2.1.

3 ADMINISTRATIVE BUILDING-
FIREFIGHTING WORKS
T.I. No. Description Of Items of Works Quantity Unit
FIRE PROTECTION EXTINGUISHER SYSTEM DRY CHEMICAL POWDER TYPE
Supply & fixing the following capacities multipurpose ABC dry chemical powder stored pressure
101
type with manometer system fire extinguisher suitable for repeated use complete with wall bracket, CO2 9 each
i
cartridge, easy refilling system etc. as per sample accepted & approved by the Engineer.
5 Kg. capacity.
102 FIRE PROTECTION (HYDRANT) SYSTEM 3 each

Fire hydrant unit (1½" dia.) :


Each 1½" dia. fire hydrant unit shall be complete with the following components and accessories.
Supplying, fitting and fixing of unframed super quality 900mmx600mm size imported mirror of 5mm
thick with hard boards at the back with all necessary fittings including making holes in walls and
mending good the damages with cement mortar (1:4), mirror clip, S.S. Screw etc. all complete
i
and of approved quality as per direction of the Engineer-in- Charge.
Supply and installation of hose angle valve / landing valve of 1½" (40mm) shall be made with brass /
bronze with instantaneous female outlet. The valve shall be UL Listed / FM approved and working pressure
shall not be less than 10kg/cm². Inlet shall be threaded end type, shall be installed inside the hydrant
cabinet.

T.I. No. Description Of Items of Works Quantity Unit


ii Fire hose : 1½" dia. 3 each

Supply & installation of fire hose of 40mm dia. 30 meter long with hose rack frame & nipple suitable
to install inside the hydrant cabinet. The hose shall conform to UL 19. The hose shall be UL Listed / FM
approved & burst pressure shall be not less that 600 psi and working pressure 200 psi, shall be made with
special quality EPDM rubber as internal lining, suitable to withstand heat and polluted water, heat
and abrasion resistance, Jacketing shall be made up of 100% polyester for extra strength. Hose shall be
30meter long in a single length and shall be with male coupling in one end other end with female coupling.
Couplings shall be bonded with hose with copper wire properly. Coupling shall be available in
NST or instantaneous couplings shall be made with bronze / alluminium alloy, polished / hard
anodized to confirm IS 9109 and BS 336.

Jet / spray nozzle : 1½" dia.


Supply & installation of jet / spray nozzle having 40mm dia. male instantaneous coupling. The
nozzle shall be operable in three modes: jet - spray - shut off. The nozzle shall be light weight and
iii 3 each
easy operable. Construction of the nozzle shall be of brass or alluminium & nylon. Working
pressure shall be not less than 7Kg / Cm². Flow shall be not less than 100 lpm @ 7kg / cm². Nozzle shall be
installed inside the cabinet.

Fire hydrant unit (2½" dia.):


Each 2½" dia. fire hydrant unit shall be complete with the following components and accessories.
Hose angle valve (landing valve) : 2½" dia.
103 Supply and installation of Hose angle valve / landing valve of 2½" (63mm) shall be made with brass / 3 each
bronze with instantaneous female outlet. The valve shall be UL Listed /FM Approved and working pressure
shall not be less than 10kg/cm². Inlet shall be threaded end type, shall be installed inside the hydrant
cabinet.
T.I. No. Description Of Items of Works Quantity Unit

STEEL CABINET
Fabrication, supply & installation of hydrant
cabinet of suitable size (as per site
measurement and requirement / recommended
by the Engineering to accommodate landing
valve, hose, nozzle and coupling. The cabinet
shall 3 each
104 be with swing type door with or
without breakable tempered glass. The
cabinet shall be made with 18 SWG sheet
steel, powder coated of red
color.
Class - II cabinet ( for 1.5'' hose rack assembly)

a. Black steel pipe ERW, 40 schedule:


Supply and installation of black steel pipe ASTM A53 ERW, 40 schedule. The pipe work shall be included
105 with welded type tee, elbow, reducer etc. and also hangers / supports etc. completed. Pipe work (over ground)
shall be painted with red oxide primer. Underground pipes should be laid after wrapping with PVC tape after
using approved prior. Pipe wall thickness shall be as per mentioned for different diameters.
i 100 mm (4 inch) dia., wall thickness: 6.0mm 50 ft.
ii 65 mm (2½ inch) dia., wall thickness: 5.2mm 20 ft.
iii 40 mm (1½ inch) dia., wall thickness: 3.7mm 30 ft.
PRESSURE GAUGE : (UL listed / FM approved)
106 Supply and installation of 3.5'' - 4” dia.l type pressure gauges including supply of all accessories 1 each
and consumable. The range shall be 0-250 psi. UL/FM approved.
AUTO AIR-VENT VALVE
Supply & installation of auto air vent valve of 1 inch (25mm) dia. of 1" dia. inlet BSP, bronze made with
107 1 each
rubber ball and seat. The valve shall be suitable to release air from the fire hydrant pipes. Shall be
suitable to withstand pressure up to 10kg/cm².
T.I. No. Description Of Items of Works Quantity Unit
Addressable type photoelectric smoke detector
Supply & installation of addressable type photoelectric smoke detector c/w standard Base. Comply with
internationally accepted standard “smoke detectors for fire protective signaling systems." Include the
following features:
The detector shall be self-restoring: detectors do not require resetting or readjustment after actuation to
restore normal operation.
Sensors shall be with plug-In arrangement and associated electronic components are mounted in a
module that connects to a fixed base with a twist-locking plug connection. Base shall provide break-off
plastic tab that can be removed to engage the head/base locking mechanism. No special tools shall be
required to remove head once it has been locked. Removal of the detector head shall interrupt the supervisory
circuit of the fire alarm detection loop and cause a trouble signal at the control unit.
Sensors shall be with quick connect arrangement: Photoelectric sensor and electronics in a single piece
construction which shall twist-lock onto a mounting base that attaches to a standard electrical box.
Each sensor base shall contain an LED that will flash each time it is scanned by the control Unit (once every
4 seconds). In alarm condition, the sensor base LED shall be on steady. Each sensor base shall contain a
108 magnetically actuated test switch to provide for easy alarm testing at the sensor location. 71 each
Each sensor shall be scanned by the Control Unit for its type identification to prevent inadvertent
substitution of another sensor type. Upon detection of a "wrong device", the control unit shall
operate with the installed device at the default alarm settings for that sensor; 2.5%
obscuration for photoelectric sensor, 1350 F and 150 F rate-of-rises for the heat sensor, but shall indicate a
"Wrong Device" trouble condition.The sensor's electronics shall be immune from false alarms caused by
EMI and RFI.
Sensors shall be including a communication transmitter and receiver in the mounting base having a unique
identification and capability for status reporting to the FACP. Sensor address shall be located in base to
eliminate false addressing when replacing sensors.Removal of the sensor head for cleaning shall not
require the setting of addresses.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be :
0° to 50°C shall be suitable for humidity range: 10% to 95% RH
Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min (0-
610m/min)
Approvals : UL listed / FM approved / LPCB approved

T.I. No. Description Of Items of Works Quantity Unit

Addressable manual pull station


Supply & installation of addressable type manual call station of red LEXAN, with molded, raised-letter
operating instructions of contrasting color. Station will mechanically latch upon operation and
remain so until manually reset by opening with a key common with the control units.
Shall be with compact construction, suitable to electronics module enclosure minimizes dust
infiltration. Allows mounting in standard electrical boxes. Screw terminals for wiring connections.
Activation of the MCS will require a firm downward pull to activate the alarm switch. The pull
109 lever latches into the alarm position and remains extended out of the housing to provide a visible 4 each
indication.
UL listed temperature Range: 32° to 120° F (0° to 49° C) intended for indoor operation.
Humidity range: Up to 93% RH at 100°F (38°C)
Housing color shall be red with white raised lettering. Housing and pull lever shall be made with lexan
polycarbonate or equal.
The MCS shall be semi-flash / surface mount type. Approvals: UL listed/FM approved.
Addressable manual pull station : Double action

Addressable notification device (horn only) :


Supply & installation of addressable type audible horn for notification purpose shall contain an
electronic module and a selectable address setting. A visible LED on each appliance shall
provide verification of communications.
The device shall be suitable to program the high / low setting of the audible (horn) appliances by
110 channel from the addressable controller. The horn shall be red color with “FIRE" lettering. 1 each
Addressable horn shall be listed to UL. The horn shall be suitable to produce sound pressure level
of 89 dBA @ 24VDC. The horn shall be suitable to mount directly to a standard single gang,
double gang or 4" square electrical box, without the use of special adapter or trim rings.
Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 93% RH at 100°F (38°C) Approvals: UL listed / FM approved.

T.I. No. Description Of Items of Works Quantity Unit

Addressable notification device (horn with strobe)


Supply & installation of addressable type horn with strobe for audible & visible application,
combination of audible & visible (A/V) notification appliances shall be listed to UL. The strobe light
shall consist of a xenon flash tube and associated lens / reflector system. Provide a label inside the strobe
lens to indicate the listed candela rating of the specific strobe. The horn shall have a minimum sound
111 4 each
pressure level of 83 to 89 dBA @ 24VDC. The audible / visible enclosure shall mount directly to
standard single gang, double gang or 4" square electrical box, without the use of special adapters or
trim rings.
Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 93% RH at 100°F (38°C) Approvals: UL listed / FM approved.
Addressable modules
Isolator module / fault Isolator module
Supply & installation of addressable type isolator / fault Isolator module shall be used in the field
wiring between the devices (contractor shall propose the quantity and location in the system
required) to detect & isolate the devices at the time short circuit in SLC.
112 The module shall be suitable to provide communications isolation to improve installation 4 each
convenience and increase the system integrity. Isolation will be automatically activated when an
output short circuit is detected (also be suitable for manual operation for isolation and trouble shooting
for wiring problems).
The device shall be suitable for indoor use only. Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 90% RH at 35°C) Approvals: UL listed / FM approved.

Supply and installation of "Exit light" complete with rechargeable battery and charge light and other
113 necessary accessories suitable for AC / DC 3 each
power supply (220V single phase)
Supply and installation of "Evacuation light" complete with rechargeable battery and charge light and
114 3 each
other necessary accessories suitable for AC / DC power supply (220V single phase)
Total of [2.1.3 ADMINISTRATIVE
BUILDING-FIREFIGHTING WORKS]
Total in words USD of [2.1.3
ADMINISTRATIVE BUILDING-
FIREFIGHTING WORKS]
2.2.3 STAFF ACCOMMODATION
BUILDING - FIRE FIGHTING WORKS
T.I.
Description of Item of Works Quantity Unit
No.
220 FIRE PROTECTION EXTINGUISHER SYSTEM 3 each
DRY CHEMICAL POWDER TYPE
Supply & fixing the following capacities multipurpose ABC dry chemical powder stored pressure
type with manometer system fire extinguisher suitable for repeated use complete with wall bracket, CO2
cartridge, easy refilling system etc. as per sample accepted & approved by the Engineer.
5 Kg. capacity.

Addressable type photoelectric smoke detector


Supply & installation of addressable type photoelectric smoke detector c/w standard Base. Comply with
internationally accepted standard “smoke detectors for fire protective signaling systems." Include the
following features:
The detector shall be self-restoring: detectors do not require resetting or readjustment after actuation to
restore normal operation.
Sensors shall be with plug-In arrangement and associated electronic components are mounted in a
module that connects to a fixed base with a twist-locking plug connection. Base shall provide break-off
221 plastic tab that can be removed to engage the head/base locking mechanism. No special tools shall be 20 each
required to remove head once it has been locked. Removal of the detector head shall interrupt the
supervisory circuit of the fire alarm detection loop and cause a trouble signal at the control unit.
Sensors shall be with quick connect arrangement: Photoelectric sensor and electronics in a single piece
construction which shall twist-lock onto a mounting base that attaches to a standard electrical box.
Each sensor base shall contain an LED that will flash each time it is scanned by the control Unit
(once every 4 seconds). In alarm condition, the sensor base LED shall be on steady.Each sensor
base shall contain a magnetically actuated test switch to provide for easy alarm testing at the sensor
location.

T.I.
Description of Item of Works Quantity Unit
No.

Each sensor shall be scanned by the Control Unit for its type identification to prevent inadvertent
substitution of another sensor type. Upon detection of a "wrong device", the control unit shall
operate with the installed device at the default alarm settings for that sensor; 2.5%
obscuration for photoelectric sensor, 1350 F and 150 F rate-of-rises for the heat sensor, but shall indicate a
"Wrong Device" trouble condition.The sensor's electronics shall be immune from false alarms caused by
EMI and RFI.
Sensors shall be including a communication transmitter and receiver in the mounting base having a unique
identification and capability for status reporting to the FACP. Sensor address shall be located in base to
eliminate false addressing when replacing sensors. Removal of the sensor head for cleaning shall not
require the setting of addresses.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be : 0°
to 50°C shall be suitable for humidity range: 10% to 95% RH
Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min (0-
610m/min)
Approvals : UL listed / FM approved / LPCB approved

222 Addressable type heat detector: 1 each


Supply & installation of addressable type heat detector / thermal sensor: combination fixed-temperature and
rate-of-rise unit with plug-in base and alarm indication lamp; 135° F fixed-temperature setting
except as indicated.
Thermal sensor shall be of the epoxy encapsulated electronic design. It shall be thermistor-based,
rate-compensated, self-restoring and shall not be affected by thermal lag.
The heat sensors of fixed temperature sensing shall be independent of rate-of-rise sensing and
programmable to operate at 135° F or 155° F. Sensor rate-of-rise temperature detection shall be
selectable at the FACP for either 15° F or 20° F per minute.
The Heat Sensors shall have the capability to be programmed as a utility monitoring device to monitor
for temperature extremes in the range from 32-deg F to 155-deg F.UL listed temperature range shall be: 0° to
38°C and operating temperature range shall be : 0° to 50°C Shall be suitable for humidity range: 10%
to 95% RH Housing color shall be frost white.
Approvals: UL listed/ FM approved.

T.I.
Description of Item of Works Quantity Unit
No.

Addressable manual pull station


Supply & installation of addressable type manual call station of red LEXAN, with molded, raised-letter
operating instructions of contrasting color. Station will mechanically latch upon operation and
remain so until manually reset by opening with a key common with the control units.
Shall be with compact construction, suitable to electronics module enclosure minimizes dust
infiltration. Allows mounting in standard electrical boxes. Screw terminals for wiring connections.
Activation of the MCS will required a firm downward pull to activate the alarm switch. The pull lever
223 latches into the alarm position and remains extended out of the housing to provide a visible indication. 1 each
UL listed temperature Range: 32° to 120° F (0° to 49° C) intended for indoor operation.
Humidity range: Up to 93% RH at 100°F (38°C)
Housing color shall be red with white raised lettering. Housing and pull lever shall be made with lexan
polycarbonate or equal.
The MCS shall be semi-flash / surface mount type.
Approvals: UL listed/FM approved.
Addressable manual pull station : Double action

224 Addressable notification device (horn only) : 1 each

Supply & installation of addressable type audible horn for notification purpose shall contain an
electronic module and a selectable address setting. A visible LED on each appliance shall
provide verification of communications.
The device shall be suitable to program the high / low setting of the audible (horn) appliances by
channel from the addressable controller. The horn shall be red color with “FIRE" lettering.
Addressable horn shall be listed to UL. The horn shall be suitable to produce sound pressure level of
89 dBA @ 24VDC. The horn shall suitable to mount directly to a standard single gang, double gang or
4" square electrical box, without the use of special adapter or trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
Approvals: UL listed / FM approved.

T.I.
Description of Item of Works Quantity Unit
No.

Addressable notification device (horn with strobe)


Supply & installation of addressable type horn with strobe for audible & visible application,
combination of audible & visible (A/V) notification appliances shall be listed to UL. The strobe light
shall consist of a xenon flash tube and associated lens / reflector system. Provide a label inside the strobe
lens to indicate the listed candela rating of the specific strobe. The horn shall have a minimum sound
225 1 each
pressure level of 83 to 89 dBA @ 24VDC. The audible / visible enclosure shall mount directly to
standard single gang, double gang or 4" square electrical box, without the use of special adapters or
trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
Approvals: UL listed / FM approved.

Addressable modules
Isolator module / fault Isolator module
Supply & installation of addressable type isolator / fault Isolator module shall be used in the field
wiring between the devices (contractor shall propose the quantity and location in the system
required) to detect & isolate the devices at the time short circuit in SLC.
The module shall be suitable to provide communications isolation to improve installation
226 2 each
convenience and increase the system integrity. Isolation will be automatically activated when an
output short circuit is detected (also be suitable for manual operation for isolation and trouble shooting
for wiring problems).
The device shall be suitable for indoor use only. Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 90% RH at 35°C)
Approvals: UL listed / FM approved.

Supply and installation of "Exit light" complete with rechargeable battery and charge light and other
227 1 each
necessary accessories suitable for AC / DC power supply (220V single phase)
Supply and installation of "Evacuation light" complete with rechargeable battery and charge light and
228 other necessary accessories suitable for AC / 1 each
DC power supply (220V single phase)
Total of [2.2.3 STAFF ACCOMMODATION
BUILDING - FIRE FIGHTING WORKS]
Total in words USD of [2.2.3 STAFF
ACCOMMODATION BUILDING - FIRE
FIGHTING WORKS]
2.3.3 CANTEEN, BANK & ATM -
FIREFIGHTING WORKS
T.I.
Description Of Items of Works Quantity Unit
No.
FIRE PROTECTION EXTINGUISHER SYSTEM DRY CHEMICAL POWDER TYPE
Supply & fixing the following capacities multipurpose ABC dry chemical powder stored pressure
354 7 each
type with manometer system fire extinguisher suitable for repeated use complete with wall bracket, CO2
cartridge, easy refilling system etc. as per sample accepted & approved by the Engineer.
i. 5 Kg. capacity.

Addressable type photoelectric smoke detector


Supply & installation of addressable type photoelectric smoke detector c/w standard Base. Comply
with internationally accepted standard “smoke detectors for fire protective signaling systems."
Include the following features:
The detector shall be self-restoring: detectors do not require resetting or readjustment after actuation to
restore normal operation.
Sensors shall be with plug-In arrangement and associated electronic components are mounted in a
module that connects to a fixed base with a twist-locking plug connection. Base shall provide break-off
plastic tab that can be removed to engage the head/base locking mechanism. No special tools shall be
required to remove head once it has been locked. Removal of the detector head shall interrupt the
supervisory circuit of the fire alarm detection loop and cause a trouble signal at the control unit.
355 Sensors shall be with quick connect arrangement: Photoelectric sensor 28 each
and electronics in a single piece construction which shall twist-lock onto a mounting base that attaches to a
standard electrical box.
Each sensor base shall contain an LED that will flash each time it is scanned by the control Unit
(once every 4 seconds). In alarm condition, the sensor base LED shall be on steady. Each sensor base shall
contain a magnetically actuated test switch to provide for easy alarm testing at the sensor location.
Each sensor shall be scanned by the Control Unit for its type identification to prevent
inadvertent substitution of another sensor type. Upon detection of a "wrong device", the control unit shall
operate with the installed device at the default alarm settings for that sensor; 2.5%
obscuration for photoelectric sensor, 1350 F and 150 F rate-of-rises for the heat sensor, but
shall indicate a "Wrong Device" trouble condition.The sensor's electronics shall be immune
from false alarms caused by EMI and RFI.

T.I.
Description Of Items of Works Quantity Unit
No.

Sensors shall be including a communication transmitter and receiver in the mounting base having a
unique identification and capability for status reporting to the FACP. Sensor address shall be located in
base to eliminate false addressing when replacing sensors.Removal of the sensor head for cleaning shall not
require the setting of addresses.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be : 0°
to 50°C shall be suitable for humidity range: 10% to 95% RH
Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min (0-
610m/min)
i. Approvals : UL listed / FM approved / LPCB approved

Addressable type heat detector:


Supply & installation of addressable type heat detector / thermal sensor: combination fixed-temperature and
rate-of-rise unit with plug-in base and alarm indication lamp; 135° F fixed-temperature setting except
as indicated.
Thermal sensor shall be of the epoxy encapsulated electronic design. It shall be thermistor-based, rate-
compensated, self-restoring and shall not be affected by thermal lag.
The heat sensors of fixed temperature sensing shall be independent of rate-of-rise sensing and
356 1 each
programmable to operate at 135° F or 155° F. Sensor rate-of-rise temperature detection shall be
selectable at the FACP for either 15° F or 20° F per minute.
The Heat Sensors shall have the capability to be programmed as a utility monitoring device to monitor for
temperature extremes in the range from 32-deg F to 155-deg F.UL listed temperature range shall be:
0° to 38°C and operating temperature range shall be : 0° to 50°C
i. Shall be suitable for humidity range: 10% to 95% RH Housing color shall be frost white. Approvals: UL
listed/ FM approved.

Addressable manual pull station


Supply & installation of addressable type manual call station of red LEXAN, with molded, raised-
letter operating instructions of contrasting color. Station will mechanically latch upon operation and
remain so until manually reset by opening with a key common with the control units.
357 Shall be with compact construction, suitable to electronics module enclosure minimizes dust
infiltration. Allows mounting in standard electrical boxes. Screw terminals for wiring connections.
Activation of the MCS will required a firm downward pull to activate the
alarm switch. The pull lever latches into the alarm position and remains extended out of the housing to
provide a visible indication.

T.I.
Description Of Items of Works Quantity Unit
No.
UL listed temperature Range: 32° to 120° F (0° to 49° C) intended for indoor operation.
Humidity range: Up to 93% RH at 100°F (38°C)
Housing color shall be red with white raised lettering. Housing and pull lever shall be made with lexan
polycarbonate or equal.
The MCS shall be semi-flash / surface mount type. Approvals: UL listed/FM approved.
i. Addressable manual pull station : Double action 4 each
Addressable notification device (horn with strobe)
Supply & installation of addressable type horn with strobe for audible & visible application, combination of
audible & visible (A/V) notification appliances shall be listed to UL. The strobe light shall consist of a
xenon flash tube and associated lens / reflector system. Provide a label inside the strobe lens to indicate
358
the listed candela rating of the specific strobe. The horn shall have a minimum sound pressure level of 83 to
89 dBA @ 24VDC. The audible / visible enclosure shall mount directly to standard single gang, double
gang or 4" square electrical box, without the use of special adapters or trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
i. Approvals: UL listed / FM approved. 4 each

Isolator module / fault Isolator module


Supply & installation of addressable type isolator / fault Isolator module shall be used in the field wiring
between the devices (contractor shall propose the quantity and location in the system required) to
detect & isolate the devices at the time short circuit in SLC.
The module shall be suitable to provide communications isolation to improve installation
359
convenience and increase the system integrity. Isolation will be automatically activated when an
output short circuit is detected (also be suitable for manual operation for isolation and trouble shooting for
wiring problems).
The device shall be suitable for indoor use only. Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 90% RH at 35°C)

i. Approvals: UL listed / FM approved. 2 each


Supply and installation of "Exit light" complete with rechargeable battery and charge light and
360 other necessary accessories suitable for AC 3 each
/ DC power supply (220V single phase)
Supply and installation of "Evacuation light" complete with rechargeable battery and charge light and other
361 3 each
necessary accessories suitable for AC / DC power supply (220V single phase)
T.I.
Description Of Items of Works Quantity Unit
No.
Total of [2.3.3 CANTEEN, BANK & ATM -
FIREFIGHTING WORKS]
Total in words USD of [2.3.3 CANTEEN,
BANK & ATM - FIREFIGHTING WORKS]

2.8. YARD - FIREFIGHTING - SUMMARY


2.8.1 YARD - FIRE FIGHTING WORKS
T.I.
Description Of Items of Works Quantity Unit
No.
FIRE PROTECTION EXTINGUISHER SYSTEM DRY CHEMICAL POWDER TYPE
Supply & fixing the following capacities multipurpose ABC dry chemical powder stored pressure
type with manometer system fire extinguisher suitable for repeated use complete with wall
532 30 each
bracket, CO2 cartridge, easy refilling system etc. as per sample accepted & approved by the
Engineer.
5 Kg. capacity.

FIRE PROTECTION (HYDRANT) SYSTEM FIRE WATER PUMP


(Engine driven) General :
Supply & installation of diesel engine driven fire pump complete with all related & essential
accessories. The pump shall be designed and installed in accordance with globally accepted international
standard. Each unit shall be tested and UL listed/FM approved.
Type: Pumps shall be of the non-overloading, centrifugal, and horizontally split, double suction type
with suction and discharge connections in the lower half of the casing, allowing removal of the
rotating element without disturbing the pipe connections and operating at not over 3000 rpm. Pumps
shall be selected for a total efficiency of not less than 65%. Pump performance curves shall be submitted
for approval together with the pump technical data.
Diesel engine :
The diesel engine brake horsepower shall be listed by UL / approved by FM suitable for rated
pump capacity. The engine shall rate at standard conditions for 500 ft above sea level at 29.4°C by
533 the testing laboratory. The engine shall be of a reputed manufacturer from which spare parts can be 2 each
obtained locally. The engine shall be provided with an adjustable governor capable of regulating engine
speed with a range of 10% between shut- off and maximum load conditions of the pump. The governor shall
be set to maintain the rated pump speed at maximum pump load.
Battery & charger :
The engine shall be provided with two maintenance free storage battery units, each having sufficient
capacity, at 5°C (41°F) to maintain cranking speed recommended by the engine manufacturer through a 6
min cycle. Two means for recharging shall be provided. One shall be the generator furnished with
the engine. The other shall be an automatically controlled charger taking power from the building power
supply.
Fuel tank :
The fuel tank shall be as per manufacturer's recommendation with rigid frame. Fuel tank shall have
capacity at least equal to 1 gallon per horsepower plus 5% volume for expansion. Fuel tank
shall be equipped with fuel supply line, return line, fill, drain, overflow, air vent and sight glass.

T.I.
Description Of Items of Works Quantity Unit
No.
Cooling system & engine exhaust pipe:
The engine shall be provided with close circuit cooling water circulation system shall be provided. The
exhaust shall be galvanized steel sized in accordance with the
manufacturer’s recommendations. The exhaust pipe shall be galvanized steel sized in accordance with the
manufacturer's recommendations. The exhaust pipe shall be as short as possible.
Controller :
The controller shall be UL listed / FM approved, completely assembled and wired from the factory. The
controller shall be 12 volt / 24 volt., and shall be complete with all necessary component and accessories.
The controller shall be operable automatically on sensing low pressure in the system and shall be provided
with a pressure-actuated switch having independent high & low calibrated adjustments. The
switch shall be responsive to water pressure in the fire protection system. The pressure-sensing
element of the switch shall be capable of a momentary surge pressure of 300 psi (minimum) without
losing its accuracy; suitable provision shall be made for relieving pressure to the pressure actuated
switch to allow testing of the operation of the controller and the pumping unit.
EFP type - I : (up to 6 storied building)
The pump shall have a capacity to handle 500 US GPM of water against a head of 262 feet (80 meter). UL
listed / FM approved.

FIRE WATER PUMP


(Motor driven)
MFP type - I : (up to 6 storied building)
Supply & installation of electrically driven centrifugal type end suction, vertical discharge Fire Water Pump
manufactured according to globally accepted international standard shall be complete with skid mounted,
534 coupled with motor, safety cover etc. Motor shall be 420V / 3 phase / 50 HZ / 2900 rpm / Class F 2 each
insulation / Enclose IP55. Motor capacity shall be as per NFPA 20. and performance curve (from
manufacturer) shall be provided to verify pump performance. The pump shall have a capacity to
handle 500 US GPM of water against a head of 263 Feet (80 Meter). [30 kw minimum but need to
conform to
NFPA 20]

535 JOCKEY PUMP 2 each


(Pressure maintenance pump)
Jockey pump ( For 1 to 20 storied building)
Supply, installation of multistage jockey pump manufactured according to globally accepted
international standard or fire hydrant system to keep a certain pressure in water distribution system. Capacity
of the pump shall be 20 US GPM against a head of 263-394 feet (80-120 meter) of water. Pump shall be
complete with motor suitable to meet performance curve of the pump. The motor shall be 420V / 3 phase/
50 HZ / 2900 rpm. [3
kw minimum but need to conform to NFPA 20]
T.I.
Description Of Items of Works Quantity Unit
No.
536 FIRE BRIGADE CONNECTION 1 each
Fire brigade connection : 4 - way
Supply and installation of 4 - way fire brigade connection complete in all respect with all accessories. The
unit shall have two Inlet connections of 2½" (63mm) male instantaneous with non-return valve and having 6"
dia. (150mm) flanged type outlet directly connected with stand pipe. It will have also one 25mm dia. drain
valve for drainage of water, rubber blank cap and chain for protection. Outlet 150mm dia. shall be as per
ANSI-B-16B-16.5B. Shall be suitable to withstand pressure of 20kg/cm². Shall be manufactured
according to BS standard & suitable for using with fire service & civil defence department of
BANGLADESH.

PUMP CONTROL PANEL FOR MOTOR DRIVEN FIRE & JOCKEY PUMPS
Supply, installation of fire & jockey pump control panel complete with MCCB / MCB / magnetic
contactor / on-off push switch / indication lamp for phase indication, run, trip mode / ampere meter /
volt meter / overload selector switch / phase failure protection device / dry operation protection device /
volt guard / connector block / bus-bar / CT of rated capacity / ventilation fan / buzzer / cable lugs / and all
other accessories. The panel shall be well dressed in side for safety purpose and for looking good.
The panel shall be suitable for 3-phase 400 ± 5% volt 50Hz power supply. The panel shall with auto-
manual mode to operate the pumps controlled by pressure sensors. For fire pump the panel shall have
537 option to start the pump automatically by stop shall be manual. For jockey pump the panel shall be 2 each
suitable to start-stop the pump automatically controlled by pressure sensor.
Enclosure of the panel shall be made with 16 SWG sheet steel and shall be painted with powder coating of
red color approved as Fire code. Door of the panel shall be swing type with locking arrangement. Knob of
main MCCB shall be extended in front screen. The panel shall be wall mounted type with fixing
arrangement properly.
The panel shall be locally assembled in accordance with standard code of practice as NEMA / IEC /
VDE / BS standards comprising of required capacity.
Controller for FP type - I

538 Fire hydrant unit (2½" dia.):


Each 2½" dia. fire hydrant unit shall be complete with the following components and
accessories.
a. Hose angle valve (landing valve) : 2½" dia. 26 each
Supply and installation of Hose angle valve / landing valve of 2½" (63mm) shall be made with brass /
bronze with instantaneous female outlet. The valve shall be UL Listed /FM Approved and working
pressure shall not be less than 10kg/cm². Inlet shall be threaded end type, shall be installed inside the
hydrant cabinet.
T.I.
Description Of Items of Works Quantity Unit
No.
b. Fire hose : 2½" dia. 26 each

Supply of fire hose of 2½" (63mm) dia. 30 meter long with hose rack frame & nipple suitable to
install inside the hydrant cabinet. The hose shall conforming to UL 19. The hose shall be UL listed / FM
approved & burst pressure shall be not less than 600 psi and working pressure 200 psi, shall be
made with special quality EPDM rubber as internal lining, suitable to withstand heat and polluted
water, heat and abrasion resistance, jacketting shall be made up of 100% polyester for extra strength. Hose
shall be 30 meter long in a single length and shall be with male coupling in one end other end with female
coupling. Couplings shall be bonded with hose with copper wire properly. Coupling shall be available in
NST or instantaneous couplings shall be made with bronze / aluminium alloy,
polished / hard anodized to confirm BS 336.

c. Jet / spray nozzle : 2½" dia. 26 each


Supply & installation of jet / spray nozzle having 2½" (63mm) dia. male instantaneous coupling.
The nozzle shall be operable in three modes: jet - spray - shut off. The nozzle shall be light weight
and easy operable. Construction of the nozzle shall be of aluminium and nylon. Working pressure shall be
not less than 7Kg / Cm². Flow shall be not less than 150 lpm @ 7kg / cm². Nozzle shall be installed inside
the cabinet.
539 PILLAR HYDRANT 26 each
Pillar hydrant : Double headed
Supply and installation of cast Iron body double dead end pillar hydrant complete with 2 (two) nos. cast
brass made controllable outlet of 65mm dia. with female instantaneous outlet, Inlet shall be 100mm
dia. flanged end. The hydrant shall be suitable to withstand test pressure of 300 psi (minimum). Color
of the unit shall be red / approved by the manufacturer or as per code. Pillar hydrant Shall be BS
standard.
540 STEEL CABINET 26 each
Fabrication, supply & installation of hydrant cabinet of suitable size (as per site measurement
and requirement / recommended by the Engineer to accommodate landing valve, hose, nozzle and coupling.
The cabinet shall be with swing type door with or without breakable tempered glass. The cabinet shall be
made with 18 SWG sheet steel, powder
coated of red color.
Class - I cabinet ( for 2.5'' hose rack assembly)
541 Black steel pipe ERW, 40 schedule:
a.Supply and installation of black steel pipe ASTM A53 ERW, 40 schedule. The pipe work shall be included
with welded type tee, elbow, reducer etc. and also hangers / supports etc. completed. Pipe work (over ground)
shall be painted with red oxide primer.
Underground pipes should be laid after wrapping with PVC tape after using approved prior. Pipe wall
thickness shall be as per mentioned for different diameters.
i. i.200 mm (8 inch) dia., wall thickness: 8.2mm 60 ft
ii. ii.150 mm (6 inch) dia., wall thickness: 7.1mm 2250 ft
iii. iii.100 mm (4 inch) dia., wall thickness: 6.0mm 512 ft
iv. iv.65 mm (2½ inch) dia., wall thickness: 5.2mm 140 ft
v. v.50 mm (2 inch) dia., wall thickness: 3.9mm 60 ft
vi. vi.40 mm (1½ inch) dia., wall thickness: 3.7mm 200 ft
vii. vii.25 mm (1inch) dia., wall thickness: 3.4mm 96 ft
T.I.
Description Of Items of Works Quantity Unit
No.
542 VALVES & FITTINGS
GATE VALVES
Supply & installation of valves & fittings complies with ANSI, flange / groove type, temperature
range: 00C-800C; working pressure: 200 PSI minimum, valve body as per ASTM A536, 65-45-12
standard, UL / FM approved.
OS & Y GATE VALVES
i. 150 mm (6 inch) dia. 11 each
ii. 100 mm (4 inch) dia. 28 each
iii. 50 mm (2 inch) dia. 4 each
543
RESILIENT SWING CHECK VALVES :
a.
i. 150 mm (6 inch) dia. 5 each
ii. 100 mm (4 inch) dia. 1 each
iii. 50 mm (2 inch) dia. 2 each
b. Y-STRAINERS
i. 150 mm (6 inch) dia. 4 each
ii. 50 mm (2 inch) dia. 2 each
544 FLEXIBLE JOINT :
Supply & installation of flexible joint complies with ANSI, temperature range: 00 C-8 working
a. pressure: 200 PSI minimum, valve body as per ASTM A536, 65-45-12 standard, UL
/ FM approved.
i. 50 mm (6 inch) dia. 8 each
ii. 65 mm (2½ inch) dia. 4 each
545 BALL VALVES class : PN20, UL / FM approved.
a.Supply & installation of ball valves complies with ANSI, temperature range: 00C-800C ; working
pressure: 200 PSI minimum, valve body as per ASTM A536, 65-45-12 standard, UL
/ FM approved.
i 50 mm (2 inch) dia. 12 each
ii 40 mm (1½ inch) dia. 12 each
546 PRESSURE GAUGE : (UL listed / FM approved) 16 each
Supply and installation of 3.5'' - 4” dia.l type pressure gauges including supply of all accessories and
consumable. The range shall be 0-250 psi. UL/FM approved.
547 PRESSURE SWITCH 6 each
Supply, installation and testing of pressure switch complete with sensing element, enclosure
material, 15 mm NPT pressure connection, direct mounting electrical connection, other material
etc. accepted / approved by the Engineer
548 PRESSURE RELIEF VALVE 1 each
Supply, installation and testing of 80 mm dia. pressure relief valve to automatically relieve excess pressure in
fire protection pumping systems. Valve body as per ASTM A536 65-45- 12 and available pressure relief
range 100-300 PSI. Inlet / outlet shall be flanged / threaded
end type.
UL listed or FM approved.
T.I.
Description Of Items of Works Quantity Unit
No.
549 AUTO AIR-VENT VALVE 2 each
Supply & installation of auto air vent valve of 1 inch (25mm) dia. of 1" dia. inlet BSP, bronze
made with rubber ball and seat. The valve shall be suitable to release air from the
fire hydrant pipes. Shall be suitable to withstand pressure up to 10kg/cm².
550 FLOW SWITCH 1 each
Supply & installation of 50-100 mm dia. flow switch of leaf type suitable for installation within
65mm and 40mm dia. water hydrant pipe. The flow shall sense flow of water within pipe and send signal to
water flow monitoring panel. Flow switch shall be under control of water flow supervisory panel to ensure
the hydrant operation. Power supply shall be
24VDC. The flow switch shall be UL listed.
Flow switch : 50-100mm dia.
551 Pressure reducing valve : 40mm dia. 1 each
Supply & installation of pressure reducing valve of 1½" (40mm) dia., brass body, screwed end type, shall
be used with 40mm dia. internal hydrant unit (where to reduce high pressure is necessary). Valve body
shall be made with hot pressed brass, seat of stainless steel ANSI304 shall be suitable for 80°C. Initial
pressure shall be 15 bar, adjustable final pressure shall be 0.5bar (min), 7bar (max)
552 Balancing, testing & commissioning of fire hydrant system. 1 job
For level : 1 to 6

ADDRESSABLE TYPE FIRE DETECTION & ALARM SYSTEM


Addressable type fire alarm control panel
Supply & installation of addressable type fire alarm control panel complete with following basic options.
Master controller assembly / CPU shall be suitable with port to add voice alarm system / fire fighter
telephone system / Printer / remote annunciator etc. FACP must be complying with internationally
accepted standard. Control units for fire - protective signaling systems.
Addressable fire alarm control panel shall be complete, non-coded, addressable, microprocessor
based with initiating devices, notification appliances, and monitoring and control devices.
Annunciation: Operation of alarm and supervisory initiating devices shall be annunciated at the FACP
indicating the location and type of device.
Environmental compensation: The FACP shall maintain a moving average of the sensor's smoke chamber
value to automatically compensate for dust, dirt, and other conditions that could affect detection
553 1 each
operations.
Programmable sensitivity: Photoelectric smoke sensors shall have various sensitivity levels ranging
from (±) 0.2% up to 3.7%, programmed and monitored from the FACP.
The FACP shall be provided with sufficient battery capacity to operate the entire system upon loss of
normal AC power in a normal supervisory mode for a period of 24 hours with 5 minutes of alarm
operation at the end of this period. The system shall automatically transfer to battery standby upon
power failure. All battery charging and recharging operations shall be automatic.
Battery: Sealed lead-acid. Provide sufficient capacity to operate the complete alarm system in normal
or supervisory (non-alarm) mode for a period of 24 hours. Following this period of operation on battery
power, the battery shall have sufficient capacity to operate all components of the system, including all alarm
indicating devices in alarm or supervisory
mode for a period of 5 minutes.

T.I.
Description Of Items of Works Quantity Unit
No.
Power supply (input power) shall be 240VAC. All circuits requiring system-operating power shall be 24
VDC and shall be individually fused at the control unit.
The incoming power to the system shall be supervised so that any power failure will be indicated at
the control unit. A green "power on" LED shall be displayed continuously while incoming power is present.
The system batteries shall be supervised so that a low battery or depleted battery condition or
disconnection of the battery shall be indicated at the control unit and displayed for the specific fault
type.
The system shall support 100% of addressable devices in alarm or operated at the same time, under
both primary (AC) and secondary (battery) power conditions.
Loss of primary power shall sound a trouble signal at the FACP. FACP shall indicate when the system is
operating on an alternate power supply.
Product data sheets for system components highlighted to indicate the specific products, features, or
functions required to meet this specification. Alternate or as-equal products submitted under this contract
must provide a detailed line-by-line comparison of how the submitted product meets, exceeds, or does not
comply with this specification.
Wiring diagrams, Shop drawings showing system details including location of FACP, all devices,
circuiting and details of graphic annunciator.
System power and battery charts with performance graphs and voltage drop calculations to assure that the
system will operate per the prescribed backup time periods and under all voltage conditions per UL and
NFPA standards.
System operation description including method of operation and supervision of each type of circuit and
sequence of operations for all manually and automatically initiated system inputs and outputs. A list of
all input and output points in the system shall be provided with a label indicating location or use of
IDC, NAC, relay, sensor, and auxiliary control circuits.
Alarm silence, system reset and priority to reset global and individual point acknowledge. Set system time
and date and clear event log, individual point access for control or parameter revisions.
Each RS port shall be capable of supporting and supervising a remote printer; the FACP shall
support as many as remote displays. The fire alarm control panel shall support five RS ports.
Cabinet shall be lockable steel enclosure. Arrange unit so all operations required for testing or for
normal care and maintenance of the system are performed from the front of the enclosure. If more than a
single unit is required to form a complete control unit, provide exactly matching modular unit
enclosures.
Operation and maintenance data for inclusion in operating and maintenance manual. Include data for
each type product, including all features and operating sequences, both automatic and manual. Provide
the names, addresses, and telephone numbers of service organizations.
Operating temperature range: 32° to 120°F (0° to 49°C)
Operating humidity range: Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Approvals: UL listed / FM approved. FACP 251-500 devices (maximum)
T.I.
Description Of Items of Works Quantity Unit
No.
Programming, testing & commissioning of addressable type fire alarm system by the competent
554 Engineer/ technical expert personnel and provide training to the nominated 1 each
personnel of Client to operate the system correctly and safely.
FACP for 251-500 addressable devices (max.)
Supply and Installation of Cables manufactured by Govt. of INDIA / BANGLADESH owned or shared
555
company Ltd. (Eastern cables) approved by the Engineer.
1C-2x1.5 sqmm (FR) cable with 1.5 sqmm (FR) ECC wire through PVC pipe of minimum
i. 2500 meter
inner Dia. 20 mm having wall thickness of 1.5 mm
C-2x2.5 sqmm (FR) cable with 2.5 sqmm (FR) ECC wire through PVC pipe of minimum inner
ii. 1600 meter
Dia. 25 mm having wall thickness of 1.5 mm
Supply and Installation of Outdoor Fire Protection Stand (2m x 1.5m x 2m) made by MS angle with 50
mm x 50 mm embedded inside concrete base 450x450x300(depth) ( below 0.75 meter from FGL).
556 On top of the frame two sided pitch roof shade will be made by GI sheet of 0.46 mm thick. The whole stand 19 nos
shall be painted with one primer coat red- oxide and two final coats of red synthetic enamel paint
complete as per the direction of Engineer in charge.
Sand Bucket-2 nos, Water bucket-1 nos. ABC Dry Chemical type Extinguisher (5.0 kg) 2 nos in steel
557 cabinet, Eye Shield (4 sets), Gas Mask ( 4 sets), Fire blanket (4 sets), Shovel 2 sets, Cutter 2 sets, Hand 19 sets
gloves 4 sets, Fire Resistive boot 4 sets, oxygen Cylinder 4 sets
558 Intentionally left blank
Total of [2.8.1 YARD - FIRE FIGHTING
WORKS]
Total in words USD of [2.8.1 YARD - FIRE
FIGHTING WORKS]

2.9.3 WATER SUPPLY & PUMP ROOM -


FIREFIGHTING WORKS
T.I.
Description Of Items of Works Quantity Unit
No.
624 FIRE PROTECTION EXTINGUISHER SYSTEM 5 each
a. DRY CHEMICAL POWDER TYPE
i. Supply & fixing the following capacities multipurpose ABC dry chemical powder stored pressure
type with manometer system fire extinguisher suitable for repeated use complete with wall bracket,
CO2 cartridge, easy refilling system etc. as per sample accepted & approved by the Engineer.
5 Kg. capacity.
625 Addressable type photoelectric smoke detector 9 each
a. Supply & installation of addressable type photoelectric smoke detector c/w standard Base. Comply
with internationally accepted standard “smoke detectors for fire protective signaling systems." Include
the following features:
The detector shall be self-restoring: detectors do not require resetting or readjustment after actuation to
restore normal operation.
Sensors shall be with plug-In arrangement and associated electronic components are mounted in a
module that connects to a fixed base with a twist-locking plug connection. Base shall provide break-off
plastic tab that can be removed to engage the head/base locking mechanism. No special tools shall be
required to remove head once it has been locked. Removal of the detector head shall interrupt the
supervisory circuit of the fire alarm detection loop and cause a trouble signal at the control unit.
Sensors shall be with quick connect arrangement: Photoelectric sensor and electronics in a single piece
construction which shall twist-lock onto a mounting base that attaches to a standard electrical box.
Each sensor base shall contain an LED that will flash each time it is scanned by the control Unit (once every
4 seconds). In alarm condition, the sensor base LED shall be on steady.Each sensor base shall contain a
magnetically actuated test switch to provide for easy alarm testing at the sensor location.
Each sensor shall be scanned by the Control Unit for its type identification to prevent inadvertent substitution
of another sensor type. Upon detection of a "wrong device", the control unit shall operate with the installed
device at the default alarm settings for that sensor; 2.5% obscuration for
photoelectric sensor, 1350 F and 150 F rate-of-rises for the heat sensor, but shall indicate a "Wrong
Device" trouble condition.The sensor's electronics shall be immune from false alarms caused by EMI and
RFI.

T.I.
Description Of Items of Works Quantity Unit
No.

Sensors shall be including a communication transmitter and receiver in the mounting base having a unique
identification and capability for status reporting to the FACP. Sensor address shall be located in base to
eliminate false addressing when replacing sensors.Removal of the sensor head for cleaning shall not
require the setting of addresses.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be : 0° to 50°C shall
be suitable for humidity range: 10% to 95% RH
Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min (0-
610m/min)
i. Approvals : UL listed / FM approved / LPCB approved

626 Addressable type heat detector: 3 each

a. Supply & installation of addressable type heat detector / thermal sensor: combination fixed-temperature
and rate-of-rise unit with plug-in base and alarm indication lamp; 135° F fixed-temperature setting
except as indicated.
Thermal sensor shall be of the epoxy encapsulated electronic design. It shall be thermistor-based,
rate-compensated, self-restoring and shall not be affected by thermal lag.
The heat sensors of fixed temperature sensing shall be independent of rate of-rise sensing and
programmable to operate at 135° F or 155° F. Sensor rate-of-rise temperature detection shall be
selectable at the FACP for either 15° F or 20° F per minute.
The Heat Sensors shall have the capability to be programmed as a utility monitoring device to
monitor for temperature extremes in the range from 32-deg F to 155-deg F.UL listed temperature range shall
be: 0° to 38°C and operating temperature range shall be : 0° to 50°C
i. Shall be suitable for humidity range: 10% to 95% RH Housing color shall be frost white. Approvals: UL
listed/ FM approved.

Addressable manual pull station


a. Supply & installation of addressable type manual call station of red LEXAN, with molded, raised-
letter operating instructions of contrasting color. Station will mechanically latch upon operation and
remain so until manually reset by opening with a key common with the control units.
627 Shall be with compact construction, suitable to electronics module enclosure minimizes dust 2 each
infiltration. Allows mounting in standard electrical boxes. Screw terminals for wiring connections.
Activation of the MCS will required a firm downward pull to activate the alarm switch. The pull
lever latches into the alarm position and remains extended out of the housing to provide a visible
indication.

T.I.
Description Of Items of Works Quantity Unit
No.
UL listed temperature Range: 32° to 120° F (0° to 49° C) intended for indoor operation.
Humidity range: Up to 93% RH at 100°F (38°C)
Housing color shall be red with white raised lettering. Housing and pull lever shall be made with lexan
polycarbonate or equal.
The MCS shall be semi-flash / surface mount type. Approvals: UL listed/FM approved.
i. Addressable manual pull station : Double action

Addressable notification device (horn only) :


a. Supply & installation of addressable type audible horn for notification purpose shall contain an
electronic module and a selectable address setting. A visible LED on each appliance shall
provide verification of communications.
b. The device shall be suitable to program the high / low setting of the audible (horn) appliances by
channel from the addressable controller. The horn shall be red color with “FIRE" lettering.
628 1 each
c. Addressable horn shall be listed to UL. The horn shall be suitable to produce sound pressure level
of 89 dBA @ 24VDC. The horn shall suitable to mount directly to a standard single gang, double gang
or 4" square electrical box, without the use of special adapter or trim rings.
d. Shall be suitable to temperature range : 0° to 50° C
e. Humidity range: Up to 93% RH at 100°F (38°C)
i. Approvals: UL listed / FM approved.
Addressable notification device (horn with strobe)
a. Supply & installation of addressable type horn with strobe for audible & visible application,
combination of audible & visible (A/V) notification appliances shall be listed to UL. The strobe
light shall consist of a xenon flash tube and associated lens / reflector system. Provide a label inside the
strobe lens to indicate the listed candela rating of the specific strobe. The horn shall have a minimum sound
629 1 each
pressure level of 83 to 89 dBA @ 24VDC. The audible / visible enclosure shall mount directly to standard
single gang, double gang or 4" square electrical box, without the use of special adapters or trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
i. Approvals: UL listed / FM approved.
d. Addressable modules

T.I.
Description Of Items of Works Quantity Unit
No.

Isolator module / fault Isolator module


a. Supply & installation of addressable type isolator / fault Isolator module shall be used in the field
wiring between the devices (contractor shall propose the quantity and location in the system
required) to detect & isolate the devices at the time short circuit in SLC.
The module shall be suitable to provide communications isolation to improve installation
630 convenience and increase the system integrity. Isolation will be automatically activated when an 4 each
output short circuit is detected (also be suitable for manual operation for isolation and trouble
shooting for wiring problems).
The device shall be suitable for indoor use only. Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 90% RH at 35°C)
i. Approvals: UL listed / FM approved.

Addressable relay / control module


a. Supply & installation of addressable relay / control module shall be used in the field wiring to connect
the conventional Initiating devices with the addressable FACP interfaces to control / operate
dampers, motors or similar appliances on receiving signal from the FACP as when as required
631 25 each
(configured by the service provider).
The device shall be suitable for indoor use only and shall be with back box.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 90% RH at 35°C)
i. Approvals: UL listed / FM approved.

i. Supply and installation of "Exit light" complete with rechargeable battery and charge light and
632 1 each
other necessary accessories suitable for AC / DC power supply (220V single phase)
i. Supply and installation of "Evacuation light" complete with rechargeable battery and charge light and
633 1 each
other necessary accessories suitable for AC / DC power supply (220V single phase)
Total of [2.9.3 WATER SUPPLY & PUMP
ROOM - FIREFIGHTING WORKS]
Total in words USD of [2.9.3 WATER
SUPPLY & PUMP ROOM - FIREFIGHTING
WORKS]

2.4.3 SECURITY BUILDINGS - 2 Nos -


FIREFIGHTING WORKS
T.I.
Description Of Items of Works Quantity Unit
No.
FIRE PROTECTION EXTINGUISHER SYSTEM DRY CHEMICAL POWDER TYPE
Supply & fixing the following capacities multipurpose ABC dry chemical powder stored
443 pressure type with manometer system fire extinguisher suitable for repeated use complete with
wall bracket, CO2 cartridge, easy
refilling system etc. as per sample accepted & approved by the Engineer.
i. 5 Kg. capacity. 2 each

Addressable type photoelectric smoke detector


Supply & installation of addressable type photoelectric smoke detector c/w standard Base. Comply
with internationally accepted standard “smoke detectors for fire protective signaling systems." Include
the following features:
The detector shall be self-restoring: detectors do not require resetting or readjustment after actuation to
restore normal operation.
Sensors shall be with plug-In arrangement and associated electronic components are mounted
in a module that connects to a fixed base with a twist-locking plug connection. Base shall provide
break-off plastic tab that can be removed to engage the head/base locking mechanism. No special tools
shall be required to remove head once it has been locked. Removal of the detector head shall
interrupt the supervisory circuit of the fire alarm detection loop and cause a trouble signal at the
444 control unit. 6 each
Sensors shall be with quick connect arrangement: Photoelectric sensor and electronics in a single
piece construction which shall twist-lock onto a mounting base that attaches to a standard electrical
box.
Each sensor base shall contain an LED that will flash each time it is scanned by the control Unit (once
every 4 seconds). In alarm condition, the sensor base LED shall be on steady.Each sensor base shall
contain a magnetically actuated test switch to provide for easy alarm testing at the sensor location.
Each sensor shall be scanned by the Control Unit for its type identification to prevent inadvertent substitution
of another sensor type. Upon detection of a "wrong device", the control unit shall operate with the installed
device at the default alarm settings for that sensor; 2.5% obscuration for photoelectric
sensor, 1350 F and 150 F rate-of-rises for the heat sensor, but shall indicate a "Wrong Device" trouble
condition.The sensor's electronics shall be immune from false alarms caused by EMI and RFI.

T.I.
Description Of Items of Works Quantity Unit
No.
Sensors shall be including a communication transmitter and receiver in the mounting base having a
unique identification and capability for status reporting to the FACP. Sensor address shall be
located in base to eliminate false addressing when replacing sensors.Removal of the sensor head for
cleaning shall not require the setting of addresses.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be : 0° to 50°C
shall be suitable for humidity range: 10% to 95% RH
Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min (0-
610m/min)
i. Approvals : UL listed / FM approved / LPCB approved

Addressable manual pull station


Supply & installation of addressable type manual call station of red LEXAN, with molded, raised-letter
operating instructions of contrasting color. Station will mechanically latch upon operation and remain so
until manually reset by opening with a key common with the control units.
Shall be with compact construction, suitable to electronics module enclosure minimizes dust infiltration.
Allows mounting in standard electrical boxes. Screw terminals for wiring connections.
Activation of the MCS will required a firm downward pull to activate the alarm switch. The pull
445 lever latches into the alarm position and remains extended out of the housing to provide a visible
indication.
UL listed temperature Range: 32° to 120° F (0° to 49° C) intended for indoor operation.
Humidity range: Up to 93% RH at 100°F (38°C)
Housing color shall be red with white raised lettering. Housing and pull lever shall be made with lexan
polycarbonate or equal.
The MCS shall be semi-flash / surface mount type.
Approvals: UL listed/FM approved.

i. Addressable manual pull station : Double action 2 each


Addressable notification device (horn with strobe)
Supply & installation of addressable type horn with strobe for audible & visible application,
combination of audible & visible (A/V) notification appliances shall be listed to UL. The strobe light
shall consist of a xenon flash tube and associated lens / reflector system. Provide a label inside the strobe
446
lens to indicate the listed candela rating of the specific strobe. The horn shall have a minimum sound pressure
level of 83 to 89 dBA @ 24VDC. The audible / visible enclosure shall mount directly to standard single
gang, double gang or 4" square electrical box, without the use of special adapters or trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
i. Approvals: UL listed / FM approved. 2 each
T.I.
Description Of Items of Works Quantity Unit
No.

Addressable modules
Isolator module / fault Isolator module
Supply & installation of addressable type isolator / fault Isolator module shall be used in the field wiring
between the devices (contractor shall propose the quantity and location in the system required) to detect &
isolate the devices at the time short circuit in SLC.
447 The module shall be suitable to provide communications isolation to improve installation convenience and
increase the system integrity. Isolation will be automatically activated when an output short circuit is
detected (also be suitable for manual operation for isolation and trouble shooting for wiring
problems).
The device shall be suitable for indoor use only. Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 90% RH at 35°C)

i. Approvals: UL listed / FM approved. 4 each


Total of [2.4.3 SECURITY BUILDINGS - 2
Nos - FIREFIGHTING WORKS]
Total in words USD of [2.4.3 SECURITY
BUILDINGS - 2 Nos - FIREFIGHTING
WORKS]

2.14.3 FUEL STATION BUILDING -


FIREFIGHTING WORKS
T.I.
Description Of Items of Works Quantity Unit
No.
986 FIRE PROTECTION EXTINGUISHER SYSTEM
DRY CHEMICAL POWDER TYPE
Supply & fixing the following capacities multipurpose ABC dry chemical powder stored pressure
type with manometer system fire extinguisher suitable for repeated use complete with wall
4 each
bracket, CO2 cartridge, easy refilling system etc. as per sample accepted & approved by the Engineer.
5 Kg. capacity.
987 Addressable type photoelectric smoke detector

Supply & installation of addressable type photoelectric smoke detector c/w standard Base. Comply
with internationally accepted standard “smoke detectors for fire protective signaling systems."
Include the following features:
The detector shall be self-restoring: detectors do not require resetting or readjustment after actuation to
restore normal operation.
Sensors shall be with plug-In arrangement and associated electronic components are mounted in
a module that connects to a fixed base with a twist-locking plug connection. Base shall provide break-
off plastic tab that can be removed to engage the head/base locking mechanism. No special tools
shall be required to remove head once it has been locked. Removal of the detector head shall interrupt the
supervisory circuit of the fire alarm detection loop and cause a trouble signal at the control unit.
Sensors shall be with quick connect arrangement: Photoelectric sensor and electronics in a single
piece construction which shall twist-lock onto a mounting base that attaches to a standard electrical
box.
Each sensor base shall contain an LED that will flash each time it is scanned by the control Unit (once
every 4 seconds). In alarm condition, the sensor base LED shall be on steady.Each sensor base shall
contain a magnetically actuated test switch to provide for easy alarm testing at the sensor location.
T.I.
Description Of Items of Works Quantity Unit
No.

Each sensor shall be scanned by the Control Unit for its type identification to prevent inadvertent substitution
of another sensor type. Upon detection of a "wrong device", the control unit shall operate with the installed
device at the default alarm settings for that sensor; 2.5% obscuration for photoelectric
sensor, 1350 F and 150 F rate-of-rises for the heat sensor, but shall indicate a "Wrong Device" trouble
condition.The sensor's electronics shall be immune from false alarms caused by EMI and RFI.
Sensors shall be including a communication transmitter and receiver in the mounting base having a
unique identification and capability for status reporting to the FACP. Sensor address shall be
located in base to eliminate false addressing when replacing sensors. Removal of the sensor head for
cleaning shall not require the setting of addresses.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be : 0° to 50°C shall
be suitable for humidity range: 10% to 95% RH

Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min (0-
610m/min) 5 each
Approvals : UL listed / FM approved / LPCB approved
988 Addressable manual pull station

Supply & installation of addressable type manual call station of red LEXAN, with molded, raised-
letter operating instructions of contrasting color. Station will mechanically latch upon operation and remain
so until manually reset by opening with a key common with the control units.
Shall be with compact construction, suitable to electronics module enclosure minimizes dust infiltration.
Allows mounting in standard electrical boxes. Screw terminals for wiring connections.
Activation of the MCS will required a firm downward pull to activate the alarm switch. The pull
lever latches into the alarm position and remains extended out of the housing to provide a visible
indication.
UL listed temperature Range: 32° to 120° F (0° to 49° C) intended for indoor
operation.

Humidity range: Up to 93% RH at 100°F (38°C)


Housing color shall be red with white raised lettering. Housing and pull lever shall be made with lexan
polycarbonate or equal.
1 each
The MCS shall be semi-flash / surface mount type.
Approvals: UL listed/FM approved.
Addressable manual pull station : Double action
T.I.
Description Of Items of Works Quantity Unit
No.
989 Addressable notification device (horn with strobe)

Supply & installation of addressable type horn with strobe for audible & visible application,
combination of audible & visible (A/V) notification appliances shall be listed to UL. The strobe light
shall consist of a xenon flash tube and associated lens / reflector system. Provide a label inside the strobe lens
to indicate the listed candela rating of the specific strobe. The horn shall have a minimum sound pressure
level of 83 to 89 dBA @ 24VDC. The audible 1 each
/ visible enclosure shall mount directly to standard single gang, double gang or 4" square electrical box,
without the use of special adapters or trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
Approvals: UL listed / FM approved.

Total of [2.14.3 FUEL STATION BUILDING


- FIREFIGHTING WORKS]
Total in words USD of [2.14.3 FUEL
STATION BUILDING - FIREFIGHTING
WORKS]

2.15.3 RECEIVING SUBSTATION


BUILDING - FIREFIGHTING WORKS
T.I.
Description Of Items of Works Quantity Unit
No.
1087 FIRE PROTECTION EXTINGUISHER SYSTEM 3 each
DRY CHEMICAL POWDER TYPE
Supply & fixing the following capacities multipurpose ABC dry chemical powder stored pressure type with
manometer system fire extinguisher suitable for repeated use complete with wall bracket, CO2
cartridge, easy refilling system etc. as per sample accepted & approved by the Engineer.
5 Kg. capacity.
Addressable type photoelectric smoke detector
Supply & installation of addressable type photoelectric smoke detector c/w standard Base. Comply
with internationally accepted standard “smoke detectors for fire protective signaling systems." Include
the following features:
The detector shall be self-restoring: detectors do not require resetting or readjustment after actuation
to restore normal operation.
Sensors shall be with plug-In arrangement and associated electronic components are mounted in a module
that connects to a fixed base with a twist-locking plug connection. Base shall provide break-off plastic tab
that can be removed to engage the head/base locking mechanism. No special tools shall be required to
remove head once it has been locked. Removal of the detector head shall interrupt the supervisory circuit of
the fire alarm detection loop and cause a trouble signal at the control unit.
Sensors shall be with quick connect arrangement: Photoelectric sensor and electronics in a single
piece construction which shall twist-lock onto a mounting base that attaches to a standard electrical box.
Each sensor base shall contain an LED that will flash each time it is scanned by the control Unit (once every
4 seconds). In alarm condition, the sensor base LED shall be on steady. Each sensor base shall contain a
1088 magnetically actuated test switch to provide for easy alarm testing at the sensor location. 12 each
Each sensor shall be scanned by the Control Unit for its type identification to prevent inadvertent substitution
of another sensor type. Upon detection of a "wrong device", the control unit shall operate with the installed
device at the default alarm settings for that sensor; 2.5% obscuration for photoelectric sensor, 1350 F and 150
F rate-of-rises for the heat sensor, but shall indicate a
"Wrong Device" trouble condition.The sensor's electronics shall be immune from false alarms caused
by EMI and RFI.
Sensors shall be including a communication transmitter and receiver in the mounting base having a
unique identification and capability for status reporting to the FACP. Sensor address shall be located
in base to eliminate false addressing when replacing sensors. Removal of the sensor head for cleaning
shall not require the setting of addresses.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be : 0° to 50°C shall
be suitable for humidity range: 10% to 95% RH
Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min
(0-610m/min)
Approvals : UL listed / FM approved / LPCB approved

T.I.
Description Of Items of Works Quantity Unit
No.
1089 Addressable manual pull station 1 each

Supply & installation of addressable type manual call station of red LEXAN, with molded, raised- letter
operating instructions of contrasting color. Station will mechanically latch upon operation and remain so until
manually reset by opening with a key common with the control units.
Shall be with compact construction, suitable to electronics module enclosure minimizes dust
infiltration. Allows mounting in standard electrical boxes. Screw terminals for wiring
connections.
Activation of the MCS will required a firm downward pull to activate the alarm switch. The pull lever
latches into the alarm position and remains extended out of the housing to provide a visible
indication.
UL listed temperature Range: 32° to 120° F (0° to 49° C) intended for indoor operation. Humidity range: Up
to 93% RH at 100°F (38°C)
Housing color shall be red with white raised lettering. Housing and pull lever shall be made with
lexan polycarbonate or equal.
The MCS shall be semi-flash / surface mount type. Approvals: UL listed/FM approved.
Addressable manual pull station : Double action

1090 Addressable notification device (horn with strobe) 2 each


Supply & installation of addressable type horn with strobe for audible & visible application,
combination of audible & visible (A/V) notification appliances shall be listed to UL. The strobe light shall
consist of a xenon flash tube and associated lens / reflector system. Provide a label inside the strobe lens to
indicate the listed candela rating of the specific strobe. The horn shall have a minimum sound pressure level
of 83 to 89 dBA @ 24VDC. The audible / visible enclosure shall mount directly to standard single gang,
double gang or 4" square electrical box, without the use of special adapters or trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
Approvals: UL listed / FM approved.

Addressable modules
Isolator module / fault Isolator module
Supply & installation of addressable type isolator / fault Isolator module shall be used in the field wiring
between the devices (contractor shall propose the quantity and location in the system required) to
detect & isolate the devices at the time short circuit in SLC.
1091 The module shall be suitable to provide communications isolation to improve installation convenience 1 each
and increase the system integrity. Isolation will be automatically activated when an output short circuit is
detected (also be suitable for manual operation for isolation and trouble shooting for wiring problems).
The device shall be suitable for indoor use only. Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 90% RH at 35°C)
Approvals: UL listed / FM approved.

Total of [2.15.3 RECEIVING SUBSTATION


BUILDING - FIREFIGHTING WORKS]
Total in words USD of [2.15.3 RECEIVING
SUBSTATION BUILDING - FIREFIGHTING
WORKS]
2.19.3 SITE OFFICE - FIREFIGHTING
WORKS
T.I.
Description Of Items of Works
No.
1275 FIRE PROTECTION EXTINGUISHER SYSTEM
DRY CHEMICAL POWDER TYPE

Supply & fixing the following capacities multipurpose ABC dry chemical powder stored
pressure type with manometer system fire extinguisher suitable for repeated use complete with
wall bracket, CO2 cartridge, easy refilling system etc. as per sample accepted & approved by the Engineer.
5 Kg. capacity.

1276 Addressable type photoelectric smoke detector

Supply & installation of addressable type photoelectric smoke detector c/w standard Base. Comply
with internationally accepted standard “smoke detectors for fire protective signaling systems." Include
the following features:
The detector shall be self-restoring: detectors do not require resetting or readjustment after actuation to
restore normal operation.
Sensors shall be with plug-In arrangement and associated electronic components are mounted
in a module that connects to a fixed base with a twist-locking plug connection. Base shall provide
break-off plastic tab that can be removed to engage the head/base locking mechanism. No special tools
shall be required to remove head once it has been locked. Removal of the detector head shall
interrupt the supervisory circuit of the fire alarm detection loop and cause a trouble signal at the
control unit.
Sensors shall be with quick connect arrangement: Photoelectric sensor and
electronics in a single piece construction which shall twist-lock onto a mounting base that
attaches to a standard electrical box.
Each sensor base shall contain an LED that will flash each time it is scanned by the control Unit (once every
4 seconds). In alarm condition, the sensor base LED shall be on steady. Each sensor base shall contain a
magnetically actuated test switch to provide for easy alarm testing at the sensor location.
Each sensor shall be scanned by the Control Unit for its type identification to prevent inadvertent substitution
of another sensor type. Upon detection of a "wrong device", the control unit shall operate with the installed
device at the default alarm settings for that sensor; 2.5% obscuration for photoelectric
sensor, 1350 F and 150 F rate-of-rises for the heat sensor, but shall indicate a "Wrong Device" trouble
condition.The sensor's electronics shall be immune from false alarms caused by EMI and RFI.
Sensors shall be including a communication transmitter and receiver in the mounting base having a
unique identification and capability for status reporting to the FACP. Sensor address shall be
located in base to eliminate false addressing when replacing sensors.Removal of the sensor head for
cleaning shall not require the setting of addresses.

T.I.
Description Of Items of Works
No.
UL listed temperature range shall be: 0° to 38°C and operating temperature range shall be : 0° to 50°C
shall be suitable for humidity range: 10% to 95% RH
Housing color shall be Frost White. Smoke sensor ambient ratings : Air velocity = 0-2000 ft/min (0-
610m/min)
Approvals : UL listed / FM approved / LPCB approved
1277 Addressable type heat detector:

Supply & installation of addressable type heat detector / thermal sensor: combination fixed-
temperature and rate-of-rise unit with plug-in base and alarm indication lamp; 135° F fixed-temperature
setting except as indicated.
Thermal sensor shall be of the epoxy encapsulated electronic design. It shall be thermistor-based, rate-
compensated, self-restoring and shall not be affected by thermal lag.
The heat sensors of fixed temperature sensing shall be independent of rate-of rise sensing and programmable
to operate at 135° F or 155° F. Sensor rate-of- rise temperature detection shall be selectable at the FACP for
either 15° F or 20° F per minute.
The Heat Sensors shall have the capability to be programmed as a utility monitoring device to
monitor for temperature extremes in the range from 32- deg F to 155-deg F.UL listed temperature range
shall be: 0° to 38°C and operating temperature range shall be : 0° to 50°C
Shall be suitable for humidity range: 10% to 95% RH Housing color shall be frost white. Approvals:
UL listed/ FM approved.

1278 Addressable manual pull station

Supply & installation of addressable type manual call station of red LEXAN, with molded, raised-
letter operating instructions of contrasting color. Station will mechanically latch upon operation and remain
so until manually reset by opening with a key common with the control units.
Shall be with compact construction, suitable to electronics module enclosure minimizes dust infiltration.
Allows mounting in standard electrical boxes. Screw terminals for wiring connections.
Activation of the MCS will required a firm downward pull to activate the alarm switch. The pull
lever latches into the alarm position and remains extended out of the housing to provide a visible
indication.
UL listed temperature Range: 32° to 120° F (0° to 49° C) intended for indoor operation.
Humidity range: Up to 93% RH at 100°F (38°C)
Housing color shall be red with white raised lettering. Housing and pull lever shall be made with lexan
polycarbonate or equal.
The MCS shall be semi-flash / surface mount type. Approvals: UL listed/FM approved.
Addressable manual pull station : Double action

T.I.
Description Of Items of Works
No.
1279 Addressable notification device (horn only) :

Supply & installation of addressable type audible horn for notification purpose shall contain an
electronic module and a selectable address setting. A visible LED on each appliance shall provide
verification of communications.
The device shall be suitable to program the high / low setting of the audible (horn) appliances by channel
from the addressable controller. The horn shall be red color with “FIRE" lettering.
Addressable horn shall be listed to UL. The horn shall be suitable to produce sound pressure level of 89
dBA @ 24VDC. The horn shall be suitable to mount directly to a standard single gang, double gang or
4" square electrical box, without the use of special adapter or trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
Approvals: UL listed / FM approved.

1280 Addressable notification device (horn with strobe)

Supply & installation of addressable type horn with strobe for audible & visible application,
combination of audible & visible (A/V) notification appliances shall be listed to UL. The strobe light
shall consist of a xenon flash tube and associated lens / reflector system. Provide a label inside the strobe lens
to indicate the listed candela rating of the specific strobe. The horn shall have a minimum sound pressure
level of 83 to 89 dBA @ 24VDC. The audible
/ visible enclosure shall mount directly to standard single gang, double gang or 4" square electrical box,
without the use of special adapters or trim rings.
Shall be suitable to temperature range : 0° to 50° C Humidity range: Up to 93% RH at 100°F (38°C)
Approvals: UL listed / FM approved.

1281 Addressable modules


Isolator module / fault Isolator module

Supply & installation of addressable type isolator / fault Isolator module shall be used in the field wiring
between the devices (contractor shall propose the quantity and location in the system required) to detect &
isolate the devices at the time short circuit in SLC.
The module shall be suitable to provide communications isolation to improve installation convenience and
increase the system integrity. Isolation will be automatically activated when an output short circuit is
detected (also be suitable for manual operation for isolation and trouble shooting for wiring
problems).
The device shall be suitable for indoor use only. Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 90% RH at 35°C)
Approvals: UL listed / FM approved.

Supply and installation of "Exit light" complete with rechargeable battery


1282
and charge light and other necessary accessories suitable for AC / DC power supply (220V single phase)
Supply and installation of "Evacuation light" complete with rechargeable battery and charge light and
1283 other necessary accessories suitable for AC / DC
power supply (220V single phase)
T.I.
Description Of Items of Works
No.
Total of [2.19.3 SITE OFFICE -
FIREFIGHTING WORKS]
Total in words USD of [2.19.3 SITE OFFICE -
FIREFIGHTING WORKS]
5A.4. CEMENT SHED
Fire fighting (Fire extinguishers inside sheds) complete as per drawing &
1579 specifications 6 Nos
5A.5. FERTILIZER SHED
1613 Fire fighting (Fire extinguishers inside sheds) 10 Nos
5A.6. OTHER DRY BULK SHED
1647 Fire fighting (Fire extinguishers inside sheds) 8 Nos
5A.7. FOOD GRAIN SHED
1681 Fire fighting (Fire extinguishers inside sheds) 10 Nos
5A.8. OTHER BREAK BULK SHED
1715 Fire fighting (Fire extinguishers inside sheds) 6 Nos
6A.5 COST ESTIMATE FOR SECURITY & SURVEILLANCE SYSTEMS

SITCI of - Software for Access control & Time attendance with multi-
operator login and license for 5 operator clients and 2 server, alarm
management, reporting, time and attendance software with user defined
generic reporting and integration feature with fire detection and alarm
system (FDAS) & CCTV and the bidder shall consider the hardware server
1848 for the same. 1 No.