Bangladesh - Ashuganj -FF WORKS BOQ FOR BILLING ITEMS - 2&7
Bangladesh - Ashuganj -FF WORKS BOQ FOR BILLING ITEMS - 2&7
3 ADMINISTRATIVE BUILDING-
FIREFIGHTING WORKS
T.I. No. Description Of Items of Works Quantity Unit
FIRE PROTECTION EXTINGUISHER SYSTEM DRY CHEMICAL POWDER TYPE
Supply & fixing the following capacities multipurpose ABC dry chemical powder stored pressure
101
type with manometer system fire extinguisher suitable for repeated use complete with wall bracket, CO2 9 each
i
cartridge, easy refilling system etc. as per sample accepted & approved by the Engineer.
5 Kg. capacity.
102 FIRE PROTECTION (HYDRANT) SYSTEM 3 each
Supply & installation of fire hose of 40mm dia. 30 meter long with hose rack frame & nipple suitable
to install inside the hydrant cabinet. The hose shall conform to UL 19. The hose shall be UL Listed / FM
approved & burst pressure shall be not less that 600 psi and working pressure 200 psi, shall be made with
special quality EPDM rubber as internal lining, suitable to withstand heat and polluted water, heat
and abrasion resistance, Jacketing shall be made up of 100% polyester for extra strength. Hose shall be
30meter long in a single length and shall be with male coupling in one end other end with female coupling.
Couplings shall be bonded with hose with copper wire properly. Coupling shall be available in
NST or instantaneous couplings shall be made with bronze / alluminium alloy, polished / hard
anodized to confirm IS 9109 and BS 336.
STEEL CABINET
Fabrication, supply & installation of hydrant
cabinet of suitable size (as per site
measurement and requirement / recommended
by the Engineering to accommodate landing
valve, hose, nozzle and coupling. The cabinet
shall 3 each
104 be with swing type door with or
without breakable tempered glass. The
cabinet shall be made with 18 SWG sheet
steel, powder coated of red
color.
Class - II cabinet ( for 1.5'' hose rack assembly)
Supply and installation of "Exit light" complete with rechargeable battery and charge light and other
113 necessary accessories suitable for AC / DC 3 each
power supply (220V single phase)
Supply and installation of "Evacuation light" complete with rechargeable battery and charge light and
114 3 each
other necessary accessories suitable for AC / DC power supply (220V single phase)
Total of [2.1.3 ADMINISTRATIVE
BUILDING-FIREFIGHTING WORKS]
Total in words USD of [2.1.3
ADMINISTRATIVE BUILDING-
FIREFIGHTING WORKS]
2.2.3 STAFF ACCOMMODATION
BUILDING - FIRE FIGHTING WORKS
T.I.
Description of Item of Works Quantity Unit
No.
220 FIRE PROTECTION EXTINGUISHER SYSTEM 3 each
DRY CHEMICAL POWDER TYPE
Supply & fixing the following capacities multipurpose ABC dry chemical powder stored pressure
type with manometer system fire extinguisher suitable for repeated use complete with wall bracket, CO2
cartridge, easy refilling system etc. as per sample accepted & approved by the Engineer.
5 Kg. capacity.
T.I.
Description of Item of Works Quantity Unit
No.
Each sensor shall be scanned by the Control Unit for its type identification to prevent inadvertent
substitution of another sensor type. Upon detection of a "wrong device", the control unit shall
operate with the installed device at the default alarm settings for that sensor; 2.5%
obscuration for photoelectric sensor, 1350 F and 150 F rate-of-rises for the heat sensor, but shall indicate a
"Wrong Device" trouble condition.The sensor's electronics shall be immune from false alarms caused by
EMI and RFI.
Sensors shall be including a communication transmitter and receiver in the mounting base having a unique
identification and capability for status reporting to the FACP. Sensor address shall be located in base to
eliminate false addressing when replacing sensors. Removal of the sensor head for cleaning shall not
require the setting of addresses.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be : 0°
to 50°C shall be suitable for humidity range: 10% to 95% RH
Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min (0-
610m/min)
Approvals : UL listed / FM approved / LPCB approved
T.I.
Description of Item of Works Quantity Unit
No.
Supply & installation of addressable type audible horn for notification purpose shall contain an
electronic module and a selectable address setting. A visible LED on each appliance shall
provide verification of communications.
The device shall be suitable to program the high / low setting of the audible (horn) appliances by
channel from the addressable controller. The horn shall be red color with “FIRE" lettering.
Addressable horn shall be listed to UL. The horn shall be suitable to produce sound pressure level of
89 dBA @ 24VDC. The horn shall suitable to mount directly to a standard single gang, double gang or
4" square electrical box, without the use of special adapter or trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
Approvals: UL listed / FM approved.
T.I.
Description of Item of Works Quantity Unit
No.
Addressable modules
Isolator module / fault Isolator module
Supply & installation of addressable type isolator / fault Isolator module shall be used in the field
wiring between the devices (contractor shall propose the quantity and location in the system
required) to detect & isolate the devices at the time short circuit in SLC.
The module shall be suitable to provide communications isolation to improve installation
226 2 each
convenience and increase the system integrity. Isolation will be automatically activated when an
output short circuit is detected (also be suitable for manual operation for isolation and trouble shooting
for wiring problems).
The device shall be suitable for indoor use only. Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 90% RH at 35°C)
Approvals: UL listed / FM approved.
Supply and installation of "Exit light" complete with rechargeable battery and charge light and other
227 1 each
necessary accessories suitable for AC / DC power supply (220V single phase)
Supply and installation of "Evacuation light" complete with rechargeable battery and charge light and
228 other necessary accessories suitable for AC / 1 each
DC power supply (220V single phase)
Total of [2.2.3 STAFF ACCOMMODATION
BUILDING - FIRE FIGHTING WORKS]
Total in words USD of [2.2.3 STAFF
ACCOMMODATION BUILDING - FIRE
FIGHTING WORKS]
2.3.3 CANTEEN, BANK & ATM -
FIREFIGHTING WORKS
T.I.
Description Of Items of Works Quantity Unit
No.
FIRE PROTECTION EXTINGUISHER SYSTEM DRY CHEMICAL POWDER TYPE
Supply & fixing the following capacities multipurpose ABC dry chemical powder stored pressure
354 7 each
type with manometer system fire extinguisher suitable for repeated use complete with wall bracket, CO2
cartridge, easy refilling system etc. as per sample accepted & approved by the Engineer.
i. 5 Kg. capacity.
T.I.
Description Of Items of Works Quantity Unit
No.
Sensors shall be including a communication transmitter and receiver in the mounting base having a
unique identification and capability for status reporting to the FACP. Sensor address shall be located in
base to eliminate false addressing when replacing sensors.Removal of the sensor head for cleaning shall not
require the setting of addresses.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be : 0°
to 50°C shall be suitable for humidity range: 10% to 95% RH
Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min (0-
610m/min)
i. Approvals : UL listed / FM approved / LPCB approved
T.I.
Description Of Items of Works Quantity Unit
No.
UL listed temperature Range: 32° to 120° F (0° to 49° C) intended for indoor operation.
Humidity range: Up to 93% RH at 100°F (38°C)
Housing color shall be red with white raised lettering. Housing and pull lever shall be made with lexan
polycarbonate or equal.
The MCS shall be semi-flash / surface mount type. Approvals: UL listed/FM approved.
i. Addressable manual pull station : Double action 4 each
Addressable notification device (horn with strobe)
Supply & installation of addressable type horn with strobe for audible & visible application, combination of
audible & visible (A/V) notification appliances shall be listed to UL. The strobe light shall consist of a
xenon flash tube and associated lens / reflector system. Provide a label inside the strobe lens to indicate
358
the listed candela rating of the specific strobe. The horn shall have a minimum sound pressure level of 83 to
89 dBA @ 24VDC. The audible / visible enclosure shall mount directly to standard single gang, double
gang or 4" square electrical box, without the use of special adapters or trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
i. Approvals: UL listed / FM approved. 4 each
T.I.
Description Of Items of Works Quantity Unit
No.
Cooling system & engine exhaust pipe:
The engine shall be provided with close circuit cooling water circulation system shall be provided. The
exhaust shall be galvanized steel sized in accordance with the
manufacturer’s recommendations. The exhaust pipe shall be galvanized steel sized in accordance with the
manufacturer's recommendations. The exhaust pipe shall be as short as possible.
Controller :
The controller shall be UL listed / FM approved, completely assembled and wired from the factory. The
controller shall be 12 volt / 24 volt., and shall be complete with all necessary component and accessories.
The controller shall be operable automatically on sensing low pressure in the system and shall be provided
with a pressure-actuated switch having independent high & low calibrated adjustments. The
switch shall be responsive to water pressure in the fire protection system. The pressure-sensing
element of the switch shall be capable of a momentary surge pressure of 300 psi (minimum) without
losing its accuracy; suitable provision shall be made for relieving pressure to the pressure actuated
switch to allow testing of the operation of the controller and the pumping unit.
EFP type - I : (up to 6 storied building)
The pump shall have a capacity to handle 500 US GPM of water against a head of 262 feet (80 meter). UL
listed / FM approved.
PUMP CONTROL PANEL FOR MOTOR DRIVEN FIRE & JOCKEY PUMPS
Supply, installation of fire & jockey pump control panel complete with MCCB / MCB / magnetic
contactor / on-off push switch / indication lamp for phase indication, run, trip mode / ampere meter /
volt meter / overload selector switch / phase failure protection device / dry operation protection device /
volt guard / connector block / bus-bar / CT of rated capacity / ventilation fan / buzzer / cable lugs / and all
other accessories. The panel shall be well dressed in side for safety purpose and for looking good.
The panel shall be suitable for 3-phase 400 ± 5% volt 50Hz power supply. The panel shall with auto-
manual mode to operate the pumps controlled by pressure sensors. For fire pump the panel shall have
537 option to start the pump automatically by stop shall be manual. For jockey pump the panel shall be 2 each
suitable to start-stop the pump automatically controlled by pressure sensor.
Enclosure of the panel shall be made with 16 SWG sheet steel and shall be painted with powder coating of
red color approved as Fire code. Door of the panel shall be swing type with locking arrangement. Knob of
main MCCB shall be extended in front screen. The panel shall be wall mounted type with fixing
arrangement properly.
The panel shall be locally assembled in accordance with standard code of practice as NEMA / IEC /
VDE / BS standards comprising of required capacity.
Controller for FP type - I
Supply of fire hose of 2½" (63mm) dia. 30 meter long with hose rack frame & nipple suitable to
install inside the hydrant cabinet. The hose shall conforming to UL 19. The hose shall be UL listed / FM
approved & burst pressure shall be not less than 600 psi and working pressure 200 psi, shall be
made with special quality EPDM rubber as internal lining, suitable to withstand heat and polluted
water, heat and abrasion resistance, jacketting shall be made up of 100% polyester for extra strength. Hose
shall be 30 meter long in a single length and shall be with male coupling in one end other end with female
coupling. Couplings shall be bonded with hose with copper wire properly. Coupling shall be available in
NST or instantaneous couplings shall be made with bronze / aluminium alloy,
polished / hard anodized to confirm BS 336.
T.I.
Description Of Items of Works Quantity Unit
No.
Power supply (input power) shall be 240VAC. All circuits requiring system-operating power shall be 24
VDC and shall be individually fused at the control unit.
The incoming power to the system shall be supervised so that any power failure will be indicated at
the control unit. A green "power on" LED shall be displayed continuously while incoming power is present.
The system batteries shall be supervised so that a low battery or depleted battery condition or
disconnection of the battery shall be indicated at the control unit and displayed for the specific fault
type.
The system shall support 100% of addressable devices in alarm or operated at the same time, under
both primary (AC) and secondary (battery) power conditions.
Loss of primary power shall sound a trouble signal at the FACP. FACP shall indicate when the system is
operating on an alternate power supply.
Product data sheets for system components highlighted to indicate the specific products, features, or
functions required to meet this specification. Alternate or as-equal products submitted under this contract
must provide a detailed line-by-line comparison of how the submitted product meets, exceeds, or does not
comply with this specification.
Wiring diagrams, Shop drawings showing system details including location of FACP, all devices,
circuiting and details of graphic annunciator.
System power and battery charts with performance graphs and voltage drop calculations to assure that the
system will operate per the prescribed backup time periods and under all voltage conditions per UL and
NFPA standards.
System operation description including method of operation and supervision of each type of circuit and
sequence of operations for all manually and automatically initiated system inputs and outputs. A list of
all input and output points in the system shall be provided with a label indicating location or use of
IDC, NAC, relay, sensor, and auxiliary control circuits.
Alarm silence, system reset and priority to reset global and individual point acknowledge. Set system time
and date and clear event log, individual point access for control or parameter revisions.
Each RS port shall be capable of supporting and supervising a remote printer; the FACP shall
support as many as remote displays. The fire alarm control panel shall support five RS ports.
Cabinet shall be lockable steel enclosure. Arrange unit so all operations required for testing or for
normal care and maintenance of the system are performed from the front of the enclosure. If more than a
single unit is required to form a complete control unit, provide exactly matching modular unit
enclosures.
Operation and maintenance data for inclusion in operating and maintenance manual. Include data for
each type product, including all features and operating sequences, both automatic and manual. Provide
the names, addresses, and telephone numbers of service organizations.
Operating temperature range: 32° to 120°F (0° to 49°C)
Operating humidity range: Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Approvals: UL listed / FM approved. FACP 251-500 devices (maximum)
T.I.
Description Of Items of Works Quantity Unit
No.
Programming, testing & commissioning of addressable type fire alarm system by the competent
554 Engineer/ technical expert personnel and provide training to the nominated 1 each
personnel of Client to operate the system correctly and safely.
FACP for 251-500 addressable devices (max.)
Supply and Installation of Cables manufactured by Govt. of INDIA / BANGLADESH owned or shared
555
company Ltd. (Eastern cables) approved by the Engineer.
1C-2x1.5 sqmm (FR) cable with 1.5 sqmm (FR) ECC wire through PVC pipe of minimum
i. 2500 meter
inner Dia. 20 mm having wall thickness of 1.5 mm
C-2x2.5 sqmm (FR) cable with 2.5 sqmm (FR) ECC wire through PVC pipe of minimum inner
ii. 1600 meter
Dia. 25 mm having wall thickness of 1.5 mm
Supply and Installation of Outdoor Fire Protection Stand (2m x 1.5m x 2m) made by MS angle with 50
mm x 50 mm embedded inside concrete base 450x450x300(depth) ( below 0.75 meter from FGL).
556 On top of the frame two sided pitch roof shade will be made by GI sheet of 0.46 mm thick. The whole stand 19 nos
shall be painted with one primer coat red- oxide and two final coats of red synthetic enamel paint
complete as per the direction of Engineer in charge.
Sand Bucket-2 nos, Water bucket-1 nos. ABC Dry Chemical type Extinguisher (5.0 kg) 2 nos in steel
557 cabinet, Eye Shield (4 sets), Gas Mask ( 4 sets), Fire blanket (4 sets), Shovel 2 sets, Cutter 2 sets, Hand 19 sets
gloves 4 sets, Fire Resistive boot 4 sets, oxygen Cylinder 4 sets
558 Intentionally left blank
Total of [2.8.1 YARD - FIRE FIGHTING
WORKS]
Total in words USD of [2.8.1 YARD - FIRE
FIGHTING WORKS]
T.I.
Description Of Items of Works Quantity Unit
No.
Sensors shall be including a communication transmitter and receiver in the mounting base having a unique
identification and capability for status reporting to the FACP. Sensor address shall be located in base to
eliminate false addressing when replacing sensors.Removal of the sensor head for cleaning shall not
require the setting of addresses.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be : 0° to 50°C shall
be suitable for humidity range: 10% to 95% RH
Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min (0-
610m/min)
i. Approvals : UL listed / FM approved / LPCB approved
a. Supply & installation of addressable type heat detector / thermal sensor: combination fixed-temperature
and rate-of-rise unit with plug-in base and alarm indication lamp; 135° F fixed-temperature setting
except as indicated.
Thermal sensor shall be of the epoxy encapsulated electronic design. It shall be thermistor-based,
rate-compensated, self-restoring and shall not be affected by thermal lag.
The heat sensors of fixed temperature sensing shall be independent of rate of-rise sensing and
programmable to operate at 135° F or 155° F. Sensor rate-of-rise temperature detection shall be
selectable at the FACP for either 15° F or 20° F per minute.
The Heat Sensors shall have the capability to be programmed as a utility monitoring device to
monitor for temperature extremes in the range from 32-deg F to 155-deg F.UL listed temperature range shall
be: 0° to 38°C and operating temperature range shall be : 0° to 50°C
i. Shall be suitable for humidity range: 10% to 95% RH Housing color shall be frost white. Approvals: UL
listed/ FM approved.
T.I.
Description Of Items of Works Quantity Unit
No.
UL listed temperature Range: 32° to 120° F (0° to 49° C) intended for indoor operation.
Humidity range: Up to 93% RH at 100°F (38°C)
Housing color shall be red with white raised lettering. Housing and pull lever shall be made with lexan
polycarbonate or equal.
The MCS shall be semi-flash / surface mount type. Approvals: UL listed/FM approved.
i. Addressable manual pull station : Double action
T.I.
Description Of Items of Works Quantity Unit
No.
i. Supply and installation of "Exit light" complete with rechargeable battery and charge light and
632 1 each
other necessary accessories suitable for AC / DC power supply (220V single phase)
i. Supply and installation of "Evacuation light" complete with rechargeable battery and charge light and
633 1 each
other necessary accessories suitable for AC / DC power supply (220V single phase)
Total of [2.9.3 WATER SUPPLY & PUMP
ROOM - FIREFIGHTING WORKS]
Total in words USD of [2.9.3 WATER
SUPPLY & PUMP ROOM - FIREFIGHTING
WORKS]
T.I.
Description Of Items of Works Quantity Unit
No.
Sensors shall be including a communication transmitter and receiver in the mounting base having a
unique identification and capability for status reporting to the FACP. Sensor address shall be
located in base to eliminate false addressing when replacing sensors.Removal of the sensor head for
cleaning shall not require the setting of addresses.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be : 0° to 50°C
shall be suitable for humidity range: 10% to 95% RH
Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min (0-
610m/min)
i. Approvals : UL listed / FM approved / LPCB approved
Addressable modules
Isolator module / fault Isolator module
Supply & installation of addressable type isolator / fault Isolator module shall be used in the field wiring
between the devices (contractor shall propose the quantity and location in the system required) to detect &
isolate the devices at the time short circuit in SLC.
447 The module shall be suitable to provide communications isolation to improve installation convenience and
increase the system integrity. Isolation will be automatically activated when an output short circuit is
detected (also be suitable for manual operation for isolation and trouble shooting for wiring
problems).
The device shall be suitable for indoor use only. Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 90% RH at 35°C)
Supply & installation of addressable type photoelectric smoke detector c/w standard Base. Comply
with internationally accepted standard “smoke detectors for fire protective signaling systems."
Include the following features:
The detector shall be self-restoring: detectors do not require resetting or readjustment after actuation to
restore normal operation.
Sensors shall be with plug-In arrangement and associated electronic components are mounted in
a module that connects to a fixed base with a twist-locking plug connection. Base shall provide break-
off plastic tab that can be removed to engage the head/base locking mechanism. No special tools
shall be required to remove head once it has been locked. Removal of the detector head shall interrupt the
supervisory circuit of the fire alarm detection loop and cause a trouble signal at the control unit.
Sensors shall be with quick connect arrangement: Photoelectric sensor and electronics in a single
piece construction which shall twist-lock onto a mounting base that attaches to a standard electrical
box.
Each sensor base shall contain an LED that will flash each time it is scanned by the control Unit (once
every 4 seconds). In alarm condition, the sensor base LED shall be on steady.Each sensor base shall
contain a magnetically actuated test switch to provide for easy alarm testing at the sensor location.
T.I.
Description Of Items of Works Quantity Unit
No.
Each sensor shall be scanned by the Control Unit for its type identification to prevent inadvertent substitution
of another sensor type. Upon detection of a "wrong device", the control unit shall operate with the installed
device at the default alarm settings for that sensor; 2.5% obscuration for photoelectric
sensor, 1350 F and 150 F rate-of-rises for the heat sensor, but shall indicate a "Wrong Device" trouble
condition.The sensor's electronics shall be immune from false alarms caused by EMI and RFI.
Sensors shall be including a communication transmitter and receiver in the mounting base having a
unique identification and capability for status reporting to the FACP. Sensor address shall be
located in base to eliminate false addressing when replacing sensors. Removal of the sensor head for
cleaning shall not require the setting of addresses.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be : 0° to 50°C shall
be suitable for humidity range: 10% to 95% RH
Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min (0-
610m/min) 5 each
Approvals : UL listed / FM approved / LPCB approved
988 Addressable manual pull station
Supply & installation of addressable type manual call station of red LEXAN, with molded, raised-
letter operating instructions of contrasting color. Station will mechanically latch upon operation and remain
so until manually reset by opening with a key common with the control units.
Shall be with compact construction, suitable to electronics module enclosure minimizes dust infiltration.
Allows mounting in standard electrical boxes. Screw terminals for wiring connections.
Activation of the MCS will required a firm downward pull to activate the alarm switch. The pull
lever latches into the alarm position and remains extended out of the housing to provide a visible
indication.
UL listed temperature Range: 32° to 120° F (0° to 49° C) intended for indoor
operation.
Supply & installation of addressable type horn with strobe for audible & visible application,
combination of audible & visible (A/V) notification appliances shall be listed to UL. The strobe light
shall consist of a xenon flash tube and associated lens / reflector system. Provide a label inside the strobe lens
to indicate the listed candela rating of the specific strobe. The horn shall have a minimum sound pressure
level of 83 to 89 dBA @ 24VDC. The audible 1 each
/ visible enclosure shall mount directly to standard single gang, double gang or 4" square electrical box,
without the use of special adapters or trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
Approvals: UL listed / FM approved.
T.I.
Description Of Items of Works Quantity Unit
No.
1089 Addressable manual pull station 1 each
Supply & installation of addressable type manual call station of red LEXAN, with molded, raised- letter
operating instructions of contrasting color. Station will mechanically latch upon operation and remain so until
manually reset by opening with a key common with the control units.
Shall be with compact construction, suitable to electronics module enclosure minimizes dust
infiltration. Allows mounting in standard electrical boxes. Screw terminals for wiring
connections.
Activation of the MCS will required a firm downward pull to activate the alarm switch. The pull lever
latches into the alarm position and remains extended out of the housing to provide a visible
indication.
UL listed temperature Range: 32° to 120° F (0° to 49° C) intended for indoor operation. Humidity range: Up
to 93% RH at 100°F (38°C)
Housing color shall be red with white raised lettering. Housing and pull lever shall be made with
lexan polycarbonate or equal.
The MCS shall be semi-flash / surface mount type. Approvals: UL listed/FM approved.
Addressable manual pull station : Double action
Addressable modules
Isolator module / fault Isolator module
Supply & installation of addressable type isolator / fault Isolator module shall be used in the field wiring
between the devices (contractor shall propose the quantity and location in the system required) to
detect & isolate the devices at the time short circuit in SLC.
1091 The module shall be suitable to provide communications isolation to improve installation convenience 1 each
and increase the system integrity. Isolation will be automatically activated when an output short circuit is
detected (also be suitable for manual operation for isolation and trouble shooting for wiring problems).
The device shall be suitable for indoor use only. Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 90% RH at 35°C)
Approvals: UL listed / FM approved.
Supply & fixing the following capacities multipurpose ABC dry chemical powder stored
pressure type with manometer system fire extinguisher suitable for repeated use complete with
wall bracket, CO2 cartridge, easy refilling system etc. as per sample accepted & approved by the Engineer.
5 Kg. capacity.
Supply & installation of addressable type photoelectric smoke detector c/w standard Base. Comply
with internationally accepted standard “smoke detectors for fire protective signaling systems." Include
the following features:
The detector shall be self-restoring: detectors do not require resetting or readjustment after actuation to
restore normal operation.
Sensors shall be with plug-In arrangement and associated electronic components are mounted
in a module that connects to a fixed base with a twist-locking plug connection. Base shall provide
break-off plastic tab that can be removed to engage the head/base locking mechanism. No special tools
shall be required to remove head once it has been locked. Removal of the detector head shall
interrupt the supervisory circuit of the fire alarm detection loop and cause a trouble signal at the
control unit.
Sensors shall be with quick connect arrangement: Photoelectric sensor and
electronics in a single piece construction which shall twist-lock onto a mounting base that
attaches to a standard electrical box.
Each sensor base shall contain an LED that will flash each time it is scanned by the control Unit (once every
4 seconds). In alarm condition, the sensor base LED shall be on steady. Each sensor base shall contain a
magnetically actuated test switch to provide for easy alarm testing at the sensor location.
Each sensor shall be scanned by the Control Unit for its type identification to prevent inadvertent substitution
of another sensor type. Upon detection of a "wrong device", the control unit shall operate with the installed
device at the default alarm settings for that sensor; 2.5% obscuration for photoelectric
sensor, 1350 F and 150 F rate-of-rises for the heat sensor, but shall indicate a "Wrong Device" trouble
condition.The sensor's electronics shall be immune from false alarms caused by EMI and RFI.
Sensors shall be including a communication transmitter and receiver in the mounting base having a
unique identification and capability for status reporting to the FACP. Sensor address shall be
located in base to eliminate false addressing when replacing sensors.Removal of the sensor head for
cleaning shall not require the setting of addresses.
T.I.
Description Of Items of Works
No.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be : 0° to 50°C
shall be suitable for humidity range: 10% to 95% RH
Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min (0-
610m/min)
Approvals : UL listed / FM approved / LPCB approved
1277 Addressable type heat detector:
Supply & installation of addressable type heat detector / thermal sensor: combination fixed-
temperature and rate-of-rise unit with plug-in base and alarm indication lamp; 135° F fixed-temperature
setting except as indicated.
Thermal sensor shall be of the epoxy encapsulated electronic design. It shall be thermistor-based, rate-
compensated, self-restoring and shall not be affected by thermal lag.
The heat sensors of fixed temperature sensing shall be independent of rate-of rise sensing and programmable
to operate at 135° F or 155° F. Sensor rate-of- rise temperature detection shall be selectable at the FACP for
either 15° F or 20° F per minute.
The Heat Sensors shall have the capability to be programmed as a utility monitoring device to
monitor for temperature extremes in the range from 32- deg F to 155-deg F.UL listed temperature range
shall be: 0° to 38°C and operating temperature range shall be : 0° to 50°C
Shall be suitable for humidity range: 10% to 95% RH Housing color shall be frost white. Approvals:
UL listed/ FM approved.
Supply & installation of addressable type manual call station of red LEXAN, with molded, raised-
letter operating instructions of contrasting color. Station will mechanically latch upon operation and remain
so until manually reset by opening with a key common with the control units.
Shall be with compact construction, suitable to electronics module enclosure minimizes dust infiltration.
Allows mounting in standard electrical boxes. Screw terminals for wiring connections.
Activation of the MCS will required a firm downward pull to activate the alarm switch. The pull
lever latches into the alarm position and remains extended out of the housing to provide a visible
indication.
UL listed temperature Range: 32° to 120° F (0° to 49° C) intended for indoor operation.
Humidity range: Up to 93% RH at 100°F (38°C)
Housing color shall be red with white raised lettering. Housing and pull lever shall be made with lexan
polycarbonate or equal.
The MCS shall be semi-flash / surface mount type. Approvals: UL listed/FM approved.
Addressable manual pull station : Double action
T.I.
Description Of Items of Works
No.
1279 Addressable notification device (horn only) :
Supply & installation of addressable type audible horn for notification purpose shall contain an
electronic module and a selectable address setting. A visible LED on each appliance shall provide
verification of communications.
The device shall be suitable to program the high / low setting of the audible (horn) appliances by channel
from the addressable controller. The horn shall be red color with “FIRE" lettering.
Addressable horn shall be listed to UL. The horn shall be suitable to produce sound pressure level of 89
dBA @ 24VDC. The horn shall be suitable to mount directly to a standard single gang, double gang or
4" square electrical box, without the use of special adapter or trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
Approvals: UL listed / FM approved.
Supply & installation of addressable type horn with strobe for audible & visible application,
combination of audible & visible (A/V) notification appliances shall be listed to UL. The strobe light
shall consist of a xenon flash tube and associated lens / reflector system. Provide a label inside the strobe lens
to indicate the listed candela rating of the specific strobe. The horn shall have a minimum sound pressure
level of 83 to 89 dBA @ 24VDC. The audible
/ visible enclosure shall mount directly to standard single gang, double gang or 4" square electrical box,
without the use of special adapters or trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
Approvals: UL listed / FM approved.
Supply & installation of addressable type isolator / fault Isolator module shall be used in the field wiring
between the devices (contractor shall propose the quantity and location in the system required) to detect &
isolate the devices at the time short circuit in SLC.
The module shall be suitable to provide communications isolation to improve installation convenience and
increase the system integrity. Isolation will be automatically activated when an output short circuit is
detected (also be suitable for manual operation for isolation and trouble shooting for wiring
problems).
The device shall be suitable for indoor use only. Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 90% RH at 35°C)
Approvals: UL listed / FM approved.
SITCI of - Software for Access control & Time attendance with multi-
operator login and license for 5 operator clients and 2 server, alarm
management, reporting, time and attendance software with user defined
generic reporting and integration feature with fire detection and alarm
system (FDAS) & CCTV and the bidder shall consider the hardware server
1848 for the same. 1 No.