LOW VOLTAGE CURRENT TRANSFORMERS type: IMW, IMP IMS, ISW, INSOA, IMR ,

Catalogue 1YMA699050-en

APPLICATION

The current transformers types IMW, IMP IMS, ISW, INSOA are , intended for supplying measuring instruments and protective circuits of electrical power devices with maximum operating voltage 0,72 kV and frequency 50 Hz. These current transformers are manufactured for secondary currents 1 A or 5 A. The current transformers types IMR 0, IMR 1, IMR 2 are intended for supplying measuring instruments and protective circuits of electrical power devices with maximum operating voltage 0,72 kV and frequency 50 Hz, particularly for fuse disconnectors of series SLM and SRE Slim Line , size 00, 1, 2 and 3.

The windings of the current transformers types INSOA, IMW, IMPa, IMPb, IMSa, IMSb are closed in the housings made of slow-burning material. The current transformers types IMSc, IMSd and ISW as well as the transformers of series IMR have the housings made of self extinguishing polycarbonate. The current transformers are made for different types of primary circuits, for busbars with cross-sectional dimensions from 205 mm up to set of two busbars 120 10 mm.The range of primary currents from 1 A up to 5000 A. The secondary terminals of the current transformers types IMW, IMP , IMS, ISW and IMR 2 can be sealed.

OPERATING CONDITIONS

The current transformers are designed for operation in indoor equipment, in temperate (N3), tropical (T3) and marine (MU) climate conditions. Rated longduration thermal current and limits of deviations of these transformers correspond to extended current range for 120%Ipn within the bounds of the ambient temperatures from 268 K (-5C) to 333 K (+60C). Additionally the current transformers types INSOA, IMW, IMPa, IMPb, IMSa, IMSb, IMSc can operate within the bounds of the ambient temperatures from 248 K (-25C) to 333 K (+60C).

COMPLIANCE WITH STANDARDS

PNIEC 185 +A1:1994 IEC185: 1987 +A1: 1990 GOST 7746 89 DIN/VDE 0414Teil: 1/01.94 The current transformers types INSOA, IMW, IMPa, IMPb, IMSa, IMSb, IMSc are approved by Polish Register of Ships and by Germanischer Lloyd for use on ships.

DESIGN

WARRANTY

The low voltage current transformers are single-phase, low power transformers, operating in quasi short-circuit conditions and transforming the current flowing through the primary circuit to the current in the secondary circuit with the observance of the requirements relating to the accuracy of the transformation specified in standards.

The factory warranty is twenty four months since the day of putting the apparatus into operation, but not longer than thirty six months since the date of purchase.

THE EXAMPLE OF ORDER

TRANSFORMERS type IMW


TECHNICAL DATA
Primary current Ipn A Secondary current Isn A Rated power Sn VA

The low voltage current transformer type IMSc Ipn = 600 A; Isn = 5 A; Sn = 10 VA; class 0,5; FS 5; for temperate climate conditions.

Type

Rated current Security short-time dynamic Class of factor for (peak) apparat. thermal accuracy Ith Idyn FS kA kA

Maximum permissible voltage of transformer Um kV

Rated test voltage Up kV

Weight Spacing of (about) cerminals

Current terminals

kg

mm

1; 2; 3; 5; 10; 15; 20; 25 30; 50 75 100 150

5 5; 7,5; 10; 15 20 5 5; 7,5; 10; 15 20 5; 7,5; 10 1 or 5 10 5; 7,5; 10; 15 15 5 5; 7,5; 10; 15 20 5; 7,5

0,2 0,5 or 1 1 0,2 0,5 or 1 1 0,5

10 5 10 5 10 5 60 x lpn 150 x lpn 0,72 3 0,8

102 or 108

M6 or M8

IMW

200

1 0,2 0,5 or 1 1 0,2

10 5

108

M8

250

10 5

300

5; 7,5; 10; 0,5 or 1 15; 20

Note: The versions of current transformer type IMW with secondary winding parameters: 5 VA, class 0,2; 10 VA, class 0,5; 15 VA, class 1 areprefered. 2 ABB

DIMENSIONAL DRAWING IMW transformers with bus bar 20 x 5 mm

102 or 108

TRANSFORMERS type IMP


TECHNICAL DATA
Rated power Type Rated ratio class 0,2 A/A VA Sn class 0,5 VA class 1 VA Security factor for apparat. FS Rated current short-time thermal Ith kA dynamic (peak) Idyn kA Maximum permissible voltage of transformer Um kV Rated test voltage Up kV Maximal dimens. of cross-section of a bus kV Weight (about) kg

IMPa

IMPb

100/5 100/1 150/5 150/1 200/5 200/1 250/5 250/1 300/5 300/1 150/5 150/1 200/5 200/1 250/5 250/1 300/5 300/1 400/5 400/1

2,5 5 5 7,5 10 5 5 * 7,5 5; 7,5; 10; 15 5; 7,5; 10; 15; 20 2,5 5 5 7,5 10 5 * 5; 7,5; 10; 15 5; 7,5; 10; 15; 20

5 5 7,5 10 5; 7,5; 10; 15 5; 7,5; 10; 15; 20 5; 7,5; 10; 15; 20 5 5 7,5 10 5; 7,5; 10; 15 5; 7,5; 10; 15; 20 5; 7,5; 10; 15; 20 10 60 x lpn 150 x lpn 0,72 3 10 x 30 0,5

10 60 x lpn 150 x lpn 0,72 3 10 x 20 0,8

5 * 7,5

* - for class 0,2 FS 10.. ABB 3

114 or 127

DIMENSIONAL DRAWING IMPa current transformers for cable max 20 mm or bar 20 x 10 mm IMPb current transformers for cable max 30 mm or bar 30 x 10 mm

Supporting version

Seal wired version

For version IMPa - the length A = 20,2 mm For version IMPb - the length A = 30,2 mm

TRANSFORMERS type IMS


TECHNICAL DATA
Primary current Type Ipn A Secondary current Isn A Rated power Sn class 0,2 class 0,5 class 1 VA VA VA Security factor for apparat. FS Rated current short-time thermal Ith kA dynamic (peak) Idyn kA Maximum permissible voltage of transformer Um kV Rated test voltage Up kV kg Weight (about)

150 200 250 300 1 or IMSa 400 5 5 5 5 5 7,5 10 5 7,5 10 15 5 7,5 10 15

500

600

5 5 7,5 5 7,5 5 7,5 10 5 7,5 10 15 5 7,5 10 15 20 5 7,5 10 15 20

60 x lpn

150 x lpn

0,72

0,45

ABB

TECHNICAL DATA
Primary current Type Ipn A Secondary current Isn A kl. 0,2 VA Rated power Sn kl. 0,5 VA kl. 1 VA Security factor for apparat. FS Rated current short-time Ith kA dynamic (peak) Idyn kA Maximum permissible voltage of transformer Um kV Rated test voltage Up kV kg Weight (about)

600

5 5

750 IMSb 800

1 lub 5 5 7,5 5 7,5

5 7,5 10 5 7,5 10 5 7,5 10 15 5 7,5 10 15

1000

10

5 7,5 10 15 5 7,5 10 15 5 7,5 10 15 5 7,5 10 15 20

5 10 5 10 5 10 5

60 x lpn

150 x lpn

0,72

0,7

DIMENSIONAL DRAWING IMSa current transformers for bus bar max 40 x 10 mm

DIMENSIONAL DRAWING IMSb current transformers for bus bar max 60 x 10 mm

ABB

TECHNICAL DATA
Primary current Type Ipn A Secondary current Isn A Rated power Sn class 0,2 class 0,5 class 1 VA VA VA Security factor for apparat. FS Rated current short-time thermal Ith kA dynamic (peak) Idyn kA Maximum permissible voltage of transformer Um kV Rated test voltage Up kV kg Weight (about)

400 500 600 5 5 7,5 10 5 7,5 10 15 5 7,5 10 15 5 7,5 10 15 20 5 7,5 10 15 20 7,5 10 15 20 7,5 10 15 20 7,5 10 15 20

750

5 5 7,5 1 5 7,5 10 5 7,5 10 7,5 10 7,5 10 7,5 10

800

IMSc

1000

or 5

1200

1500

1600

2000

7,5 10 7,5 10 5 7,5 10 15 5 7,5 10 15 5 7,5 10 15 5 7,5 10 15 20 5 7,5 10 15 20 7,5 10 15 20 7,5 10 15 20 7,5 10 15 20

60 x lpn

150 x lpn

0,72

0,9

10 5 10 5 10 5

DIMENSIONAL DRAWING IMSc current transformers for bus bar max 80 x 10 mm

ABB

TECHNICAL DATA
Primary curent Type Secondary current Rated current thermal, 1-sec. dynamic (peak) Weight (about)

Ipn [A]
1500

Isn [A]

Parameters of secondary windings

Ith [kA]
5 VA class 0,2 FS 10 15 VA class 0,5 FS 5 30 VA class 1 FS 5 5 VA class 0,2 FS 10 15 VA class 0,5 FS 5 30 VA class 1 FS 5 15 VA class 0,2 FS 5 30 VA class 0,5 FS 5 45 VA class 1 FS 5 15 VA class 0,2 FS 5 30 VA class 0,5 FS 5 45 VA class 1 FS 5 30 VA class 0,2 FS 5 60 VA class 0,5 FS 5 60 VA class 1 FS 5 45 VA class 0,2 FS 5 60 VA class 0,5 FS 5 90 VA class 1 FS 5 60 VA class 0,2 FS 5 90 VA class 0,5 FS 5 120 VA class 1 FS 5
Maximum permissible voltage of transformer Test voltage

Idyn [kA]
100

[kg]

37,5

1,3 40 105

1600 1 or IMSd 2500 5

2000

50

125 1,5

62,5

156,5

3000

75

187 1,6

4000

100

250

5000

100

250

1,8

Extended current range

Um [kV] 0,72

Up [kV] 3

ext. % x Ipn 120% x Ipn

DIMENSIONAL DRAWING IMSd current transformers for bus bar max 120 x 30 mm or 100 x 50 mm

ABB

TRANSFORMERS type ISW


TECHNICAL DATA
Primary current Type Ipn A Secondary current Isn A Rated power Sn class 0,5 VA class 1 VA Security factor for apparat. FS Rated current short-time thermal Ith kA dynamic (peak) Idyn kA Maximum permissible voltage of transformer Um kV Rated test voltage Up kV kg Weight (about)

200 250 300 400 500 ISWa 600 750 1 or 5

2,5 2,5 5; 7,5 5; 7,5 10 5; 7,5 10; 15 5; 7,5 10; 15 5; 7,5 10; 15 2,5 2,5 2,5; 5 2,5; 5 7,5; 10 2,5; 5 7,5; 10 2,5; 5 7,5; 10 15 2,5; 5 7,5; 10 15 2,5; 5 7,5; 10 15; 20 5; 7,5; 10; 15; 20; 30 5; 7,5; 10; 15; 20; 30 5; 7,5; 10; 15; 20; 30

2,5 2,5; 5 2,5; 5 5; 7,5 10 5; 7,5 10; 15 5; 7,5 10; 15 5; 7,5 10; 15 20 5; 7,5 10; 15 20 2,5 2,5 2,5; 5 7,5 2,5; 5 7,5; 10 2,5; 5 7,5; 10 15 2,5; 5 7,5; 10 15 2,5; 5 7,5; 10 15; 20 2,5; 5 7,5; 10 15; 20 5; 7,5; 10; 15; 20; 30 5; 7,5; 10; 15; 20; 30 5; 7,5; 10; 15; 20; 30
ABB

60 x lpn

150 x lpn

0,72

0,8

800 250 300 400 500 600

750 1 ISWb 800 or 5 1000

60 x lpn

150 x lpn

0,72

0,8

1200

1500

1600

DIMENSIONAL DRAWING ISWa current transformers for cable max 48 mm or bus bar max 50 x 30 mm

DIMENSIONAL DRAWING ISWb current transformers for cable max 48 mm or bus bar max 60 x 30 mm

TRANSFORMERS type INSOA


TECHNICAL DATA
Rated ratio A/A Rated power Sn class 3 VA Security factor for apparat. FS Rated current short-time thermal Ith kA dynamic (peak) Idyn kA Maximum permissible voltage of transformer Um kV Rated test voltage Up kV Maximal dimensions of cross-section of a bus mm Weight (about) kg

Type

INSOA

100/5 100/1 150/5 150/1 200/5 200/1 300/5 300/1 400/5 400/1

4 5; 7,5 5; 7,5; 10 5; 7,5; 10 5; 7,5; 10 2

60 x lpn

150 x lpn

0,72

10 x 30

0,4

DIMENSIONAL DRAWING INSOA current transformers for cable max 30 mm or bus bar max 30 x 10 mm

Supporting version

Seal wired version

ABB

TRANSFORMERS type IMR0


TECHNICAL DATA
Rated primary current Ipn [A] Parameters of secondary winding for version A =30 mm power; class; FS Parameters of secondary winding for version A =50 mm power; class; FS Rated Rated test Rated current secondary voltage current short-time dynamic Isn thermal (peak) [A] [kV] [kA] [kA] Maximal cross -section of busbar [mm] Weight (about) [kg]

Type

50 75 IMR0 100 150 200 2,5 VA class 3 FS 5 2,5 VA class 1 FS 5 2,5 VA class 1 FS 5 1 VA class 0,5 FS 5 4 VA class 3 FS 5 2,5 VA class 0,5 FS 5

1 VA class 3 FS 5 2,5 VA class 3 FS 5 1 VA class 3 FS 5 2,5 VA class 3 FS 5 1 VA class 0,5 FS 5 4 VA class 3 FS 5 5 VA class 1 FS 5 2,5 VA class 0,5 FS 5 4 VA class 0,5 FS 5

1 5 3 1 or 5

60 x lpn 150 x lpn

20 x 5

0,4

DIMENSIONAL DRAWING IMR0 current transformers for cable max 18 mm or bus bar max 20 x 5 mm

Version with secondary terminals

Version with leaded cables LYc, length approximately 20 cm

TRANSFORMERS type IMR1


TECHNICAL DATA
Rated primary current Type Ipn [A] power; class; FS Parameters of secondary winding Rated secondary current Isn [A] Rated test voltage Up [kV]

The current transformer type IMR 1 for A = 20,5 mm


Rated current short-time thermal [kA] dynamic (peak) [kA] Maximal cross -section of busbar [mm] Mass (about) [kg]

75 100 150 IMR1a 200 250 300 400


10

1 VA class 1 FS 5 2,5 VA class 3 FS 5 1 VA class 1 FS 5 2,5 VA class 1 FS 5 2,5 VA class 0,5 FS 5 5 VA class 1 FS 5 5 VA class 0,5 FS 5 7,5 VA class 1 FS 5 5 VA class 0,5 FS 5 7,5 VA class 1 FS 5 7,5 VA class 0,5 FS 5 10 VA class 1 FS 5 10 VA class 0,5 FS 5 15 VA class 1 FS 5

1 or 5

60 x lpn

150 x lpn

20 x 10

0,6

ABB

The current transformer type IMR 1 for A = 25,5 mm


Rated primary current Type Ipn [A] power; class; FS Parameters of secondary winding Rated secondary current Isn [A] Rated test voltage Up [kV] Rated current short-time thermal [kA] dynamic (peak) [kA] Maximal cross -section of busbar [mm] Weight (about) [kg]

100 150 200 IMR1b 250 300 400 500

1 VA class 1 FS 5 2,5 VA class 3 FS 5 1 VA class 0,5 FS 5 2,5 VA class 1 FS 5 2,5 VA class 0,5 FS 5 5 VA class 1 FS 5 2,5 VA class 0,5 FS 5 5 VA class 1 FS 5 5 VA class 0,5 FS 5 7,5 VA class 1 FS 5 7,5 VA class 0,5 FS 5 10 VA class 1 FS 5 10 VA class 0,5 FS 5 15 VA class 1 FS 5

1 or 5

60 x lpn

150 x lpn

25 x 10

0,6

DIMENSIONAL DRAWING IMR1a current transformers for cable max 18 mm or bus bar max 20 x 10 mm

DIMENSIONAL DRAWING IMR1b current transformers for cable max 23 mm or bus bar max 25 x 10 mm

Version with secondary terminals

Version with leaded cables LYc, length approximately 20 cm

For version IMR 1a - the length A = 20,5 cm. For version IMR 1b - the length A = 25,5 cm.

TRANSFORMERS type IMR2


TECHNICAL DATA
Rated primary current Type Ipn [A] power; class; FS Parameters of secondary winding Rated secondary current Isn [A] Rated test voltage Up [kV] Rated current short-time thermal [kA] dynamic (peak) [kA] Maximal cross -section of busbar [mm] Weight (about) [kg]

200 250 300 IMR2 400 500 600 630 650


ABB

5 VA class 1 FS 5 5 VA class 0,5 FS 5 10 VA class 1 FS 5 10 VA class 0,5 FS 5 10 VA class 1 FS 5 15 VA class 0,5 FS 5 15 VA class 1 FS 5 15 VA class 0,5 FS 5 20 VA class 1 FS 5 15 VA class 0,5 FS 5 20 VA class 1 FS 5 15 VA class 0,5 FS 5 20 VA class 1 FS 5 15 VA class 0,5 FS 5 20 VA class 1 FS 5

1 or 5

60 x lpn

150 x lpn

40 x 10

0,6

11

DIMENSIONAL DRAWING IMR2 current transformers for cable max 30 mm or bus bar max 40 x 10 mm Version with secondary terminals Version with leaded cables LYc, length approximately 20 cm

max. diameter of conductor 30

Manufacturer reserves for itself the right to train the changes resulting from the technological progress.

ABB Sp. z o.o. Power Technologies Division ul. Leszno 59 06-300 Przasnysz, Poland Phone: ( +48 22) 52 52 838, 51 52 831 ( +48 29) 75 33 233, 75 33 240 Fax: +48 22 51 52 659, +48 29 75 33 327 www.abb.com

1YMA699050-en Publication 04.2003