Professional Documents
Culture Documents
PSP MODULE 3 Diffl Gener Trans Bus
PSP MODULE 3 Diffl Gener Trans Bus
PSP MODULE 3 Diffl Gener Trans Bus
21EEE161
Department of Electrical & Electronics Engineering
2023-2024
Generator Protection
Transformer
Bus zone Protection
Module-4: Circuit Breakers
Module-5: Protection against Over voltages
Module-3:
Differential Protection
Generator Protection
Transformer
Bus zone Protection
Differential Protection
Differential Protection
• In this simple scheme, under normal operating conditions, the current entering into the
piece of equipment under protection is equal (or in the case of a transformer,
proportional) to its exiting current.
• In this example we will assume that the entry and exit currents are equal.
• A circuit breaker either side of the equipment under protection is controlled by an
overcurrent relay.
Differential Protection
• Current transformers of identical types and turns ratio are installed on either side of
the equipment.
• These current transformers induce identical secondary currents, because their primary
currents are identical and they have the same turns ratio.
• By simple inspection of the diagram, it is clear to see that under these circumstances no
spill current will flow through the relay, therefore no trip signals will be generated.
• The current exiting the equipment, albeit large, is still the same as the current entering it,
therefore the relay will not trip.
• This is because, because faults external to the equipment are in a different protection
zone and are protected within another scheme. https://www.youtube.com/watch?v=ML6Dz1qHs6w
Differential Protection
This system is operating in either of the two following principles:
1. Current balance principle.
2. Voltage balance principle.
• Therefore a current ΔI = Is1 + Is2 will flow in the operating winding of the relay.
• This will cause the relay to trip the circuit breaker connected to the faulty system.
• Hence the relay trips when
Voltage Balanced Differential Protection
• The current differential relay is not suitable for the protection of the feeders.
• For the protection of the feeders, the voltage balance differential relays are used.
• The voltage differential relay uses two similar current transformer places across the
protective zone with the help of pilot wire.
Voltage Balanced Differential Protection
• The relays are connected in series with the secondary of the current transformer.
• The relays are connected in such a way that no current flows through it in the normal
operating condition.
• The voltage balance differential relay uses the air core CTs in which the voltages induces
regarding current.
• When the fault occurs in the protection zone, the current in the CTs become
unbalance because of which the voltage in the secondary of the CTs disturbs.
• The current starts flowing through the operating coil.
• Thus, the relay starts operating and gives the command to the circuit breaker to operates.
Disadvantages of Simple Differential Relay:
1. There may be a probability of mismatching in cable impedance from CT
secondary to the remote relay panel.
2. These pilot cables’ capacitance causes incorrect operation of the relay when
large through fault occurs external to the equipment.
3. Accurate matching of characteristics of current transformer cannot be
achieved hence there may be spill current flowing through the relay in normal
operating conditions. This occurs due to constructional error and pilot cable
impedance.
4. Mal-operation of relays due to currents circulating vis path other than the main
pilot loop
Disadvantages of Simple Differential Relay:
5.During large external fault conditions, large primary current flowing through the
CTs causes unequal currents in their secondaries due to inherent difference in the CT
characteristics and unequal dc offset components in the fault currents.
6.If CTs have different saturation levels, their ratio and phase angle errors will be
different, hence difference in magnitude or phase angle of current results in
differential current flowing through the relay.
Characteristics of Simple Differential Relay:
The fault current is maximum under following conditions:
(i) Symmetrical 3 phase fault
(ii) Fault is close to transformer terminals
(iii) Source impedance is minimum
𝐼𝐹𝘍 𝑚 𝑎 𝑥
Stability Ratio = 𝐼𝐹𝘍 𝑚 𝑖
𝑛
Percentage Differential Current Relay
• This relay has an operating winding and two restraining winding connected as shown in
Fig..
• The function of the restraining windings is to prevent undesired relay operation
should a current flow in the operating winding due to CT during external fault.
Percentage Differential Current Relay
• The relay operates if the operating torque produced by the operating coil is more than the restraining torque
produced by the restraining coil.
• As the torque is proportional to the ampere-turns (AT), the relay will operate when the ampere-turns of the
operating coil (AT)0, will be greater than ampere-turns of the restraining coil, (AT)r.
Percentage Differential Current Relay
Percentage Differential Current Relay
(ii) Bias Setting : The bias (K ) of the relay is the ratio of the number of turns in the restraining coil (Nr)
to the number of turns in the operating coil (N0). It can also be defined as the ratio of minimum current
through operating coil for causing operation to the restraining current. It can be expressed as
Typical values of bias setting might be 10% for generator and 20 to 40% for transformer (the higher
bias values are used for tap-changing transformers).
Bias Setting of Percentage Differential Relay
•Figure shows the tapping on the restraining coil for adjusting the bias (slope) of the relay.
•The bias (slope) is adjusted by changing the tapping on the restraining coil.
•Both halves of the restraining coil must be symmetrically tapped.
Three-Terminal System-Application of a Percentage-Differential Relay:
• Percentage-differential relay protection can be applied to the system elements having more than
two terminals, as in the three-terminal application shown in Fig..
• Each of the three restraining coils has the same number of turns, and each coil develops a
torque independently of others.
• Their torques is added arithmetically.
• The percent slope characteristic for such a relay will vary with the distribution of currents
between the three restraining coils
• Percentage-differential relays are generally
instantaneous or high speed. Time delay is not required
for selectivity because the percentage-differential
characteristic makes these relays immune to the effects
of transients when the relays are properly applied.
Module-3:
Differential Protection
Generator Protection
Transformer
Bus zone Protection
Rotating Machines Protection
Basic Construction Generator
PROTECTION OF GENERATORS
(i) Stator Protection
a) Percentage Differential Protection
b) Protection against Stator Inter Turn fault
c) Stator overheating protection
(ii) Rotor Protection
a) Field ground fault protection (Rotor Earth Fault)
b) Loss of excitation protection
c) Protection against rotor overheating because of unbalanced three phase stator
current
(iii) Miscellaneous
a) Overvoltage protection
b) Over-speed protection
c) Protection against Motoring
d) Protection against vibration
e) Bearing overheating protection
f) Protection against auxiliary failure
g) Protection against voltage regulator failure
PROTECTION OF GENERATORS
(i) Stator Protection
a) Percentage Differential Protection
b) Protection against Stator Inter Turn fault
c) Stator overheating protection
PROTECTION OF GENERATORS
(i) Stator Protection
a) Percentage Differential Protection
PROTECTION OF GENERATORS
(i) Stator Protection
a) Percentage Differential Protection
• Any internal fault inside the stator winding is cleared by mainly differential protection
scheme of the generator or alternator.
• The differential protection is provided in the generator by using longitudinal
differential relay.
• There are two sets of current transformers, one CT is connected to the line side of the
generator and other is connected to the neutral side of the generator in each phase.
• It is needless to say that the characteristics of all current transformers installed against each
phase must be matched.
• If there is any major mismatched in the current transformer’s characteristics of both sides of
the generator, there may be high chance of malfunctioning of differential relay during the
fault external to the stator winding and also may be during normal operating conditions of
the generator.
PROTECTION OF GENERATORS
(i) Stator Protection
a) Percentage Differential Protection
• To ensure that the relay does not operate for the faults external to the operated zone of the
protection scheme, a stabilizing resistor is fitted in series with the relay operating oil.
• It also ensures that if one set of CT has been saturated, there will be no possibility of
malfunctioning of the differential relay.
a) Percentage Differential Protection
• Consider the fault occurs on the R phase of the network because of the insulation
breakdown.
• Because of the fault, the current in the secondary of the transformer becomes unequal.
• The differential currents flow through the relay coil.
• Thus, the relay becomes operative and gives the command to the circuit breaker for
operation.
• If the fault occurs between any two phases, say Y and B then short-circuit current
flows through these phases.
• Due to fault, unbalanced current flows through CTs.
• The differential current flows through the relay operating coil and thus relay trips their
contacts. https://www.youtube.com/watch?v=9RHWY3IJ--0
Problems Associated with Differential Protection System
• A neutral resistance wire is used in the differential protection system for avoiding the
adverse effect of earth fault currents.
• When an earth fault occurs near the neutral, it will cause a small, short circuit current
to flow through the neutral point because of small emf.
• The earth fault can be isolated by using the restricted earth fault protection
scheme.
• The earth fault protection scheme consists the earth fault relay, which gives the tripping
command to the circuit breaker and hence restrict the fault current.
• The earth fault relay is placed in the residual part of the current transformers
shown in the figure below
Restricted Earth Fault Protection
• The connection of earth fault relay with the star or delta winding of the transformer is
shown in the figure below
https://www.youtube.com/watch?v=BN03zOYMpQk
Restricted Earth Fault Protection
• The connection of earth fault relay with the star or delta winding of the transformer is
shown in the figure below
• The current transformers are placed on both sides of the protective zone.
• The secondary terminal of the current transformer is connected in parallel with the relay.
• The output of the current transformer is equal to the zero sequence current flows in
the line.
• The zero sequence current is absent for the external fault and for the internal fault it
becomes twice the value of fault current.
Restricted Earth Fault Protection
• Let F1 be the external fault occurs in the network.
• This fault induces the I1 and I2 current which flows in the secondary of the CTs.
• The resultant current of the I1 and I2 becomes zero.
• When the fault occurs inside the protective zone say F2, then only current I2 exist, and I1 is
neglected.
• The current I2 passes through the earth fault relay.
• The earth fault relay operates only for the internal fault of the protective zone.
Restricted Earth Fault Protection
• The earth fault relay must be very sensitive for sensing the fault.
• The relay is designed for sensing the fault current which is 15% more than that of the
rated winding current
• The high voltage generator contains a large number of conductors per slot in the stator
winding hence, in these cases the additional inter turn fault protection of the stator winding
may be essential.
• Moreover in modern practice, inter turn protection is becoming essential for all large
generating units
• Several methods can be adopted for providing inter turn protection to the stator winding of
generator.
• Cross differential methods is most common among them.
• In this scheme the winding for each phase is divided into two parallel paths.
Inter Turn Fault Protection of
Stator Winding of Generator
• Electrical overcurrent relays cannot sense the winding temperature accurately because
temperature rise depends on I2Rt and also on cooling.
• Electrical protection cannot detect failure of the cooling system.
Stator Overheating Protection
• The practice is to embed resistance temperature-detector coils or thermocouples in the slots
below the stator coils of the generators of large capacity (above 1 MVA) for protection
against overheating.
• Large number of such detectors are located at different places in the windings so that an
indication can be obtained of the temperature conditions throughout the stator.
• Several of the detectors that provide the highest temperature indication are selected for use
with temperature indicator or recorder usually having alarm contacts, or the detector
providing the highest indication may be arranged to operate a temperature relay to
sound alarm.
• Supplementary temperature devices may be provided for monitoring the cooling system;
such devices would give the earliest alarm in the event of failure of cooling system.
• But it is usually realized that the stator temperature detectors and alarm devices are sufficient
Stator Overheating Protection
Stator Overheating Protection
• The most reliable method of detecting such a condition is by means of temperature
detector coils embedded at various points in the stator winding arranged to provide an
indication of the temperature conditions which exist over the stator winding.
• The major disadvantage of such type of system it that it can detect the fault for most
of the rotor circuit except the rotor centre point.
• This current unbalanced the magnetic field and increase the stress on the magnetic bearing.
• Another disadvantage of alternating current is that the relay cannot pick up the current that
normally flow through the capacitance to the ground.
• Thus, the care must be taken to avoid resonance between the capacitance and the relay
inductance.
Rotor Earth Fault Protection of Alternator or Generator
• The problem of the AC injection system can be
overcome by using the DC injection method.
• This method is simple and has no problem of leakage
currents.
• The one terminal of the sensitive relay is connected to
the exciter, and the other terminal is connected to the
negative terminal of the DC source.
• In case of high-speed turbo-generators, the continuous current which can be carried is usually
between 10 and 15% of the positive sequence continuous rating.
• The negative sequence heating follows a normal resistance law and hence is proportional to
the square of the current.
• The heating time constant of the machine is largely a function of the cooling system employed.
•This is expressed by a rating equation:
where
I2 – is the negative sequence current expressed on a per unit basis of continuous maximum
rating (CMR),
t – is the current duration in seconds, and
K – is a constant which for turbo type machines will usually have a value between 3 and 20
it is 60 for salient pole hydro generator
Protection Against Unbalanced Stator Currents
Protection Against Unbalanced Stator Currents
• The problem of protecting against this condition lies in obtaining a relay characteristic
which will accurately match this heating characteristic.
• The usual arrangement is an inverse with definite minimum time delay relay connected to a
network which segregates the negative sequence current from the positive and zero sequence
current Fig.
• The relay has a long operating time and has a range of settings to allow its characteristic to
be accurately matched to those of the machine.
• The typical time range is 0.2 sec to 2000 sec
• The Relay consists of special electromagnet, shaded pole construction with a Mu metal
shunt.
• The NPS filter gives an output proportional to I2, that actuates an alarm as well as time
current relay, with very inverse characteristics.
• Timer is adjustable for 8% to 40% of negative sequence component, the delay prevents
unnecessary sounding of alarm on unbalanced loads of short duration
PROTECTION OF GENERATORS
(iii) Miscellaneous
a) Overvoltage protection
b) Over-speed protection
c) Protection against Motoring
d) Protection against vibration
e) Bearing overheating protection
f) Protection against auxiliary failure
g) Protection against voltage regulator failure
REFER TO TEXT BOOK:
BADRI RAM & VISHWAKARMA- Page 359 to 361
(a) Overvoltage Protection
Overvoltage may be caused by a defective voltage regulator or it may occur due to sudden loss of electrical
load on generators. When a load is lost, there is an increase in speed and hence the voltage also increases. In
case of a steam power station, it is possible to bypass the steam before the speed reaches a limit above which
a dangerous overvoltage can be produced. In steam power stations, the automatic voltage regulator controls
the overvoltages which is associated with overspeed. In hydro-stations it is not possible to stop or divert
water flow so quickly and overspeed may occur. Therefore, overvoltage relays are provided with hydro and
gas-turbine sets. But overvoltage relays are not commonly used with turbo-alternators.
Internal faults:
insulation deterioration
winding failure
overheating
contamination of oil
External faults:
lighting strikes
system overload
short circuit
Differential Protection of a Transformer
Differential Protection of a Transformer
• External fault is cleared by the relay system outside the transformer within the shortest possible
time in order to avoid any danger to the transformer due to these faults.
• The protection for internal fault in such type of transformer is to be provided by using
differential protection system.
Differential Protection of a Transformer
• Differential protection schemes are mainly used for protection against phase-to-phase fault and
phase to earth faults.
• The differential protection used for power transformers is based on Merz-Prize circulating
current principle.
• Such types of protection are generally used for transformers of rating exceeding 2 MVA.
Differential Protection of a Transformer
• This current is as large as 10 times full load current and its decay respectively.
• This magnetizing current is flows in the primary winding of the power transformers due to
which it causes a difference in current transformer output and it makes the differential
protection of the transformer to operate falsely.
• To overcome this problem the kick fuse is placed across the relay coil. These fuses are of the
time-limit type with an inverse characteristic and do not operate in short duration of the switch
in the surge. When the fault occurs the fuses blow out and the fault current flows through the
relay coils and operate the protection system. This problem can also be overcome by using a
relay with an inverse and definite minimum type characteristic instead of an
instantaneous type.
Harmonic Restraining in Differential Protection
• The differential relay is used for protection of transformer ,alternator and large rating HT
motor.
• The magnetic flux in the core is not sinusoidal and transformer generates harmonics.
• The sensing of the harmonics and restraining the differential protection relay operation at
the time of charging of the transformer is one of the solution.
• This requirement is fulfilled by harmonic restraining in differential protection of the
transformer.
Harmonic Restraining in Differential Protection
• The magnetizing inrush current, according to Fourier series, has 2nd and 5th order
harmonics.
• The 2nd order harmonic is rich when transformer draws magnetizing current
at the time of switching of transformer.
• The frequency of the 2nd order harmonics is 100 Hz.
• The differential relay has a 100 Hz filter circuit which measures the frequency and
the magnitude of the 2nd order harmonic current in the differential current.
Harmonic Restraining in Differential Protection
• If the relay senses the current of 100 Hz frequency and if the current is more than the
differential current setting of the relay, the relay will observe that the transformer is taking
the inrush magnetizing current and the relay blocks its main tripping mechanism.
• Therefore, the 2nd order harmonic current needs to be blocked in the differential relay
because 2nd order harmonic current will operate under no fault within the transformer.
• Thus, the harmonic current blocking is an important feature of the differential
protection relay.
• In the harmonic restraint differential protection scheme, the harmonic restraint
differential relay has the 2nd,3rd,5th order harmonic blocking circuit and the
differential protection circuits.
• If the inrush current contains predominant 2nd order harmonic current, it is
symptom of transformer energization and differential protection is supposed to be
blocked during normal transformer energization.
• If the ratio of the second harmonic current to the fundamental is greater than
2nd order harmonic current set point, the relay blocks the differential
operation because relay sees this condition as transformer energization.
Harmonic Restraining in Differential Protection
• The magnitude of 2nd order harmonic current in inrush current depends on
transformer material, construction and remeanace.
• Therefore, the setting of the 2nd order harmonic blocking current can not
be calculated in a straightforward way.
• The relay measures the ratio of 2nd order harmonic current and the fundamental
current and the setting of the 2nd order harmonic blocking current can be done
accordingly.
• The setting of the 2nd order harmonic restraining is generally kept between 20-25
% of the differential relay setting.
• If the current is below the differential relay setting, the relay does not trip
because the relay will observe it as a transformer charging phenomenon.
• If the harmonic restraining current is more than the differential relay setting, the
relay will trip with differential protection fault.
Harmonic Restraining in Differential Protection
• If the magnitude of the 5th order harmonic current is more than the the setting of the
differential protection relay setting the relay will trip. If the magnitude of the 5th order
harmonic current is less than the setting of the differential protection relay setting the
relay will not trip.
• The setting of the 5th order harmonic restraining is generally kept between 20- 25 %
of the differential relay setting.
• The operation of transformer is not possible without having the harmonic restraint in
differential protection.
•Short circuit faults such as inter turn faults, incipient winding faults, and core faults may
occur due to the impulse breakdown of the insulating oil or simply the transformer oil.
•Buchholz relay will sense such faults and closes the alarm circuit.
https://www.youtube.com/watch?v=Y5dAaeLPzzk
Buchholz Relay Working Principle
•Buchholz relay relies on the fact that an electrical fault inside the transformer tank is
accompanied by the generation of gas and if the fault is high enough it will be accompanied by a
•Whenever a fault occurs inside the transformer, the oil in the transformer tank gets overheated
and gases are generated. The generation of the gases depends mainly on the intensity of fault
produced.
•The heat generated during the fault will be high enough to decompose the transformer oil and
•This is the basic principle behind the working of the Buchholz relay.
Buchholz Relay Working Principle
Buchholz Relay
CONSTRUCTION OF A BUCHHOLZ RELAY
• These gas bubbles flow in upward direction and get collected in the Buchholz relay.
• The collected gas displaces the oil in Buchholz relay and the displacement is equivalent
to the volume of gas collected.
• The displacement of oil causes the upper float to close the upper mercury switch which
is connected to an alarm circuit.
• Hence, when minor fault occurs, the connected alarm gets activated.
https://www.youtube.com/watch?v=_jNqmFvKVro
Working of Buchholz Relay
• The collected amount of gas indicates the severity of the fault occurred.
• During minor faults the production of gas is not enough to move the lower float.
• Hence, during minor faults, the lower float is unaffected.
• During major faults, like phase to earth short circuit, the heat generated is high and a
large amount of gas is produced.
• This large amount of gas will similarly flow upwards, but its motion is high enough to
tilt the lower float in the Buchholz relay.
• In this case, the lower float will cause the lower mercury switch which will trip the
transformer from the supply, i.e. transformer is isolated from the supply.
Advantages Of Buchholz Relay
•Buchholz relay indicates the internal faults due to heating and it helps in avoiding the
major faults.
•Severity of the fault can be determined without even dismantling the transformer.
•If a major fault occurs, the transformer can be isolated with the help of Buchholz relay to
prevent accidents.
PRD (Pressure Relief Device)
PRD (Pressure Relief Device)
• PRD (Pressure Relief Device) is a device which is used for avoiding high oil pressure
builds up inside the transformer during fault conditions.
When the pressure in front of the piston exceeds the counter force of the spring, the piston will
move operating the switching contacts. The micro switch inside the switching unit is
hermetically sealed and pressurized with nitrogen gas.
Overcurrent relays for Transformers
Overcurrent relays for Transformers
• Overcurrent Relays are used for protection of transformers of rating 100kVA and below
5MVA.
• An earth fault tripping element is also used in addition to the O/c failure.
• Such relays are used as primary protection of transformer which is not provided by
differential protection.
• With the advent of ring main units incorporating SF6 circuit breakers and isolators,
protection of distribution transformers can now be provided by overcurrent trips.
• For example, tripping controlled by time limit fuses connected across the
secondary windings of in-built current transformers) or by relays connected to current
transformers located on the transformer primary side.
• Overcurrent relays are also used on larger transformers provided with standard
circuit breaker control.
Restricted Earth Fault Protection
Restricted Earth Fault Protection
• This type of Restricted Earth Fault Protection is provided to detect earth-faults within
the protected zone of the transformer.
• A CT is fitted in each connection to the protected winding, and the CT secondary
windings are connected in parallel to a relay.
Restricted Earth Fault Protection
• The star connected neutral earthed side is protected by restricted earth fault protection.
• An earth fault F1 beyond the transformer causes the currents I2 and I1 to flow in CT
secondaries.
• If the resultant current in earth fault relay is negligible, the relay does not operate.
• For earth fault within the transformer star connected winding F2 only I2 flows and I1 is
negligible. Hence, the earth fault relay operates.
• When fault occurs very near to neutral point, the voltage available for driving earth
fault relay is very small.
• Hence the practice is to set the relay such that it operates for earth fault current of the
order of 15% of rated current.
• Such setting protects restricted portion of winding, hence the name is restricted earth
fault protection.
Restricted Earth Fault Protection
• Ideally, the output of the CTs is proportional to the sum of the zero sequence currents
in the line and neutral earth connection if the latter is within the protected zone.
• For internal earth faults this sum is equal to two times the total fault current, but for
external faults zero-sequence currents are either absent or sum to zero in the line and
neutral-earth connection.
• The maximum over fluxing in transformer shall not exceed 110% of the designed flux
density, and the transformer can be operated continuously at 110 % of the designed flux
density.
• However, the operation of the transformer above 110% and up to 130 % of the flux density
can be allowed for a shorter period of the time.
• If the flux density increases to 140 %, the transformer shall be tripped instantaneously to
avoid the permanent damage.
• The flux density in the core is proportional to the ratio of V/f.
Transformer Over Fluxing Protection
• The flux in the core remains constant for the constant V/f ratio.
• The mathematical expression of the flux density is as given below:
The voltage induced in the primary when the sinusoidal voltage is applied is
E=4.44 ΦfN
Φ=E/4.44f N
The Number of turns in the primary is constant for a given transformer
Φ=K* E/f
The induced voltage is approximately proportional to the applied voltage if the primary
impedance is ignored.
Φ=K*V/f ----------(1)
Transformer Over Fluxing Protection
B=K1*V/f -----------(2)
B 𝖺 V/f
• Thus the flux density in the core is directly proportional to the ratio of V/f if the
number of turns of the primary is fixed.
Transformer Over Fluxing Protection
• The relay measures the voltage and the frequency of the supply source.
• It calculates the ratio of the Volt/hertz on a real-time basis and compares the measured
value with the set-point.
• The relay is programmed for an inverse definite minimum time (IDMT characteristics).
• The setting of the over fluxing can be done for the 110 to 140 % of the rated flux of
the transformer.
• The protection scheme of the transformer is as given below.
Earthing Transformer Protection
Earthing Transformer Protection
• If the earthing transformer on the Delta Side is outsides the Zone of protection the Earth
Fault(E/F) in the delta system outside Current Transformer (CT) locations would produce
current distributions as shown which circulate within the differential CT secondaries and
is kept out of operating coils.
• Zig-Zag or inter connected star grounding transformer has normal magnetising
impedance of high value but for E/F, currents flow in windings of the same – core in
such a manner that the ampere turn cancel and hence offer lower impedance.
• In cases where the neutral point of three phase system is not accessible like the system
connected to the delta connected side of a electrical power transformer, an artificial
neutral point may be created with help of a zigzag connected earthing transformer.
Earthing Transformer Protection
• This is a core type transformer with three limbs.
• Every phase winding in zigzag connection is divided into two equal halves.
• One half of which is wound on one limb and other half is wound on another limb of the
core of transformer.
• 1st half of Red phase winding is wound on the 1st limb of the core and 2nd half of same
Red phase is wound on 3rd limb.
• 1st half of Yellow phase winding is wound on the 2nd limb of the core and 2nd half of
same Yellow phase is wound on 1st limb.
• 1st half of Blue phase winding is wound on the 3rd limb of the core and 2nd half of
same Blue phase is wound on 2nd limb.
• End point of all three winding ultimately connected together and forms a common
neutral point.
• Now if any fault occurs at any of the phases in delta connected system, the zero
sequence fault current has close path of circulating through earth as shown in the
figure.
Earthing Transformer Protection
• In normal condition of the system, the voltage across the winding of the earthing
transformer is 1/√3 times of rated per phase voltage of the system.
• But when single line to ground fault occurs on any phase of the system, as shown in the
figure, zero sequence component of the earth fault current flows in the earth and returns to
the electrical power system by way of earth star point of the earthing transformer.
• It gets divided equally in all the three phases.
• Hence, as shown in the figure, the currents in the two different halves of two windings in
the same limb of the core flow in opposite directions.
• And therefore the magnetic flux set up by these two currents will oppose and neutralize
each other.
• As there is no increase in flux due to fault current, there is no change of dφ/dt means
no choking effect occurs to impede the flow of fault current.
• So it can be concluded that, the zigzag type earthing or grounding transformer
maintains the rated supply voltage at normal current as well as when a solid single
line to ground fault current flows through it.
Earthing Transformer Protection
• The unit protection principle remains valid for a system having more than two connections,
so a transformer with three or more windings can still be protected by the application of
the above principles.
• When the power transformer has only one of its three windings connected to a source of
supply, with the other two windings feeding loads, a relay with only two sets of CT
inputs can be used, connected as shown in Figure.
• The separate load currents are summated in the CT secondary circuits, and will
balance with the infeed current on the supply side.
Protection of Three Winding Transformer
• When more than one source of fault current infeed exists, there is a danger in the
scheme of Figure(a) of current circulating between the two paralleled sets of
current transformers without producing any bias.
• It is therefore important a relay is used with separate CT inputs for the
two secondaries – Figure (b).
• The zone of such a scheme includes the stator windings, the step up transformer and the
intervening connections.
Differential Protection Generator Transformer Unit
• The transformer is delta-star hence the current transformers on high voltage side are
delta connected while those on generator side are star connected.
• This cancels the displacement between line currents introduced by the delta connected
primary of the transformer.
• Where there is no fault, the secondary currents of the current transformer connected on
generator side are equal to the currents in the pilot wires from the secondaries of the
delta connected current transformers on the secondary of main transformer.
• When a fault occurs, the pilot wires carry the differential current to operate the
percentage differential relay.
• For the protection against the earth faults, an earth fault relays is put in the secondary
winding of the main step up transformers as shown.
• In such a case, differential protection acts as a backup protection to the restricted earth
fault protection.
• This overall differential protection scheme does not include unit transformer as a
separate differential scheme is provided it.
Differential Protection Generator Transformer Unit
PHASE FAULT
• Phase-phase faults clear of earth are less common.
• They may occur on the end portion of stator coils or in the slots if the winding
involves two coil sides in the same slot.
• In the later case the fault will involve earth in a very short time.
• Phase fault current is not controlled by the method of earthing the neutral point.
INTERTURN FAULTS
• Interturn faults are also uncommon, but not unknown
• A greatest danger arising from failure to deal with interturn faults quickly is fire. A
large portion of the insulation is inflammable
Example 10.1
• Busbar protection or bus zone protection includes, besides bus itself, the apparatus
such as circuit breakers, disconnecting switches, instruments, transformers etc.
• Though the bus zone faults are rare, experience shows that bus protection is highly
desirable in large and important stations.
• Moreover, the need for bus zone protection is highly felt because, the faults level at
busbar is very high and the faults on bus-bar causes discontinuance of power to a large
portion of the system.
• A bus fault tends to be appreciably more severe, both with respect to the safety of
personnel, system stability and the damage to the equipment's.
Busbar Protection
• Hence no current will flow through the relay and it will not operate.
• If any fault, either a phase to phase fault or phase to earth fault occurs in the systems, the
sum of these currents will not be zero and some current will flow through the relay and
causes the relay to operate and isolate the faulty section.
• That is a current in the relay indicates a fault within the protected zone and initiates
opening of the generator breaker CB1 and CB2 and each of the line breakers CB3, CB4 and
CB5 including the bus breaker CB6.
• In this type, the busbars can be sectionalized to identify the fault in that particular section.
Busbar Protection
• The main drawback with this type of differential protection is the difference in the
magnetic conditions of the iron cored CTs which may result in false operation of the relay
at the time of an external fault. Even with identical CTs having large iron cores to avoid
the saturation with maximum fault currents, the DC transient component presents
difficulty because of its slow decay.
• Biasing of differential relays improves the stability considerably; but is not a complete
solution.
• It can be seen that a high impedance bus differential relay can discriminate between
internal and external faults better than the usual low impedance relay.
• In other words, the ratio of the relay current during an internal fault to relay current during
an external fault is greater if the impedance of the relay is higher.
Frame Leakage Protection Working Principle
• Frame Leakage Protection of Busbar is used to protect the busbar, circuit breaker, isolator
switches instrument transformer from busbar earth faults.
• All Busbar used in a power system is neatly bound with PVC insulation or other high voltage
insulation material. PVC protects the busbar from earth faults.
• Due to check relay, accidental operation of single relay to trip the circuit gets avoided.
CONTENT
Module 1: Introduction to Power System Protection
Module-2: Overcurrent Protection Syllabus for
Distance Protection Second
Internal
Module-3: Differential Protection Assessment
Rotating Machines Protection
Transformer and
Bus zone Protection
Module-4: Circuit Breakers
Module-5: Protection against Over voltages