E-Line KB

Busbar Systems

EAE ELEKTRÝK A.Þ.

TSE - ISO
EN - 9000
CERTIFICATE NO
450/97

800 A.....6000 A
R

KB 800...6000 A KO 160...800 A KM 63...100 A KA 25...32 A TB 100 A DL 25...40 A

E-Line Busbar Systems 25 A......6000 A

Universal Cable Trays

Modular Enclosures

D-Line Under floor Ducting System

Lighting Fixtures Sunshine/ Starlight/ Starlux/ Plug-in Light/ Echolight 58W

EAE ELEKTRÝK A.Þ.


Ýkitelli Organize Sanayi Bölgesi
Turgut Özal Cad. Haseyad No:112
34670 Ýkitelli / Ýstanbul / TURKEY
Tel.: (0.212) 549 23 02 (9 Line)
Fax: (0.212) 549 23 10

Http://www.eae.com.tr
E-mail: electric@eae.com.tr P-Line Parapet Cable Distribution Systems
E-Line KB R

Contents

Introduction 2-3

Design & Horizontal 4


Distribution
i
er
riy
ba
ýn
ng
Ya

Design & Vertical 5

Genleþme Modülü
( 70 cm. )
ý
ktas
No

Distribution
kýþ
Çý
2.
tusu
Ku
kýþ
Çý
-Ýn ý
Plug ktas
No
kýþ
Çý

B
1.
Alüminyum Ýletken

Çýkýþ Yükseklikleri

Özel Boyda Plug-Ýn Busbar


KBA 800 1000 1250 1600 2000 2500 3000 4000

( h ) Kat Yüksekliði ( cm. )


Standartlar IEC 439-1, IEC 439-2
Ýzolasyon Gerilimi V IEC 664-1/1000V

A
Frekans Hz 50/60 Hz
Koruma Sýnýfý IP 42 (aksesuarla IP 54) ý
ktas
Anma Akýmý A 800 1000 1250 1600 2000 2500 3000 4000 No

Technical Characteristics 6-7


Ek
Kýsadevre (Dinamik) kA 105 105 105 220 220 220 264 264 ar
sb
Bu
Kýsadevre (1 sn.) kA rms 50 50 50 100 100 100 150 150
Direnç R mW/m 0,057 0,043 0,034 0,029 0,021 0,017 0,014 0,011
Endüktif Reaktans XL mW/m 0,031 0,026 0,019 0,016 0,013 0,010 0,009 0,006
Empedans Z mW/m 0,065 0,050 0,039 0,032 0,025 0,020 0,017 0,013
L1, L2, L3 mm² 525 700 910 1050 1400 1820 2100 2730
N mm² 525 700 910 1050 1400 1820 2100 2730 (a
) Dö
Aðýrlýk - Feeder, Bolt-on kg/m 16 19 22 29 36 44 53 62 þe
me
Aðýrlýk - Plug-in kg/m 17 20 23 31 38 46 56 65 Ka
lýn
Ýletken Boyutu mm 7x75 7x100 7x130 2(7x75) 2(7x100) 2(7x130) 3(7x100) 3(7x130) lýð
ý(
cm
.)

BUSBAR

Order Code System 8 ÝLETKEN CÝNSÝ


BUSBAR ANMA AKIMI
KORUMA SINIFI
TÝPÝ
MODÜL ÝSMÝ

KB A 16 0 0 - T R 4

Standard Components 9

Elbows 10

Standard Components 14

Flexibles / Expansions 15

Panel Connections 16-17

Transformer Connections 18-19

Tap-off Boxes 20-21

Feeder Boxes 22

Selection Feeder Boxes 23

Fixing Elements 24-25

Determination of 26
Special Length

Certificates 27-28
E-Line KB R

Introduction

EAE Electric manufactures, designs and provides Fast, flexible engineering


a wide range of busbar systems from 25 A to 6000 A The large number of tap-off points makes it possible
busbar systems have many advantages over wire to engineer the power supply systems at an early stage,
and conduit. even before the final disposition of loads is known.

Lower total installed cost Flexible power supply


Busbar material costs are often equal or less than Tap-off points at short intervals make electrical power
wire and conduit. available in all locations; the power supply can be
adapted to different production processes simply by
Lower life cycle cost relocating the tap-off unit.
Busbar components can be added, deleted or relocated
after the initial installation, saving time and money. E-Line Busbar Systems; conform to EN standards
and are tested according to EN 60439-2 (200).
Predictable characteristics
Busbar systems conform to common standards.
Readily published characteristics on busbar
short-circuit ratings, voltage drops, weights and
dimensions can be used.

Wire Systems

E-Line Busbar System

2
E-Line KB R

Technical Features

Housing, sheet metal


General
The perfect design for high current busbar systems Conductors (Al, Cu)
Tin plated
is the "compact structure" where tin plated, insulated
conductors are tightly placed into the sheet metal
housing (Figure 1).

Figure 1

One bolt joint ensures safety and


easy installation
Insulator layers
E-Line KB busbars are installed by tightening the
"one bolt joint". Belleville spring washers on both ends
of the bolt retains the original contact pressure, ensuring
a more secure, reliable and maintenance - free joint.
E-Line busbar systems are easily installed (Figures 2-3).

* The bolt is tightened to 80 Nm (60 lbft) using the torque spanner.

Figure 2
Heat Transfer Insulators
"In compact structure" there is no empty space filled with
air and heat is easily transferred to the environment by the
housing that works like a heat-shink (Figure 4).
Figure 3

High Short-Circuit Endurance


As there are no support points in "compact structure"
50

60

momentum levers are not formed.


This feature ensures high short-circuit endurance.

80Nm
Torqu Spanner (60lbft)

Minimum Voltage Drop


In E-Line KB, inductive reactance is very low due to
closely placed conductors (Figures 1-4).
The voltage drop comparison of compact and ventilated
busbar that have same cross sectional area prove
the importance of the compact structure (Figure 5).
L1
L2
L3
N
Standard Prefabricated Structure Figure 4
E-Line KB busbar system can be adapted to
any kind of building structure using.
Space-saving prefabricated components.
All necessary components and fitting elements
PE
are manufactured items.

* Special components can be manufactured in one week on request.


Voltage Drop

Ventilated Busbar
13,3 Section: 700 mm²
No Need For Fire Barrier I: 1000A
cosj:0,8

There is no risk of chimney effect in E-Line KB's 9 KBA1000 Busbar


compact structure. Internal fire barriers are not needed. Section: 700 mm²
6

0 Line length (m)


50 m 100 m
Figure 5

3
E-Line KB R

Design & Horizontal Distribution

While designing an electrical distribution Rated Current


system with E-Line KB a few approximate The current is calculated using the following equation:
details will be necessary.
P.a
Location, number, type and approximate ratings IB =
of loads, Ö3.U.cos j
Transformer rates and short-circuit capacities, IB = Operation current (A)
Utilization factor=a, P = Installed load (W)
System coordination with other distribution system a = Utilization factor
(heat, water, etc ), U = Supply voltage (V)
Determining the route of E-Line KB on layout,
If necessary, coordination of E-Line KB Busbar with
E-Line KO runs, Busbar current rating is chosen as equal to or higher
Deciding on suitable hanger types.
then the calculated IB current.
After the voltage drop calculation if the chosen
Utilization Factor (a)
current rate is not convenient, a higher rating is
Utilization factor (a) depends on the type and
number of loads. chosen.
It is usually around 0.7 or lower. The utilization factor
of a line that supplies electricity to motors and lighting Short-Circuit
systems is usually lower than 0.6. Tested short-circuit capacities are given on technical
It is as low as 0.30 in weld shops of car factories, characteristics table on pages 6-7.
a can be 1 in lines where only one big load is supplied.
Busbar Installation Plan
Voltage Drop Our distributor's project & design departments
For practical voltage drop calculation, necessary will help you for preparing the installation plans on
values, formula and easy calculation methods are request.
given on the technical characteristics table on pages 6-7.

Components List
Item Components Quantity

1 KBA 2050 - STD Busbar (20 x 3m.) 60 m.


8 pc. KBB 1650 2 KBA 2050 - D Downwards Elbow 2 pc.
6 pc. KBB 2550
3 KBA 2050 - R Right Elbow 1 pc.
4 KBA 2050 - U Upwards Elbow 1 pc.
4 KBA 2050 - L Left Elbow 1 pc.
4 KBA 2050 - P11 Panel Connection 1 pc.
5 KBA 2050 - S10 End Closer 1 pc.
6 KBA 2050 - X85 Special Straight Length 1 pc.
54 m. (18 pc. x 3 m.)
KBA 2050 7 KBA 2050 - X105 Special Straight Length 1 pc.
8 KBA 2050 - X107 Special Straight Length 1 pc.
9 KBA 2050 - X176 Special Straight Length 1 pc.
10 KBA 2050 - X142 Special Straight Length 1 pc.
11 KBB 1650 Tap-off Box 8 pc.
12 KBB 2550 Tap-off Box 6 pc.

Company : Yener Tekstil


Project : Çorlu Tesisleri
Project No : 0120
Prepared by

Name : Ercan Yýldýz


Date : 18 / 10 / 1994
Signature:

Project Sample

4
E-Line KB R

Design & Vertical Distribution

As each building's structure is different than the other


Line end
for vertical applications of E-Line KB special projects
has to be designed.
The details on this page briefly explain the necessary a= ......
information for drawing a vertical application project.

er
a rri
eB
Fir

a= ...... 10. Floor

h= ......
I14

a= ...... 9. Floor
Vertical Expantion
( 70 cm. )

h= ......
I13

8. Floor
lug a= ......
.P
2th

h= ......
x
Bo
off I12
( h ) Height of store measured from ceiling to ceiling ( cm. )

-
T ap
g-in a= ...... 7. Floor
Plu
lug

h= ......
.P
1th
B

I11
Special Length Plug-in Busbar

a= ...... 6. Floor
Tap-off Point

h= ......
I10

a= ...... 5. Floor
A

h= ......
I9
t I8
oin a= ...... 4. Floor
rJ
s ba
Bu
h= ......

I7
I6
a= ...... 3. Floor
h= ......

I5

(a a= ...... 2. Floor
)C
eil
ing
h= ......

thi
ck
ne I4
ss
(c
m. a= ...... 1. Floor
)
h= ......

Project Design I3

a= ...... Ground Floor


The details below should be sent to our
N
h= ......

Project & Design department. …


11 I2
10
Location and dimensions of the floor penetration 9
a= ...... 1. Basement
where busbar will be installed. 8
7
h= ......

Number, height and ceiling thickness of storeys. 6


5
(a=..., h=...) I1
4

Connected load for each storey. 3


a= ...... 2. Basement
2
Supply type of the vertical line (busbar or cable). 1
h= ......

Enterance Feeder side,


Basement
cable or busbar
Please send the information to us by fax or e-mail
with a sample drawing like the sample (Figure 1). 3. Basement
Busbar System Cable System
Figure 1

5
E-Line KB R

Technical Characteristics
Aluminium Conductor - KBA
Rated Current In A 800 1000 1250 *1600 1600 2000 2500 *3050 3100 4000 *4250

Busbar Code 08 10 12 13 16 20 25 27 30 40 41
Standards IEC 60439-2: 2000

Rated Insulation Voltage Ui V 1000

Rated Operational Voltage Ue V 1000

Rated Frequency f Hz 50 / 60

Protection Degree IP 55

Short-circuit (1 sec) Icw kA rms 50 50 50 50 100 100 100 100 120 120 120

Short-circuit (peak) Ip kA 105 105 105 105 220 220 220 220 264 264 264
Short-circuit Value
of Neutral Conductor (1 sec) Icw kA 30 30 30 30 60 60 60 60 72 72 72
Short-circuit Value kA
of Neutral Conductor (peak) Ip 63 63 63 63 132 132 132 132 158,4 158,4 158,4
Short-circuit Value kA
of Protective Circuit (1 sec) Icw 30 30 30 30 60 60 60 60 72 72 72

Short-circuit Value kA
of Protective Circuit (peak) Ip 63 63 63 63 132 132 132 132 158,4 158,4 158,4

20
R 20°C R 20 mW/m 0,055 0,041 0,032 0,026 0,028 0,021 0,016 0,013 0,014 0,011 0,009

Direct Current Resistance R mW/m 0,061 0,047 0,039 0,030 0,034 0,024 0,015 0,014 0,014 0,012 0,010

Empedance Z mW/m 0,076 0,055 0,044 0,038 0,037 0,027 0,021 0,017 0,018 0,014 0,012
Losses at Rated Current I²R1 W/m 128,6 162,0 201,6 268,8 299,5 348 318,8 474,4 461,3 655,3 596,1
Resistance (at Rated Current, mW/m
at Steady State Op. Temp.) R 1 0,067 0,054 0,043 0,035 0,039 0,029 0,017 0,017 0,016 0,014 0,011
Reactance mW/m
(at Rated Current) X1 0,045 0,030 0,020 0,023 0,016 0,014 0,014 0,010 0,011 0,006 0,006

Impedance Z1 mW/m 0,085 0,065 0,048 0,043 0,042 0,032 0,024 0,022 0,022 0,016 0,014
(at Rated Current)
L1, L2, L3, N mm² 525 700 910 1120 1050 1400 1820 2240 2100 2730 3360

PE (for 5 conductors) mm² 525 700 910 1120 1050 1400 1820 2240 2100 2730 3360

PE (for 4 ½ conductors) mm² 262,5 350 455 560 525 700 910 1120 1050 1365 1680
Housing Cross Section
(Sheet Metal) mm² 918 968 1028 1088 1836 1936 2056 2176 2904 3084 3264

Conductor Size mmxmm 7x75 7x100 7x130 7x160 2(7x75) 2(7x100) 2(7x130) 2(7x160) 3(7x100) 3(7x130) 3(7x160)

Weight - 4 Conductors kg/m 16 19 22 24 29 36 44 46 53 62 70

Weight - 5 Conductors kg/m 17,5 21 24,5 27 32 40 49 51 59 69,5 79


(1)
Fault Loop
Resistance (R0 PH-N) R0 mW/m 0,1313 0,1035 0,0779 0,0694 0,0711 0,0528 0,0412 0,0364 0,0373 0,0306 0,0248
(1)
Fault Loop mW/m
Reactance (X PH-N) X 0,1311 0,1063 0,0843 0,0707 0,0730 0,0569 0,0525 0,0416 0,0456 0,0397 0,0450
(1)
Fault Loop mW/m
Impedance (Z0 PH-N) Z0 0,1880 0,1502 0,1163 0,0999 0,1034 0,0789 0,0674 0,0561 0,0596 0,0508 0,0515
(1)
Fault Loop mW/m
Resistance (R0 PH-PE) R0 0,3279 0,2865 0,2488 0,2133 0,1785 0,1529 1255 0,1121 0,1041 0,0933 0,0858
(1)
Fault Loop X mW/m 0,2934 0,2549 0,2138 0,1822 0,1639 0,1344 0,1104 0,0935 0,0948 0,0839 0,0738
Reactance (X PH-PE)
(1)
Fault Loop mW/m
Impedance (Z 0 PH-PE) Z0 0,4400 0,3835 0,3280 0,2806 0,2423 0,2037 0,1672 0,1460 0,1408 0,1255 0,1132
(1)
Measurements and calculations of fault-loop circuit is done according to EN 60439-2 appendix N2b.
* New product group a
Load Distribution Factor
Voltage Drop Calculation F= Supply
L L= Load 1.00
Voltage drop of a busbar system can be calculated with the
F L
following formula taking into account the "a" load distribution constant.
F= Supply
-3 L1,L2,L3,L4 0.50
DV=aÖ3.L.I.(R.Cosj+X1 .Sinj) 10 V F L1 L2 L3 L4 Load

F= Supply
DV = Voltage Drop (V) L1,L2 0.25
a = Load Distribution Constant L1 F L2 Load

L = Line Length (m)


F= Supply
I = Line Current (A) L1,L2,L3,L4 0.125
L1 L2 F L3 L4 Load
R = Resistance (mW/m)
X1 = Inductive Reactance (mW/m) F= Supply
Cosj = Load Factor L1,L2,L3,L4 0.25
F L1 L2 L3 L4 F Load
Note: a constant is on amperic value.

6
E-Line KB R

Technical Characteristics
Copper Conductor - KBC
Rated Current In A 1000 1250 1600 *2000 2000 2500 3000 *4000 4000 5000 *6000

Busbar Code 10 12 16 19 20 25 30 39 40 50 60
Standards IEC 60439-2: 2000

Rated Insulation Voltage Ui V 1000

Rated Operational Voltage Ue V 1000

Rated Frequency f Hz 50 / 60

Protection Degree IP 55

Short-circuit (1 sec) Icw kA rms 50 50 50 50 100 100 100 100 120 120 120

Short-circuit (peak) Ip kA 154 154 154 154 220 220 220 220 264 264 264
Short-circuit Value
of Neutral Conductor (1 sec) Icw kA 30 30 30 30 60 60 60 60 72 72 72

Short-circuit Value kA
of Neutral Conductor (peak) Ip 63 63 63 63 132 132 132 132 158,4 158,4 158,4

Short-circuit Value kA
of Protective Circuit (1 sec) Icw 30 30 30 30 60 60 60 60 72 72 72

Short-circuit Value kA
of Protective Circuit (peak) Ip 63 63 63 63 132 132 132 132 158,4 158,4 158,4

20
R 20°C R 20 mW/m 0,034 0,026 0,020 0,016 0,017 0,013 0,010 0,008 0,009 0,007 0,005

Direct Current Resistance R mW/m 0,046 0,033 0,026 0,018 0,021 0,016 0,013 0,008 0,012 0,009 0,006

Empedance Z mW/m 0,054 0,041 0,033 0,023 0,025 0,021 0,017 0,011 0,014 0,010 0,007
Losses at Rated Current I²R1 W/m 159,0 173,4 222,7 300 276 337,5 378,0 528 624,0 750,0 756

Resistance (at Rated Current, R mW/m 0,053 0,037 0,029 0,025 0,023 0,018 0,014 0,011 0,013 0,010 0,007
at Steady State Op. Temp.) 1

Reactance X1 mW/m 0,031 0,025 0,020 0,015 0,015 0,014 0,010 0,007 0,008 0,005 0,004
(at Rated Current)
Impedance Z1 mW/m 0,059 0,046 0,036 0,029 0,028 0,023 0,018 0,013 0,016 0,012 0,008
(at Rated Current)
L1, L2, L3, N mm² 525 700 910 1120 1050 1400 1820 2240 2100 2730 3360

PE (for 5 conductors) mm² 525 700 910 1120 1050 1400 1820 2240 2100 2730 3360

PE (for 4 ½ conductors) mm² 262,5 350 455 560 525 700 910 1120 1050 1365 1680
Housing Cross Section
(Sheet Metal) mm² 918 968 1028 1088 1836 1936 2056 2176 2904 3084 3264

Conductor Size mmxmm 7x75 7x100 7x130 7x160 2x(7x75) 2(7x100) 2(7x130) 2(7x160) 3(7x100) 3(7x130) 3(7x160)

Weight - 4 Conductors kg/m 28 36 44 52 54 70 86 102 104 128 152

Weight - 5 Conductors kg/m 33 42 52 60 64 82 102 118 122 152 187


(1)
Fault Loop
Resistance (R0 PH-N) R0 mW/m 0,0885 0,0685 0,0545 0,0416 0,0448 0,0345 0,0301 0,0218 0,0204 0,0223 0,0149
(1)
Fault Loop mW/m
Reaktance (X PH-N) X 0,1260 0,0995 0,0917 0,0707 0,0748 0,0589 0,0506 0,0416 0,0399 0,0372 0,0450
(1)
Fault Loop mW/m
Impedance (Z 0 PH-N) Z0 0,1565 0,1225 0,1077 0,0820 0,0880 0,0688 0,0594 0,0470 0,0451 0,0437 0,0474
(1)
Fault Loop mW/m
Resistance (R0 PH-PE) R0 0,2956 0,2489 0,2070 0,1493 0,1414 0,1234 0,1209 0,0785 0,0954 0,0897 0,6006
(1)
Fault Loop X mW/m 0,2905 0,2401 0,1898 0,1822 0,1446 0,1162 0,1074 0,0935 0,1021 0,0803 0,0738
Reactance (X PH-PE)
(1)
Fault Loop mW/m
Impedance (Z0 PH-PE) Z0 0,4145 0,3459 0,2809 0,2355 0,2024 0,1695 0,1618 0,0122 0,1399 0,1204 0,0951
(1)
Measurements and calculations of fault-loop circuit is done according to EN 60439-2 appendix N2b.
* New product group a
Load Distribution Factor
Voltage Drop Calculation F= Supply
L L= Load 1.00
Voltage drop of a busbar system can be calculated with the
F L
following formula taking into account the "a" load distribution constant.
F= Supply
-3 L1,L2,L3,L4 0.50
DV=aÖ3.L.I.(R.Cosj+X1 .Sinj) 10 V F L1 L2 L3 L4 Load

F= Supply
DV = Voltage Drop (V) L1,L2 0.25
a = Load Distribution Constant L1 F L2 Load

L = Line Length (m)


F= Supply
I = Line Current (A) L1,L2,L3,L4 0.125
L1 L2 F L3 L4 Load
R = Resistance (mW/m)
X1 = Inductive Reactance (mW/m) F= Supply
Cosj = Load Factor L1,L2,L3,L4 0.25
F L1 L2 L3 L4 F Load

7
E-Line KB R

BUSBAR TYPE
Order Code System CONDUCTOR TYPE
BUSBAR CODE
PROTECTION DEGREE
UTILIZATION TYPE
UNPAINTED / PAINTED
COMPONENT

KB A 16 5 0 TR41

Busbar Type Standard Length STD


Special Length X
Upwards Elbow U
Downwards Elbow D
Aluminium ( Al ) A CONDUCTOR TYPE Right Elbow R
Copper (Cu) C Left Elbow L
Upwards Vertical Offset UV
Downwards Vertical Offset DV
Al Cu Conductor
Right Horizontal Offset RH
Conductor Conductor Size
Left Horizontal Offset LH
Rated Busbar Rated Busbar Right Upwards Combined Offset KRU
Current Code Current Code
Left Upwards Combined Offset KLU
800 08 1000 10 7x75
Right Downwards Combined Offset KRD
1000 10 1250 12 7x100
BUSBAR
Left Downwards Combined Offset KLD
1250 12 1600 16 7x130
* 1600 *2000 CODE Upwards Right Combined Offset KUR
13 19 7x160
1600 16 2000 20 2x(7x75
Upwards Left Combined Offset KUL
2000 20 2500 25 2x(7x100) Downwards Right Combined Offset KDR
2500 25 3000 30 2x(7x130) Downwards Left Combined Offset KDL
* 3050 27 *4000 39 2x(7x160) Left Side Feeder "T" TYL
3100 30 4000 40 3x(7x100) Right Side Feeder "T" TYR
4000 40 5000 50 3x(7x130) Central Feeder "T" TO
* 4250 41 *6000 60 3x(7x160) Horizontal Expansion YDT
Vertical Expansion DDT
* New product group
Reduction RD
End Closer S10
PROTECTION DEGREE COMPONENTS End Closer S11
IP 55 5
Panel Connection P10
Panel Connection P11
Upwards Panel Connection PU20
Upwards Panel Connection PU21
Conductors
4 5 4+½ Downwards Panel Connection PD20
Bolt-on 0 3 6 TYPE* Downwards Panel Connection PD21
Plug-in 1 4 7 Right Panel Connection PR30
Fedeer 2 5 8 Right Panel Connection PR31
Left Panel Connection PL30
Left Panel Connection PL31
Transformer Connection TR11
Unpainted - Upwards Transformer Connection TU21
Painted B Downwards Transformer Connection TD21
Transformer Connection TR31
Transformer Connection TR41
Right Transformer Connection TR51
Left Transformer Connection TL51
Flexible F
*TYPE Utilization Type Feeder Box B10
Feeder Box B11
Feeder Box B20
Feeder Box B21
Bolt-on Energy is suplied
from the joints.

Plug-in Energy is supplied either


from the joints or the
plug-in points.

Feeder Used where there is no need


to use tap-off boxes.

8
E-Line KB BUSBAR TYPE
R

CONDUCTOR TYPE
Standard Straight Length BUSBAR CODE
PROTECTION DEGREE
TYPE
UNPAINTED / PAINTED
COMPONENT

KB
Bolt-on
Bolt-on Bolt-on
L1
L2
L3
Bolt-on
N
3000
0
Electrical energy up to 800 A can be Sample Order:
supplied from the joints of bolt-on type 3000 A, Copper, Bolt-on,
by bolt-on tap-off boxes. IP 55, 4 Conductors
KBC 3050 - STD L1
As feeder or sub-feeder line, L2
L3
Where a load has to be supplied N
from the busbar.

Plug-in

Bolt-on Plug-in Plug-in Bolt-on


L1
L2 1
L3 Plug-in
N
950 1100 950
3000
Sample Order:
2000 A, Copper, Plug-in,
Electrical energy up to 800 A can be 950
IP 55, 4 Conductors
supplied from the joints and up to 400 A
can be supplied from the plus. KBC 2051 - STD L1
L2 0
L3 110 3000
N
In application of bolt-on
As vertical feeder line high rise buildings 950
For frequent energy supply

Feeder
L1 N
L2 L3
L3 L2
N L1
3000
2 Feeder

For applications where there is no need


to use tap-off boxes. Sample Order:
2500 A, Aluminium,
L1
Transformer - panel connections Feeder, IP 55, 4 Conductors L2
L3
00

Main panel - sub-panel connections


00

KBA 2552 - STD


00
33

N
Generator, composition supplies

Busbar cross-section dimesions


Al Cu
A
Conductor Conductor
Rated Busbar Rated Busbar
(mm)
Current Code Current Code
800 08 1000 10 130
1000 10 1250 12 155
1250 12 1600 16 185
* 1600 *2000
Special Straight Length
13 19 215
1600 16 2000 20 250 X
2000 20 2500 25 300 Special Straight
Length in (cm)
2500 25 3000 30 360 Sample Order:
* 3050 27 *4000 39 420 2000 A, Copper, Feeder, IP 55,
3100 30 4000 40 445 4 Conductors, 147 cm L1
X

L2
4000 40 5000 50 535 KBC 2052-147 L3
N
* 4250 41 *6000 60 625
Minimum Length = 35 cm
* New product group

9
E-Line KB BUSBAR TYPE
CONDUCTOR TYPE
Elbows BUSBAR CODE
PROTECTION DEGREE
TYPE
UNPAINTED / PAINTED
COMPONENT

KB

- U Upwards Elbow

400
325
Sample Order:
3000 A, Copper, Bolt-on, L1
L2
IP 55, 4 Conductors L3
N
KBC 3050-U 5
32
0
40

0
40
5
- D Downwards Elbow 32

L1

400
L2
Sample Order:

325
L3
3000 A, Copper, Bolt-on, N
IP 55, 4 Conductors
KBC 3050-D

- L Left Elbow

A
B

Sample Order:
2000 A, Aluminium, Bolt-on,
IP 55, 4 Conductors
KBA 2050-L L1
L2
L3
B

Al Cu - R Right Elbow
A B
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm)
Current Code Current Code Sample Order:
A
A

800 08 1000 10 420 355 2000 A, Aluminium, Bolt-on,


B

1000 10 1250 12 445 367 IP 55, 4 Conductors


1250 12 1600 16 475 383 KBA 2050-R
* 1600 13 *2000 19 505 398
1600 16 2000 20 540 415 L1
L2
2000 20 2500 25 590 440 L3
N
2500 25 3000 30 650 470
* 3050 27 *4000 39 710 500
3100 30 4000 40 735 512
4000 40 5000 50 825 558
* 4250 41 *6000 60 915 603
* New product group Please call us for non-standard components.

10
E-Line KB BUSBAR TYPE
CONDUCTOR TYPE
Elbows BUSBAR CODE
PROTECTION DEGREE
TYPE
UNPAINTED / PAINTED
COMPONENTS

KB

X=min:20 cm, Left Horizontal Offset


max: *Please see table
A B
Sample Order:
X=60 cm, 3000 A, Copper
Bolton, IP 55, 4 Conductors

KBC 3050-LH60 - LH
x X
(cm)

B
A
L1
L2
L3
N

X=min:20 cm, Right Horizontal Offset


max: *Please see table
X
Sample Order: A
X=60 cm, 3000 A, Copper B
Bolton, IP 55, 4 Conductors

KBC 3050-RH60 - RH
x B
(cm)
A

L1
L2
L3
N

0
40
5
32

Y=min:15 cm / max:64 cm Upwards Vertical Offset


Sample Order:
Y=45 cm, 2000 A, Aluminium
Bolt-on, IP 55, 4 Conductors
Y

KBA 2050-UV45 - UV
Y
(cm)
L1
L2
L3
N
5
32
0
40
Al Cu
A B X
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm) (cm)
Current Code Current Code
0
800 08 1000 10 420 355 70 40
1000 10 1250 12 445 367 73 5
32
1250 12 1600 16 475 383 76 Downwards
* 1600 13 *2000 19 505 398 78 Vertical Offset
Y=min:15cm / max:64 cm
1600 16 2000 20 540 440 82 Sample Order:
2000 20 2500 25 590 470 87 Y=45 cm, 2000 A, Aluminium
2500 25 3000 30 650 513 93 L1
Bolt-on, IP 55, 4 Conductors L2
* 3050 27 *4000 39 710 500 99 L3
N
3100 30 4000 40 735 512 102
KBA 2050-DV45 - DV
4000 40 5000 50 825 560 111
* 4250 41 *6000 60 915 603 120 Y
(cm) 5
32
Y

* New product group 0


40

11
E-Line KB BUSBAR TYPE
CONDUCTOR TYPE
Elbows BUSBAR CODE
PROTECTION DEGREE
TYPE
UNPAINTED / PAINTED
COMPONENT

KB

A
- K U L Upwards Left B
Combined Offset
Sample Order:
3000 A, Aluminium
Bolt-on, IP 55, 4 Conductors

KBA 3050-KUL

L1

300
L2
L3
N
5
32
0 0
KUL 4

- K U R Upwards Right A
Combined Offset B

Sample Order:
3000 A, Aluminium
Bolt-on, IP 55, 4 Conductors

KBA 3050-KUR

L1
L2

300
L3
N
5
32
0 0
KUR 4

0
- K D L Downwards Left 40
Combined Offset 32
5

Sample Order:
3000 A, Aluminium L1
L2
Bolt-on, IP 55, 4 Conductors L3
N

KBA 3050-KDL
300

KDL A

Al Con. Cu Con. A B
Rated Busbar Rated Busbar 0
(mm) (mm) 40
Current Code Current Code - K D R Downwards Right 5
800 08 1000 10 420 355 Combined Offset 32
1000 10 1250 12 445 367
Sample Order:
1250 12 1600 16 475 383 3000 A, Aluminium
* 1600 13 *2000 19 505 398 Bolt-on, IP 55, 4 Conductors L1
1600 16 2000 20 540 415 L2
300

L3
2000 20 2500 25 590 440 N
KBA 3050-KDR
2500 25 3000 30 650 470
* 3050 27 *4000 39 710 500
3100 30 4000 40 735 512
4000 40 5000 50 825 558 B
* 4250 41 *6000 60 915 603 KDR
* New product group A

Please call us for non-standard components.

12
E-Line KB BUSBAR TYPE
CONDUCTOR TYPE
Elbows BUSBAR CODE
PROTECTION DEGREE
TYPE
UNPAINTED / PAINTED
COMPONENT

KB

- K L U Left Upwards
Combined Offset
Sample Order:
3000 A, Aluminium

400
Bolt-on, IP 55, 4 Conductors

325
KBA 3050-KLU

30
0

A
L1
L2
L3 KLU
N

- K R U Right Upwards
Combined Offset

Sample Order:

A
3000 A, Aluminium

B
Bolt-on, IP 55, 4 Conductors
KBA 3050-KRU

325
400
30
0
L1
L2
L3
N
KRU

- K L D Left Downwards
Combined Offset
30

Sample Order:
0

3000 A, Aluminium
400

Bolt-on, IP 55, 4 Conductors


325

KBA 3050-KLD
B

L1
L2
L3
N
KLD

Al Cu
A B
Conductor Conductor
Rated Busbar Rated Busbar (mm) (mm)
Current Code Current Code - K R D Right Downwards
800 08 1000 10 420 355 Combined Offset
1000 10 1250 12 445 367
1250 12 1600 16 475 383 Sample Order:
A

* 1600 *2000 3000 A, Aluminium


13 19 505 398
B

Bolt-on, IP 55, 4 Conductors


1600 16 2000 20 540 415
2000 20 2500 25 590 440
KBA 3050-KRD
2500 25 3000 30 650 470
* 3050 27 *4000 39 710 500
3100 30 4000 40 735 512
30
0

4000 40 5000 50 825 558 L1


L2
325

* 4250 41 *6000 60 915 603


400

L3
* New product group
N KRD
Please call us for non-standard components.

13
E-Line KB BUSBAR TYPE
CONDUCTOR TYPE
Standard Components BUSBAR CODE
PROTECTION DEGREE
TYPE
UNPAINTED / PAINTED
COMPONENT

KB

End Closer
- S 1 0
End Closer Sample Order:
Is used to close the end of busbar run. 2500 A, Copper, Bolt-on, L1
L2 0
IP 55, 4 Conductors L3 60
KBC 2550-S10 N

End Closer
- S 1 1 L1
L2
Sample Order: L3
N
2500 A, Copper, Bolt-on, 0
60
IP 55, 4 Conductors
KBC 2550-S11

- RD Reduction
800 A - 08
Reduction Sample Order: 1000 A - 10 00
10
2000A / 1600A, Aluminium, 1250 A - 12
Is used to change the busbar cross section. Bolt-on, IP 55, 4 Conductors 1600 A - 13
1600 A - 16
5
KBA 2050-RD16 2000 A - 20 33
2500 A - 25
3050 A - 27
5
3100 A - 30 L1 66
4000 A - 40 L2
L3
4250 A - 41 N
5000 A - 50

Right Side Feeder "T"

A
- T Y R C
B
Sample Order:
2500 A, Aluminium, Bolt-on,
IP 55, 4 Conductors
KBA 2550-TYR L1
L2
L3
N

Left Side Feeder "T"

A
C
B
- T Y L
Sample Order:
2500 A, Aluminium, Bolt-on,
Al Cu IP 55, 4 Conductors
A B C
Conductor Conductor KBA 2550-TYL L1
L2
Rated Busbar Rated Busbar (mm) (mm) (mm) L3
Current Code Current Code N

800 08 1000 10 420 355 710


1000 10 1250 12 445 367 735
1250 12 1600 16 475 383 765
Central Feeder "T"
* 1600 13 *2000 19 505 398 796
1600 16 2000 20 540 440 830 - T O
A
2000 20 2500 25 590 470 880 Sample Order: C
B
2500 25 3000 30 650 513 940 3000 A, Copper, Bolton,
* 3050 27 *4000 39 710 500 1000 IP 55, 4 Conductors
3100 30 4000 40 735 512 1024 KBC 3050-TO
4000 40 5000 50 825 558 1115
* 4250 41 *6000 60 915 603 1205 L1
L2
* New product group L3
N
Please call us for non-standard components.

14
E-Line KB BUSBAR TYPE
CONDUCTOR TYPE
Flexibles & Expansions BUSBAR CODE
PROTECTION DEGREE
TYPE
UNPAINTED / PAINTED
COMPONENT

KB

- Y D T Horizontal Expansion
Sample Order:
2500 A, Aluminium,
Bolt-on, 4 Conductors
Horizontal Expansion KBA 2550-YDT
Used at every 40 m in horizontal L1
L2
long lines and for crossing building L3
expansions. N

00
15
- D D T Vertical Expansion
Sample Order:
2000 A, Copper, Bolt-on,
4 Conductors
Vertical Expansion
KBC 2050-DDT L1
For vertical application in many storey L2
L3
building. N

One vertical expansion unit is advised

0
to be used at every floor between 70
fixed support points.

- F Flexibles
Sample Order: L
800 A, Aluminium (cm)
Flexible are used for
KBA 0800-F40
Transformer - busbar,
Panel - busbar connections.

* B
L
X
Z Y

B=.....mm
X=.....mm
Y=.....mm
Z=.....mm
ø=.....mm

This side is punched according


Please call us for non-standard components. to the needs of the custommer.

15
E-Line KB BUSBAR TYPE
CONDUCTOR TYPE
R

BUSBAR CODE
Panel Connections PROTECTION DEGREE
TYPE
UNPAINTED / PAINTED
COMPONENT

KB

250

250
Panel Connection

200

200
Panel Feeder - P 1 0 N
L3 N
Busbar Feeder - P 1 1 P10 L 2 L1 L3
L 2 L1
L1 L2 P11
L3 L1 L2
N L3
Sample Order: N
2000 A, Copper, Bolt-on,
L for Busbar Feeder
L3 N 1L
40
0
40
0
L1 L L1
2
L2
NL 2 L
3L
3N KBC 2050-P11
L 3 5 5
N 2L
1
32 32

Upwards Panel Connection

400

400
325

325
Panel Feeder - PU20
Busbar Feeder - PU21

200

200
Sample Order:
N N
2000 A, Copper, Bolt-on, L3 L3
L2 L2
for Panel Feeder L1 L1
Attention !... PU20 PU21
KBC 2050-PU20
The position of the panel board conductors
and the position of the busbar according 0 0
40 40
to panel board must be taken into account Downwards Panel Connection 5 5
before installation. 32 32

Panel Feeder - PD20


Busbar Feeder - PD21

400

400
Side is defined as 0

325

325
Side is defined as 1

200

200
Sample Order:
2000 A, Copper, Bolt-on,
for Busbar Feeder L1 L1
L2 L2
KBC 2050-PD21 L3 L3
N N
Rated Current / Busbar Code PD20 PD21
Aluminium (Al) 800 / 08 1000 / 10 1250 / 12 *1600 / 13 1600 / 16 2000 / 20 2500 / 25 *3050 / 27
Copper (Cu) 1000 / 10 1250 / 12 1600 / 16 *2000 / 19 2000 / 20 2500 / 25 3000 / 30 *4000 / 39

A (mm) 75 100 130 160 196 246 306 366


B (mm) 40 50 60 60 40 50 60 60
C (mm) 40 50 40 40 40 50 40 40
D (mm) 17,5 25 35 50 17,5 25 35 50
E (mm) 17,5 25 25 25 17,5 25 25 25
F (mm) 330 355 385 415 451 500 560 620
G (mm) 150 175 205 235 271 320 380 440
150

1 2
200

200

ø13 ø13
E C

E C

B D B D B D
12 A 12 A
100 100 100 100 ø7 ø7
12

12
100 100 100 100 100

100 100 100 100 100

1 E-Line KB Busbar 2 2
2 Panel Connection Plate 3
3
3 Opening on the panel board
500

600

600
500

1 1

* Please call us for non-standard G G


components..
** Panel connection unit 100 100 100 100 100 100
connection bars have M12x40
size screws. F F

16
E-Line KB BUSBAR TYPE
CONDUCTOR TYPE
R

Panel Connections BUSBAR CODE


PROTECTION DEGREE
TYPE
UNPAINTED / PAINTED
COMPONENT

KB

A
A
Right Panel Connection B
B

A
Panel Feeder - P R30

A
B
Busbar Feeder - P R31

B
200
Sample Order:

200
L
L3 N 1L 2000 A, Copper, Bolt-on,
L1 L L1 NL 2 L
2
3N
L 3
L2 3L
2L
for Panel Feeder
N
1
N L3 L1 2
KBC 2050-PR30 L2
L
L3
L1 N
PR30 PR31

A A

B B
Attention !... Left Panel Connection

A
A
The position of the panel board conductors

B
B
and the position of the busbar according Panel Feeder - P L 30
to panel board must be taken into account Busbar Feeder - P L 31

200
before installation.

200
Sample Order:
2000 A, Copper, Bolt-on, L1 2
L
L3 N L3
A and B dimensions of PL30 and PL31 are same for Busbar Feeder N L2
L1
as left and right elbows, please refer to page 10 KBC 2050-PL31
for the dimensions. PL30 PL31

Rated Current / Busbar Code


Aluminium (Al) 3100 / 30 4000 / 40 4250 / 41
Copper (Cu) 4000 / 40 5000 / 50 6000 / 60

A (mm) 392 482 572


B (mm) 50 60 60
C (mm) 50 40 40
D (mm) 25 35 50
E (mm) 25 25 25
F (mm) 645 735 825
G (mm) 465 555 645
200

200

ø13 ø13
E C

E C

B D B D B D B 45 B D B 45 B D B 45 B D
12 A 12 A
ø7
12

12

ø7
2
100 100 100 100 100

100 100 100 100 100

3 3
600

600
500

500

1 1

G G

100 100 100 100 100 100 100 100 100 100 100 100
* Please call us for non-standard
components. F F

17
E-Line KB BUSBAR TYPE
CONDUCTOR TYPE
Transformer Connections BUSBAR CODE
PROTECTION DEGREE
TYPE
UNPAINTED / PAINTED
COMPONENT

KB

Transformer - T R11
Connection

Sample Order:

250
2500 A, Aluminium, Feeder,
4 Conductors

200
N KBA 2552-TR11
L3

TR11 N
L2 L3
L 2 L1
L1 L2
L3
N
L1

0
40
Upwards - T U21 5
32
Transformer Connection
Sample Order:
2500 A, Aluminium, Feeder,

400
325
4 Conductors
KBA 2552-TU21

200
TU21
N
L3
L2
L1

0
Downwards - T D21 40
5
Transformer Connection 32
For transformer and panel connection Sample Order:
applications EAE design and planning 2500 A, Aluminium, Feeder,
group will prepare your projects upon
400

4 Conductors
325

request.
KBA 2552-TD21
200

For the design the following informations are


required;
TD21
Plan of transformer and panel board room,
heights. L2
L1
Transformer dimensions, distance between N
L3
bushings.
Panel board dimensions.

Transformer - T R31
Connection
0
80

Sample Order:
2500 A, Aluminium, Bolt-on,
200

4 Conductors
KBA 2550-TR31
For connection dimesions please refer L1
to tables on pages 16 and 17. L2
L3 50
TR31 N
65
51
16
165

Please call us for non-standard components.

18
E-Line KB BUSBAR TYPE
CONDUCTOR TYPE
Transformer Connections BUSBAR CODE
PROTECTION DEGREE
TYPE
UNPAINTED / PAINTED
COMPONENT

KB

Transformer - T R41
Connection
Sample Order:

00
20
N
2000 A, Copper, Bolt-on, L1
0
L 11
3
4 Conductors
KBC 2050-TR41 0
L2 L2 67

L1 L3 0
67
N
0
29

TR41

Right - T R51 A
Transformer Connection
B
Sample Order:

A
2500 A, Aluminium, Feeder,

B
4 Conductors
KBA 2552-TR51

200

L1 2
L
For transformer and panel connection TR51 L3
N
applications EAE design and planning
group may prepare your projects upon
request.

For Project;

Plan of transformer and panel board room,


heights.
Transformer dimensions, distance between
bushings.
Panel board dimensions.
Left - T L51 A
Transformer Connection
B
A and B dimensions of TR51 and TL51 are same
as left and right elbows. Sample Order:
A

2500 A, Aluminium, Feeder,


B

Please refer to page 10 for the dimensions. 4 Conductors


KBA 2552-TL51
200

N L3
L2
L1
TL51

Please call us for non-standard components.

19
E-Line KB BUSBAR TYPE
BOX TYPE
RATED CURRENT Bolt on- B
Tap-off Boxes PROTECTION 160 A-16
250 A-25
Plug in- P

DEGREE
with Fused Switches (SYK) CONDUCTOR IP-55-5
400 A-40
630 A-63
4-0
5-1
CABLE GLAND PLATES
KB
Cable Gland Plates

Cable Order Inner


Mat. Gland Type Code Diameter
Sheet ---- RP0 (mm)

Sheet PG29 RP1 25

Sheet PG36 RP2 32

Sheet Special RP3 63


Bolt-on
Tap-off Boxes

65
Sheet 2xSpecial RP4 63 KB B 1 650

B
KB B 2 550
KB B 4 050
PP* 4xPG21 RP5 18
KB B 6 350

C
PP 4xPG29 RP6 25
Sample Order:
te
Bolt-on / 630 A / IP-55 / Pl
a

A
5 Conductors nd )
L1 la des
PP 4xPG36 RP7 32 KBB 6351 L2 L e
G si
3
N a bl n 3
C ( o

PP 8xPG29 RP8 25

PP* Polypropylene

Tap-off boxes are equipped with


EAE SYK fused switches
The tap-off boxes are in red RAL
3020 colour as standard.

EAE SYK
Can operate under load
Are equipped with NH fuse holders
Have interlock mechanism
KB P 1650
KB P 2550
Plug-in
KB P 4050
Tap-off Boxes
65

SYK 160 A
B

SYK 250 A Sample Order:


SYK 400 A Plug-in / 400 A / IP-55 /
C
C

SYK 630 A 5 Conductors


KBP 4051

a te
Tap-off A B C Standard Fuse Pl
nd s)
AA

Boxes (mm) (mm) (mm) Gland Size L1 laide


L2 G s
e
L3 bl n 3
KBB 16 540 310 180 RP2 NH00 N Ca (o
KBB 25 690 390 240 RP3 NH 1
KBB 40 690 390 240 RP4 NH 2
KBB 63 720 430 255 RP4 NH 3
KBP 16 540 310 180 RP2 NH00
KBP 25 690 390 240 RP3 NH 1
KBP 40 690 390 240 RP4 NH 2

Tap-off boxes can be equipped with any brand


of switches, circuit breakers and etc.
Please call us for non-standard tap-off boxes.

20
E-Line KB BUSBAR TYPE
BOX TYPE
RATED CURRENT Bolt on- B
Tap-off Boxes PROTECTION 160 A-16
250 A-25
Plug in- P

DEGREE
for MCCB's CONDUCTOR IP-55-5
400 A-40
630 A-63
4-0
5-1
CABLE GLAND PLATES
KB
Cable Gland Plates

Cable Order Inner


Mat. Gland Type Code Diameter
Sheet ---- RP0 (mm)

Sheet PG29 RP1 25

Sheet PG36 RP2 32

Sheet Special RP3 63


Bolt-on
Tap-off Boxes
Sheet 2xSpecial RP4 63 KB B 1 650

B
KB B 2 550
KB B 4 050
PP* 4xPG21 RP5 18

C
KB B 6 350

PP 4xPG29 RP6 25
Sample Order: te
a
Bolt-on / 630 A / IP-55 / Pl

A
nd )
5 Conductors la des
L1 G si
PP 4xPG36 RP7 32 KBB 6351
L2 L e
bl n 3
3
N C a ( o

PP 8xPG29 RP8 25

PP* Polypropylene
Special Cable Gland Plates
Cable Order Inner
Mat. Gland Type Code Diameter
(mm)
Sheet ---- RPK0 ----

Sheet PG21 RPK1 18

Sheet PG29 RPK2 25


KB P 1650
Sheet PG36 RPK3 32 KB P 2550
Plug-in
KB P 4050
Tap-off Boxes
B

Sheet 1xSpecial RPK4 63


Sample Order:
Plug-in / 400 A / IP-55 /
C

Tap-off A B C Standard MCCB Type 5 Conductors


Boxes (mm) (mm) (mm) Gland *ABB
KBP 4051
KBB 16 520 310 135 RPK3 S2
e
KBB 25 570 310 145 RPK4 S3 at
Pl
KBB 40 690 310 180 RP4 S5 nd s)
A

laide
L1 G s
KBB 63 690 310 180 RP4 S6 L2 e
bl n 3
KBP 16 520 310 240 RPK3 S2 L3 Ca (o
N
KBP 25 570 310 240 RPK4 S3
KBP 40 670 310 240 RP4 S5

Sample tap-off box sizes are for ABB brand MCCBs

* Tap-off boxes can be equipped with any brand


of MCCBs.

Please call us for non-standard tap-off boxes.

21
E-Line KB BUSBAR TYPE
CONDUCTOR TYPE
Feeder Boxes BUSBAR CODE
PROTECTION DEGREE
TYPE
UNPAINTED / PAINTED
COMPONENT

KB
Cable Gland Plates Feeder Box B10
Busbar Cable Type L1
Housing Type Gland Plate L2
- B 1 0 L3
Sample Order: N
PE
3000 A, Aluminium, Bolt-on
1 KBA 3050 - B10

Feeder Box B11

Sample Order: - B 1 1
1000 A, Aluminium, Bolt-on
3 KBA 1050 - B11 L1
L2
L3
N
PE

Feeder Box B20


- B 2 0
Sample Order:
2500 A, Aluminium, Bolt-on L1
KBA 2550 - B20 L2
250 A L3
N
PE

200 D C

Ampere Ratings Feeder Box B21


Aluminium Copper Gland
A B C D - B 2 1
(Al) (Cu) Type
Rated Busbar Rated Busbar Sample Order:
(mm) (mm) (mm) (mm)
Current Code Current Code 3000 A, Aluminium, Bolt-on
800 08 1000 10 500 500 300 300 1 KBA 3050 - B21
1000 10 1250 12 500 500 300 300 1
1250 12 1600 16 500 500 300 300 1 L1
* 1600 13 *2000 19 500 500 500 300 2 L2
L3
1600 16 2000 20 500 500 500 300 2 N
2000 20 2500 25 500 500 500 300 2 PE
2500 25 3000 30 500 500 500 300 2
* 3050 27 *4000 39 700 500 650 500 2
3100 30 4000 40 700 500 650 500 3
4000 40 5000 50 700 500 650 500 3
* 4250 41 *6000 60 700 500 750 500 3
Please call us for
* New product group non-standard feeder boxes.

22
E-Line KB R

Selection Feeder Boxes

Application of
Feeder Boxes for the horizontal lines

L1
In horizontal applications neutral conductor L2
is considered to be lower conductor. L3
N
PE

Application of
PE
L1
L2
L3
N

Feeder Boxes for the vertical lines

In vertical applications the neutral conductor


should be on the right side.

23
E-Line KB ORDER CODE
LENGTH L (mm)
R

Fixing Elements

D10
TU0
Supports

T10
IDD 400
IDD 600
IDD 800 IDD
IDD 1000 L
IDD 1200
IDD 2000

BR4 BR4 200


BR4 300
BR
BR4 400 40

BR4 500
BR4 600 40

STK

STK 200
STK 300 STK
IDD STK 400

UDD 400
IDD UDD 600
UDD 800 UDD
IDT UDD 1000 L
UDD 1200
IDY

STS 200
STS 300 STS
STS 400
5
15

UDY 400
UDY 600
UT UDY 800 UDY
A
UDY 1000 L
UDY 1200
UDY 2000
Al Cu
A
Conductor Conductor
Rated Busbar Rated Busbar (mm)
Current Code Current Code IDT Fixing Element
800 08 1000 10 135 Steel Dowel
1000 10 1250 12 160
1250 12 1600 16 190 T10 500 (M10)
* 1600 13 *2000 19 220 T10 1000 (M10)
1600 16 2000 20 255 T12 500 (M12) Extension
2000 20 2500 25 305 T12 1000 (M12) Unit
2500 25 3000 30 365 TUO-(M10)
* 3050 27 *4000 39 425 UT TU2 -(M12)
3100 30 4000 40 450 KBA1250 UT
L

4000 40 5000 50 540 KBA3000 UT Steel Dowel


* 4250 41 *6000 60 630 KBC2000 UT
* New product group KBC4000 UT D10 -(M10)
D12 -(M12)
Please call us for non-standard components.

24
E-Line KB ORDER CODE
LENGTH L (mm)
R

Fixing Elements

Supports

UDD 300
400
...
UDD 2000
Standard sizes of UDD are between
300 mm to 2000 mm.

UDYB
UDYB 300
400
...
1000
Standard sizes of UDYB are between
300 mm to 1000 mm.

UDD

STS

TMP 5

UDY PDD 300


400
...
2000
Standard sizes of PDD are between
300 mm to 2000 mm.

PDD

PDDB 300
400
...
1000
PDDB Standard sizes of PDDB are between
300 mm to 1000 mm.

Please call us for non-standard components.

25
E-Line KB R

Determination of Special Length

After the installation of standard 3m busbar lengths, you will be in need of special
lengths which are smaller than 3m. The minimum length for these special
elements can be 35 cm. Please measure the lengths of these modules as shown
below.

"A" length should be indicated in cm. Measure the asistance from one end of the
side housing to the other.

A=Length of Special Busbar

26
EC CONFORMITY CERTIFICATE

Product Group E-Line KB Busbar Energy Distribution System


Manufacturer EAE Elektrik A.Þ.
Ýkitelli Organize Sanayi Bölgesi Turgut Özal Cad.
Haseyad No:112 34670 Ýkitelli / Ýstanbul

This conformity certificate has been issued after running the below listed tests at laboratories.

Standard IEC 60439-2 : 2000-03

Type Tests
1- Temperature-rise limits
2- Dielectric properties
3- Short-circuit strength
4- Effectiveness of the protective circuit
5- Clearances and creepage distances
6- Mechanical operation
7- Degree of protection
8- Electrical Characteristics
9- Structural Strength
10-Crushing resistance
11-Resistance of insulating materials to abnormal heat
12-Fire barrier

Date EAE Elektrik A.Þ.


11.09.2002

EAE Elektrik A.Þ.


Ýkitelli Organize Sanayi Bölgesi Turgut Özal Cad. Haseyad No:112 34670 Ýkitelli / Ýstanbul
Tel.:(+90212) 549 23 02 (Pbx), Fax:(+90212) 549 23 10 Web: www.eae.com.tr Mail: eae@eae.com.tr

27
E-Line KB R

Certificates

28
Component List
Item Component Quantity
E-Line KB
Project Design Form

Company :
Project :
Project No :

Name :
Date :
Signature :
Prepared by

Please dublicate this page for your own use.


G & B / SFB / Ulaþ Tanýtým 612 40 66
20/03/2003