S E C T I O N - 04

SCHEDULE OF EQUIPMENT (OPTION 2)

Electric Operated VSD Driven , Screw Type Water Chiller with Continuous
Step less Capacity Modulation.

(a) Number of unit. 2 Nos (Two)


(b) Cooling Capacity 450 TR
(Dual Compressors , Dual VFD and
TWO Independent Refrigeration
circuits, continuous step less
capacity modulation 10 ~ 100 %)
Power consumption at specified
conditions KW/Ton 0.72(max)
(c) Chilled Water
Inlet temperature 55°F (12.8°C)
Outlet temperature 43°F (6.1°C)
Circulation 900 USgpm
Fouling Factor 0.0005 ft2-h-°F/Btu
Pressure drop (max) 15 ft. WC

(d) Condenser Water


Inlet temperature 90°F (32.2 °C)
Circulation 1350 USgpm
Fouling Factor 0.001 ft2-h-°F/Btu
Pressure drop (max) 15 ft. WC

(e) Annual Operating hours at Full Load 7,000 hours minimum


(f) Ambient 104/85 DB/WB°F (40/29.5 °C)
(g) Altitude Sea Level

Note: 1. Water boxes for Condenser shall be marine type with hinges and
shall be suitable for water working Pressure at least 10 Bar.

2. The supplier shall demonstrate that the Chiller can work


continuously without tripping at 10% load.

3. Chiller Electric Power Supply : 415 V/3/50 Hz

4. All water connections shall be Flanged type.

5. The Pre-wired control panel shall have IP-54/55 protection.