ifc200 p; 1926085 9thcc:n/a Fire Controls Initiating Devices
IFC-200
Rev:Rev: 08/25/98 logo: standard left ft: none right ft: standard Sect# = 0 seQ# = 20
Features
AWACS prealarm application rapid Poll Algorithm for manual stations walk test feature LCD-80 remote display/ control (up to four per IFC-200 various indicating appliance codes
To Order
Specify the code number from the following selection chart.
Repair Parts
Repair unit.
Selection Chart
Code Number Description
Specifications
IFC-200 Intelligent Fire Controller
AC Power 120 VAC at 50/60 Hz, 3A 14 AWG with 600V Insulation, Minimum 32 to 120F (0 to 49C) 85 % RH (non-condensing) at 86F (30C) Resistive: Inductive: 2A at 30 VDC 1A at 30 VDC (0.6 pf) 0.3A at 120 VDC (0.35 pf) Contacts are not rated for pilot duty or motor loads. 16.0 x 14.5 x 5.5 in. (406.4 x 368.3 x 139.7 mm) Maximum Charging Circuit: Dual Rate High Charge: 29.1V Normal Flat Charge -27.6V Limited Circuit Charge: 0.7A Typical Maximum Battery Capacity: 17 AH (Batteries larger than 12 AH require a UL Listed battery cabinet.) 20 to 55 AH with External NR45-24 Battery Charger UL, ULC Wire Size Ambient Operating Conditions Control Module Contact Ratings Dimensions (H x W x D)
BEIFC-200G
Analog Fire Alarm Panel. Basic Equipment Kit: Single Printed Circuit Board with One SLC Loop (198 Devices) Back-lit, 80-character Display System and Programming Keypad and 5.0A Power Supply Includes Gray Door, Note:Backbox ordered separately. Same as BEIFC-200G but Includes a Red Door Same as BEIFC-200G but 230 VAC Same as BEIFC-200R but 230 VAC Backbox (no door), Gray, IFC-200 Note: Must be ordered with a BEIFC for a complete assembly. Backbox (no door), Red, IFC-200 Note: Must be ordered with a BEIFCR for a complete assembly.
SBB-4X
Total current of regulated power, non-resettable power, four wire smoke power, and four indicating circuits must not exceed 5.0A. Total external system current in excess of 2.5A requires 12 AH or 17 AH batteries, not 7.0 AH. For power supply calculations, refer to the IFC-200 Technical Manual (FAN 444).
SBB-4XR
Electrical Characteristics
IFC-200 Intelligent Fire Controller
Indicating Appliance and Releasing Circuits Power-limited Circuitry Maximum Wiring Voltage Drop Normal Operating Voltage Current for All External Devices Current Limit Maximum Signaling Current/Circuit End-of-Line Resistor Contact Rating: Alarm and Trouble: Supervisory: 2 VDC 24 VDC 5.0A Positive Temperature Coefficient 2.25A 4.7K, 1/2 watt (P/N 71252) UL Listed for Indicating Appliance Circuits 2.0A at 30 VDC (resistive), 0.5A at 30 VAC (resistive) Form-C Form-A
Accessories
Code Number
4XTM RTM-8 4XMM TR-4X6 PK-200 911A BB-17
Description
Plug-in Transmitter Module Plug-in Relay/Transmitter Meter Module Semi-flush Trim Ring Programming Kit/Offline Edit Three Channel Digital Communicator Battery Backbox
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson 10/98 Johnson Controls, Inc Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
1/1