
The units must be used for their intended purpose and IEC 1010-1, Class III equipment.
connected in accordance with the connection diagram. The units may only be operated with safety extra-low
The locally valid national regulations relating to setting voltage SELV or SELV(E) (functional extra-low voltage
up electrical systems must be followed, e.g. in the with protective separation).
Federal Republic of Germany DIN VDE 0100 and DIN
VDE 0800.
Regulations for subsequent installation
Device may be grounded upon requirement.
The attachment of the inductive limit switch to the
The protective measures provided in the units can positioner is to be regarded as a modification to an
become ineffective if the unit is not used in accordance explosion-protected unit and is therefore permissible
with the operation instructions. only in accordance with the national legal regulations.
The technical design of the kit is the same as that of
Regulations for Position transmitter the certified version of a positioner with a built-in option
The attachment of the position transmitter with the Id inductive limit switch Type BIB663 + BIB633 K,
No. EW 420 661 054 and EW 420 661 063 to the PTB-Nr. Ex-87.B.2010.
positioner is to be regarded as a modification to an The following applies to the Federal Republic of
explosion-protected unit and is therefore permissible Germany: The attachment must be certified by an
only in accordance with the national legal regulations. approved expert as a modification in accordance with
The technical design of the kit is the same as that of §9 ElexV.
the certified version of positioners with a built-in option
electrical position transmitter.
Regulations for Limit Switch with Micro Switches
The following applies to the Federal Republic of This device fulfills the requirements stipulated in
Germany: In accordance with§9 ElexV, the attachment IEC 1010-1, Class II equipment, Contamination level 2
must be certified by an approved expert. and over voltage category II.
MI EVE0102 A-(en)
Page 30 TROUBLE SHOOTING SRI986
11 TROUBLE SHOOTING
36 37 35 38 37 36
MI EVE0102 A-(en)
SRI986 ITEMS Page 31
61 46 44 45 78
40
13
70 43 18 17 42 41 7 70 37
61 44 45 47 48 67
MI EVE0102 A-(en)
Page 32 SRI986
Schneider Electric Systems USA, Inc. Global Customer Support Copyright 2010-2019 Schneider Electric
38 Neponset Avenue Inside U.S.: 1-866-746-6477 Systems USA, Inc. All rights reserved.
Foxboro, MA 02035 Outside U.S.:1-508-549-2424
United States of America https://pasupport.schneider-electric.com **Schneider Electric is a trademark** of
http://www.schneider-electric.com Schneider Electric Systems USA, Inc., its
subsidiaries, and affiliates. All other trademarks
are the property of their respective owners.