INFRAGROUP CONSULTANTS BILL OF QUANTITY

PORTO MANYA ELECTRICAL


& LOW CURRENT NETWORK
Item Description Unit Qty Unit Price Total

1 PACKAGE SUBSTATION
1-1 Supply, install, connect and test IP54 type tested power
package substation consists of 11 KV medium voltage (2+1
SF6 LBS) RMU, an immersed oil type 1500KVA transformer
11/0.38 KV (∆/Y), 50Hz, low tension panel with 2500A ACB,
circuit breakers as indicated in single line diagram including
Raychem insulated bus-bars, earth leakage switches,
hygrostat, heaters, fans and relays, measuring and protective
devices, ventilation fans with filters, metal enclosure,
concrete foundation, terminations of cables/wires with their
respective breakers, and all necessary accessories and
ancillary civil works and material required for complete
installation as specified, shown on drawings and EEA
electrical company regulation.
1-1-1 Ditto as above but for substation SUB-TR (2) with P.F.C unit. No 1
1-1-2 Ditto as above but for substation SUB-TR (3) with P.F.C unit. No 1
1-1-3 Ditto as above but for substation SUB-TR (4) with P.F.C unit. No 1
1-1-4 Ditto as above but for substation SUB-TR (5) with P.F.C unit. No 1
1-1-5 Ditto as above but for substation SUB-TR (6) with P.F.C unit. No 1
1-1-6 Ditto as above but for substation SUB-TR (8) with P.F.C unit. No 1
1-1-7 Ditto as above but for substation SUB-TR (10) with P.F.C unit. No 1
1-1-8 Ditto as above but for substation SUB-TR (11) with P.F.C unit. No 1
1-2 Supply, install, connect and test IP54 type tested power
package substation consists of 11 KV medium voltage (2+1
SF6 LBS) RMU, an immersed oil type 1000KVA transformer
11/0.38 KV (∆/Y), 50Hz, low tension panel with 1600A ACB,
circuit breakers as indicated in single line diagram including
Raychem insulated bus-bars, earth leakage switches,
hygrostat, heaters, fans and relays, measuring and protective
devices, ventilation fans with filters, metal enclosure,
concrete foundation, terminations of cables/wires with their
respective breakers, and all necessary accessories and
ancillary civil works and material required for complete
installation as specified, shown on drawings and EEA
electrical company regulation.
1-2-1 Ditto as above but for substation SUB-TR (1) with P.F.C unit. No 1
1-2-2 Ditto as above but for substation SUB-TR (12) with P.F.C unit. No 1
1-2-3 Ditto as above but for substation SUB-TR (13) with P.F.C unit. No 1
1-2-4 Ditto as above but for substation SUB-TR (14) with P.F.C unit. No 1
1-2-5 Ditto as above but for substation SUB-TR (15) with P.F.C unit. No 1
1-2-6 Ditto as above but for substation SUB-TR (16) with P.F.C unit. No 1
1-2-7 Ditto as above but for substation SUB-TR (17) with P.F.C unit. No 1
1-3 Supply, install, connect and test IP54 type tested power
package substation consists of 11 KV medium voltage (3+1
Page 1
BOQ Rev. no. 1 Issue date: Mar 2021
INFRAGROUP CONSULTANTS BILL OF QUANTITY

PORTO MANYA ELECTRICAL


& LOW CURRENT NETWORK
Item Description Unit Qty Unit Price Total

SF6 LBS) RMU, an immersed oil type 1500KVA transformer


11/0.38 KV (∆/Y), 50Hz, low tension panel with 2500A ACB,
circuit breakers as indicated in single line diagram including
Raychem insulated bus-bars, earth leakage switches,
hygrostat, heaters, fans and relays, measuring and protective
devices, ventilation fans with filters, metal enclosure,
concrete foundation, terminations of cables/wires with their
respective breakers, and all necessary accessories and
ancillary civil works and material required for complete
installation as specified, shown on drawings and EEA
electrical company regulation.
1-3-1 Ditto as above but for substation SUB-TR(7) No 1
1-4 Supply, install, connect and test IP54 type tested power
package substation consists of 11 KV medium voltage (3+1
SF6 LBS) RMU, an immersed oil type 1000KVA transformer
11/0.38 KV (∆/Y), 50Hz, low tension panel with 1600A ACB,
circuit breakers as indicated in single line diagram including
Raychem insulated bus-bars, earth leakage switches,
hygrostat, heaters, fans and relays, measuring and protective
devices, ventilation fans with filters, metal enclosure,
concrete foundation, terminations of cables/wires with their
respective breakers, and all necessary accessories and
ancillary civil works and material required for complete
installation as specified, shown on drawings and EEA
electrical company regulation.
1-4-1 Ditto as above but for substation SUB-TR(9) No 1
2 MEDIUM VOLTAGE FEEDERS CABLES:
Furnishing, supplying, installing, connecting and testing of
XLPE/STA/PVC armored Aluminum cables (12/20KV),
including terminations, Raychem insulation, warning tapes,
hooking up, U.P.V.C conduits, sleeves, trenches, manholes,
warning tapes, cable marker, spacer, elbows, connections,
supports, and all civil works such as excavation & backfilling,
concrete, blocks, drilling, building cuts, rung, filler/plaster,
asphalting and cleaning the site resulting from these works
and all necessary accessories and ancillary works required to
complete the work and materials as specified in standard
codes, specifications, and Egyptian Electrical Authority (EEA)
regulation standard required for complete installation
according to drawing.
2-1 Cable (3x240) mm2, AL, XLPE/STA/PVC. Mt 4300
3 FEEDERS AND SUB FEEDERS CABLES:
Furnishing, supplying, installing, connecting and testing of
XLPE/PVC copper or aluminum cables (0.6/1 KV), including

Page 2
BOQ Rev. no. 1 Issue date: Mar 2021
INFRAGROUP CONSULTANTS BILL OF QUANTITY

PORTO MANYA ELECTRICAL


& LOW CURRENT NETWORK
Item Description Unit Qty Unit Price Total

terminations, Raychem insulation, hooking up, U.P.V.C


conduits, sleeves, trenches, manholes, warning tapes, cable
marker, spacer, elbows, connections, supports, all necessary
civil works like excavation & backfilling, concrete, drilling,
rung, filler/plaster asphalting and cleaning the site resulting
from these works and all necessary accessories and ancillary
works required to complete the work as specified in standard
codes, specifications, and drawings.
3-1 FROM TR. TO PILARS:
3-1-1 (3x120+70) mm2, AL, XPLE/STA/PVC. Mt 870
3-1-2 (3x95+50) mm2, AL, XPLE/STA/PVC. Mt 550
3-2 FROM PILLAR. TO VILLA MDB:
3-2-1 (4x35) mm2, AL, XPLE/STA/PVC. Mt 1200
3-2-2 (4x25) mm2, AL, XPLE/STA/PVC, . Mt 1100
3-3 FROM MDB-TR. TO BUILDING MDB:
3-3-1 (4x35) mm2, AL, XPLE/STA/PVC. Mt 1200
3-3-2 (3x240+120) mm2, AL, XPLE/STA/PVC, +70mm2E CU, PVC. Mt 1360
3-3-3 (3x185+95) mm2, AL, XPLE/STA/PVC. Mt 700
3-3-4 (3x150+70) mm2, AL, XPLE/STA/PVC. Mt 1300
3-3-5 (3x70+35) mm2, AL, XPLE/STA/PVC. Mt 120
3-4 FOR STREET LIGHTING:
3-4-1 (4X35) mm2, AL, PVC/STA/PVC, +16mm2E CU, PVC. Mt. 470
3-4-2 (4x16) mm2, AL, XPLE/STA/PVC, +10mm2E CU, PVC. Mt 8700
4 FEEDING PILLARS:
Supplying, installing, connecting and testing free standing
feeding pillars, complete with concrete mounting foundation,
incoming/outgoing MCSF, terminations of cables/wires with
their respective breakers, terminal blocks, cable glands,
labels, tags, metering, measuring instruments, grounding and
all necessary accessories and ancillary works for preparing
low tension panel board room and all required for complete
installation.
4-1 Ditto as above, but for PILLAR (FP-13.1) No. 1
4-2 Ditto as above, but for PILLAR (FP-13.2) No. 1
4-3 Ditto as above, but for PILLAR (FP-14.1) No. 1
4-4 Ditto as above, but for PILLAR (FP-14.2) No. 1
4-5 Ditto as above, but for PILLAR (FP-15.1) No. 1
4-6 Ditto as above, but for PILLAR (FP-15.2) No. 1
4-7 Ditto as above, but for PILLAR (FP-16.1) No. 1
4-8 Ditto as above, but for PILLAR (FP-16.2) No. 1
5 STREET LIGHTING PANEL BOARD
Supplying, installing, connecting & testing and of street
lighting panel boards, weatherproof protection (IP54), the
work shall be including, but not limited to Concrete mounting
Page 3
BOQ Rev. no. 1 Issue date: Mar 2021
INFRAGROUP CONSULTANTS BILL OF QUANTITY

PORTO MANYA ELECTRICAL


& LOW CURRENT NETWORK
Item Description Unit Qty Unit Price Total

base, grounding, circuit breakers, enclosures, fixings,


supports and associated lighting contactors, photocell, timer
and (A-M-O) switch and all necessary accessories and
ancillary works for complete installation as specified and as
indicated in drawings.
5-1 Ditto as above, but for lighter panel ST-01 No. 1
5-2 Ditto as above, but for lighter panel ST-02 No. 1
5-3 Ditto as above, but for lighter panel ST-04 No. 1
5-4 Ditto as above, but for lighter panel ST-05 No. 1
5-5 Ditto as above, but for lighter panel ST-09 No. 1
5-6 Ditto as above, but for lighter panel ST-12 No. 1
5-7 Ditto as above, but for lighter panel ST-14 No. 1
5-8 Ditto as above, but for lighter panel ST-15 No. 1
5-9 Ditto as above, but for lighter panel ST-16 No. 1
5-10 Ditto as above, but for lighter panel ST-17 No. 1
6 UNDERGROUND DUCT BANKS:
Supply and install, Reinforced concrete duct bank for the
cable to cross the roads, the work shall be including but not
limited to Insulation UPVC conduits, tapes, cable marker,
spacer, elbows, connections, supports, all necessary
accessories and ancillary civil works like excavation &
backfilling, concrete, drilling, rung, filler/plaster asphalting
and cleaning the site resulting from these works and all
necessary accessories and ancillary works required to
complete the work as specified in standard codes,
specifications, and drawings.
6-1 Reinforced concrete duct bank, with 4 UPVC conduits,
160mm diameter for medium voltage cables. Mt 30
6-2 Reinforced concrete duct bank, with 3 UPVC conduits,
160mm diameter for medium voltage cables. Mt 10
6-3 Reinforced concrete duct bank, with 2 UPVC conduits,
160mm diameter for medium voltage cables. Mt 270
6-4 Reinforced concrete duct bank, with 7 UPVC conduits,
100mm diameter for low voltage cables. Mt 10
6-5 Reinforced concrete duct bank, with 2 UPVC conduits, 75mm
diameter for low voltage cables. Mt 35
6-6 Reinforced concrete duct bank, with 3 UPVC conduits, 50mm
diameter for street lighting cables. Mt 250
6-7 Reinforced concrete duct bank, with 5 UPVC conduits,
100mm diameter for L.C Fiber Optic network cables Mt 80
6-8 Reinforced concrete duct bank, with 2 UPVC conduits,
100mm diameter for L.C Fiber Optic network cables Mt 480
6-9 Reinforced concrete duct bank, with 2 UPVC conduits, 50mm
diameter for L.C Fiber Optic network cables Mt 80
Page 4
BOQ Rev. no. 1 Issue date: Mar 2021
INFRAGROUP CONSULTANTS BILL OF QUANTITY

PORTO MANYA ELECTRICAL


& LOW CURRENT NETWORK
Item Description Unit Qty Unit Price Total

7 STREET LIGHTING POLES:


7-1 Supply, install, test, commission decorative lighting pole 10 m
height with single arm contains one lamp 112W led with
tamper/ heat resistance glass lighting fixture (IP65)
complete with lamp holder, The pole is made from hot deep
drawn rolled galvanized steel complete with locked
inspection door, metal support base, UPVC conduits, circuit
breaker 10A, Bakelite isolation termination board,
thermoplastic cable (3x2 mm2) to feed the fixture, steel
grounding rod coated by copper, 6mm2 PVC grounding CU
cable, terminations of cables/wires with their termination
board, concrete foundation base and all necessary accessories
and ancillary civil works and material required for complete
installation as specified, shown on drawings and as referring
to land escape lighting consultant .

No. 286
7-2 Ditto as above but with double arm. No. 36
7-3 Ditto as above but for ground spike (move through 180)
lighting unit with 12W LED UPLIGHTER, IP-67. No. 128
8 FIBER DISTRIBUTION NETWORKS:
8-1 U.P.V.C PIPES
Supplying , installing, connecting and testing and put into
operation of UPVC pipes/conduits, SCH-40 needed for pulling
L.C Fiber Optic network cables including elbows, connections,
supports, all necessary accessories and ancillary civil works
like excavation & backfilling, concrete, sand required for
complete installation as specified and as indicated in the
drawings, specifications, and according to standards
requirement.
8-1-1 Ditto as above but UPVC pipes/conduits with 50mm
Diameter. Mt. 3200
8-1-2 Ditto as above but UPVC pipes/conduits with 100mm
Diameter. Mt. 5300
8-2 HANDHOLES & MANHOLES FOR LOW CURRENT
NETWORK:
Supplying, installing, connecting and testing and put into
operation pre-cast concrete hand hole & man hole for L.C
fiber optic cables, the item including UPVC pipes/conduit
sleeves, connections, supports, metal cover, drain pipe outlet
ground rod, all necessary accessories and ancillary civil
works like excavation & backfilling, concrete, drilling, rung,
filler/plaster and cleaning the site resulting from these works
and all necessary accessories and ancillary works required to

Page 5
BOQ Rev. no. 1 Issue date: Mar 2021
INFRAGROUP CONSULTANTS BILL OF QUANTITY

PORTO MANYA ELECTRICAL


& LOW CURRENT NETWORK
Item Description Unit Qty Unit Price Total

complete the work as specified in standard codes,


specifications and drawings.
8-2-1 Ditto but pre-cast concrete hand hole with dimension of
80cmx80cm. No. 7
8-2-2 Ditto but pre-cast concrete hand hole with dimension of
60cmx60cm. No. 57
9 EARTHING SYSTEM:
9-1 Furnishing, supplying, installing connecting and testing a
complete protective earthing system for medium voltage
package substation system including earthing pits, earthing
electrodes, distributing bus bar and test link, earth continuity
conductor, earthing conductor to 11 KV switchgear, ring
main units, 11KV load break switches, transformers…etc
complete with all accessories, fixings, brackets, test links,
suspensions, drilling and cutting to form a complete
installation as specified and as indicated on the drawings
(Resistance should not be exceed than 3 ohm). Ls 17
9-2 Ditto but a complete protective earthing system for low voltage
package substation system including earthing pits, earthing
electrodes, distributing bus bar and test link, earth continuity
conductor, earthing conductor to main switchboards, diesel
generator sets, fuel tanks,...etc complete with all accessories,
fixings, brackets, test links, suspensions, drilling and cutting to
form a complete installation as specified and as indicated on the
drawings (Resistance should not be exceed 2 ohm). Ls 17
9-3 Ditto but a complete protective earthing system for pillars
including earthing pits, earthing electrodes, distributing bus bar
and test link, earth continuity conductor, earthing conductor to
main switchboards complete with all accessories, fixings,
brackets, test links, suspensions, drilling and cutting to form a
complete installation as specified and as indicated on the
drawings (Resistance should not be exceed 2 ohm). Ls 11
TOTAL :