AMENDMENT NO.

2 NOVEMBER 2009 TO IS 15683 : 2006 PORTABLE FIRE EXTINGUISHERS PERFORMANCE AND CONSTRUCTION SPECIFICATION
(Page 6, clause 7.6.1, line 3) Delete as defined in IS 6910 and add the following after first sentence: Figure 7 is an example of typical test apparatus for external corrosion test. (Page 10, Table 5) Substitute the following for the existing table: Table 5 Amount of Extinguishing Medium Used to Obtain Minimum Class B Rating of Extinguishers (Clause 8.1.2)
Extinguishing Medium Content (Charge) Powder kg (1) l2 2<l3 3<l4 Carbon Dioxide kg (2) l2 2<l5 l>5 Clear Agent kg Foam or Water with Additives (4) 5 9 9 Minimum Class B Rating

(Page

le
l2

(3)

(5) 8B 13 B 21 B

2<l4

(Page 23, clause 10.1) Add the following at the end: A small band of distinguishing colour of 5 percent of surface area shall be painted for different type of extinguishers.

No

tf
Sl No. 1 2 3 4 5

or

17, clause 9.2.5) Shift clause 9.2.5 as 9.1.1 under clause 9.1 on page 16 and renumber the subsequent clauses from 9.2.6 onwards.

sa
1

4<l6

Extinguishers Water Powder Foam Carbon Dioxide Clean Agent

Band Colour Red Blue Yellow Black Green

Amend No. 2 to IS 15683 : 2006 (Page 23, clause 10.2.1.1) Add the following sentence at the end: The marks specified above shall be applied to the metal of the body by hard stamping or engraving. (Page 27, clause 11.1) Insert the following figure at the end:

FIG. 7 TEST APPARATUS OF EXTERNAL CORROSION TEST

(CED 22)
Reprography Unit, BIS, New Delhi, India

No

tf

or

sa

le

No tf or sa le

AMENDMENT NO. 3 FEBRUARY 2010 TO IS 15683 : 2006 PORTABLE FIRE EXTINGUISHERS PERFORMANCE AND CONSTRUCTION SPECIFICATION
(Page 23, clause 10.1) Delete the following last sentence: The paint shall conform to IS 2932.

(CED 22)
Reprography Unit, BIS, New Delhi, India