CT Class and Va
CT Class and Va
Catalogue 1YMA699050-en
APPLICATION
The current transformers types IMW, IMP IMS, ISW, INSOA are , intended for supplying measuring instruments and protective circuits of electrical power devices with maximum operating voltage 0,72 kV and frequency 50 Hz. These current transformers are manufactured for secondary currents 1 A or 5 A. The current transformers types IMR 0, IMR 1, IMR 2 are intended for supplying measuring instruments and protective circuits of electrical power devices with maximum operating voltage 0,72 kV and frequency 50 Hz, particularly for fuse disconnectors of series SLM and SRE Slim Line , size 00, 1, 2 and 3.
The windings of the current transformers types INSOA, IMW, IMPa, IMPb, IMSa, IMSb are closed in the housings made of slow-burning material. The current transformers types IMSc, IMSd and ISW as well as the transformers of series IMR have the housings made of self extinguishing polycarbonate. The current transformers are made for different types of primary circuits, for busbars with cross-sectional dimensions from 205 mm up to set of two busbars 120 10 mm.The range of primary currents from 1 A up to 5000 A. The secondary terminals of the current transformers types IMW, IMP , IMS, ISW and IMR 2 can be sealed.
OPERATING CONDITIONS
The current transformers are designed for operation in indoor equipment, in temperate (N3), tropical (T3) and marine (MU) climate conditions. Rated longduration thermal current and limits of deviations of these transformers correspond to extended current range for 120%Ipn within the bounds of the ambient temperatures from 268 K (-5C) to 333 K (+60C). Additionally the current transformers types INSOA, IMW, IMPa, IMPb, IMSa, IMSb, IMSc can operate within the bounds of the ambient temperatures from 248 K (-25C) to 333 K (+60C).
PNIEC 185 +A1:1994 IEC185: 1987 +A1: 1990 GOST 7746 89 DIN/VDE 0414Teil: 1/01.94 The current transformers types INSOA, IMW, IMPa, IMPb, IMSa, IMSb, IMSc are approved by Polish Register of Ships and by Germanischer Lloyd for use on ships.
DESIGN
WARRANTY
The low voltage current transformers are single-phase, low power transformers, operating in quasi short-circuit conditions and transforming the current flowing through the primary circuit to the current in the secondary circuit with the observance of the requirements relating to the accuracy of the transformation specified in standards.
The factory warranty is twenty four months since the day of putting the apparatus into operation, but not longer than thirty six months since the date of purchase.
The low voltage current transformer type IMSc Ipn = 600 A; Isn = 5 A; Sn = 10 VA; class 0,5; FS 5; for temperate climate conditions.
Type
Rated current Security short-time dynamic Class of factor for (peak) apparat. thermal accuracy Ith Idyn FS kA kA
Current terminals
kg
mm
5 5; 7,5; 10; 15 20 5 5; 7,5; 10; 15 20 5; 7,5; 10 1 or 5 10 5; 7,5; 10; 15 15 5 5; 7,5; 10; 15 20 5; 7,5
102 or 108
M6 or M8
IMW
200
10 5
108
M8
250
10 5
300
Note: The versions of current transformer type IMW with secondary winding parameters: 5 VA, class 0,2; 10 VA, class 0,5; 15 VA, class 1 areprefered. 2 ABB
102 or 108
IMPa
IMPb
100/5 100/1 150/5 150/1 200/5 200/1 250/5 250/1 300/5 300/1 150/5 150/1 200/5 200/1 250/5 250/1 300/5 300/1 400/5 400/1
2,5 5 5 7,5 10 5 5 * 7,5 5; 7,5; 10; 15 5; 7,5; 10; 15; 20 2,5 5 5 7,5 10 5 * 5; 7,5; 10; 15 5; 7,5; 10; 15; 20
5 5 7,5 10 5; 7,5; 10; 15 5; 7,5; 10; 15; 20 5; 7,5; 10; 15; 20 5 5 7,5 10 5; 7,5; 10; 15 5; 7,5; 10; 15; 20 5; 7,5; 10; 15; 20 10 60 x lpn 150 x lpn 0,72 3 10 x 30 0,5
5 * 7,5
114 or 127
DIMENSIONAL DRAWING IMPa current transformers for cable max 20 mm or bar 20 x 10 mm IMPb current transformers for cable max 30 mm or bar 30 x 10 mm
Supporting version
For version IMPa - the length A = 20,2 mm For version IMPb - the length A = 30,2 mm
500
600
60 x lpn
150 x lpn
0,72
0,45
ABB
TECHNICAL DATA
Primary current Type Ipn A Secondary current Isn A kl. 0,2 VA Rated power Sn kl. 0,5 VA kl. 1 VA Security factor for apparat. FS Rated current short-time Ith kA dynamic (peak) Idyn kA Maximum permissible voltage of transformer Um kV Rated test voltage Up kV kg Weight (about)
600
5 5
1000
10
5 10 5 10 5 10 5
60 x lpn
150 x lpn
0,72
0,7
ABB
TECHNICAL DATA
Primary current Type Ipn A Secondary current Isn A Rated power Sn class 0,2 class 0,5 class 1 VA VA VA Security factor for apparat. FS Rated current short-time thermal Ith kA dynamic (peak) Idyn kA Maximum permissible voltage of transformer Um kV Rated test voltage Up kV kg Weight (about)
400 500 600 5 5 7,5 10 5 7,5 10 15 5 7,5 10 15 5 7,5 10 15 20 5 7,5 10 15 20 7,5 10 15 20 7,5 10 15 20 7,5 10 15 20
750
800
IMSc
1000
or 5
1200
1500
1600
2000
7,5 10 7,5 10 5 7,5 10 15 5 7,5 10 15 5 7,5 10 15 5 7,5 10 15 20 5 7,5 10 15 20 7,5 10 15 20 7,5 10 15 20 7,5 10 15 20
60 x lpn
150 x lpn
0,72
0,9
10 5 10 5 10 5
ABB
TECHNICAL DATA
Primary curent Type Secondary current Rated current thermal, 1-sec. dynamic (peak) Weight (about)
Ipn [A]
1500
Isn [A]
Ith [kA]
5 VA class 0,2 FS 10 15 VA class 0,5 FS 5 30 VA class 1 FS 5 5 VA class 0,2 FS 10 15 VA class 0,5 FS 5 30 VA class 1 FS 5 15 VA class 0,2 FS 5 30 VA class 0,5 FS 5 45 VA class 1 FS 5 15 VA class 0,2 FS 5 30 VA class 0,5 FS 5 45 VA class 1 FS 5 30 VA class 0,2 FS 5 60 VA class 0,5 FS 5 60 VA class 1 FS 5 45 VA class 0,2 FS 5 60 VA class 0,5 FS 5 90 VA class 1 FS 5 60 VA class 0,2 FS 5 90 VA class 0,5 FS 5 120 VA class 1 FS 5
Maximum permissible voltage of transformer Test voltage
Idyn [kA]
100
[kg]
37,5
1,3 40 105
2000
50
125 1,5
62,5
156,5
3000
75
187 1,6
4000
100
250
5000
100
250
1,8
Um [kV] 0,72
Up [kV] 3
DIMENSIONAL DRAWING IMSd current transformers for bus bar max 120 x 30 mm or 100 x 50 mm
ABB
2,5 2,5 5; 7,5 5; 7,5 10 5; 7,5 10; 15 5; 7,5 10; 15 5; 7,5 10; 15 2,5 2,5 2,5; 5 2,5; 5 7,5; 10 2,5; 5 7,5; 10 2,5; 5 7,5; 10 15 2,5; 5 7,5; 10 15 2,5; 5 7,5; 10 15; 20 5; 7,5; 10; 15; 20; 30 5; 7,5; 10; 15; 20; 30 5; 7,5; 10; 15; 20; 30
2,5 2,5; 5 2,5; 5 5; 7,5 10 5; 7,5 10; 15 5; 7,5 10; 15 5; 7,5 10; 15 20 5; 7,5 10; 15 20 2,5 2,5 2,5; 5 7,5 2,5; 5 7,5; 10 2,5; 5 7,5; 10 15 2,5; 5 7,5; 10 15 2,5; 5 7,5; 10 15; 20 2,5; 5 7,5; 10 15; 20 5; 7,5; 10; 15; 20; 30 5; 7,5; 10; 15; 20; 30 5; 7,5; 10; 15; 20; 30
ABB
60 x lpn
150 x lpn
0,72
0,8
60 x lpn
150 x lpn
0,72
0,8
1200
1500
1600
DIMENSIONAL DRAWING ISWa current transformers for cable max 48 mm or bus bar max 50 x 30 mm
DIMENSIONAL DRAWING ISWb current transformers for cable max 48 mm or bus bar max 60 x 30 mm
Type
INSOA
100/5 100/1 150/5 150/1 200/5 200/1 300/5 300/1 400/5 400/1
60 x lpn
150 x lpn
0,72
10 x 30
0,4
DIMENSIONAL DRAWING INSOA current transformers for cable max 30 mm or bus bar max 30 x 10 mm
Supporting version
ABB
Type
50 75 IMR0 100 150 200 2,5 VA class 3 FS 5 2,5 VA class 1 FS 5 2,5 VA class 1 FS 5 1 VA class 0,5 FS 5 4 VA class 3 FS 5 2,5 VA class 0,5 FS 5
1 VA class 3 FS 5 2,5 VA class 3 FS 5 1 VA class 3 FS 5 2,5 VA class 3 FS 5 1 VA class 0,5 FS 5 4 VA class 3 FS 5 5 VA class 1 FS 5 2,5 VA class 0,5 FS 5 4 VA class 0,5 FS 5
1 5 3 1 or 5
20 x 5
0,4
DIMENSIONAL DRAWING IMR0 current transformers for cable max 18 mm or bus bar max 20 x 5 mm
1 VA class 1 FS 5 2,5 VA class 3 FS 5 1 VA class 1 FS 5 2,5 VA class 1 FS 5 2,5 VA class 0,5 FS 5 5 VA class 1 FS 5 5 VA class 0,5 FS 5 7,5 VA class 1 FS 5 5 VA class 0,5 FS 5 7,5 VA class 1 FS 5 7,5 VA class 0,5 FS 5 10 VA class 1 FS 5 10 VA class 0,5 FS 5 15 VA class 1 FS 5
1 or 5
60 x lpn
150 x lpn
20 x 10
0,6
ABB
1 VA class 1 FS 5 2,5 VA class 3 FS 5 1 VA class 0,5 FS 5 2,5 VA class 1 FS 5 2,5 VA class 0,5 FS 5 5 VA class 1 FS 5 2,5 VA class 0,5 FS 5 5 VA class 1 FS 5 5 VA class 0,5 FS 5 7,5 VA class 1 FS 5 7,5 VA class 0,5 FS 5 10 VA class 1 FS 5 10 VA class 0,5 FS 5 15 VA class 1 FS 5
1 or 5
60 x lpn
150 x lpn
25 x 10
0,6
DIMENSIONAL DRAWING IMR1a current transformers for cable max 18 mm or bus bar max 20 x 10 mm
DIMENSIONAL DRAWING IMR1b current transformers for cable max 23 mm or bus bar max 25 x 10 mm
For version IMR 1a - the length A = 20,5 cm. For version IMR 1b - the length A = 25,5 cm.
5 VA class 1 FS 5 5 VA class 0,5 FS 5 10 VA class 1 FS 5 10 VA class 0,5 FS 5 10 VA class 1 FS 5 15 VA class 0,5 FS 5 15 VA class 1 FS 5 15 VA class 0,5 FS 5 20 VA class 1 FS 5 15 VA class 0,5 FS 5 20 VA class 1 FS 5 15 VA class 0,5 FS 5 20 VA class 1 FS 5 15 VA class 0,5 FS 5 20 VA class 1 FS 5
1 or 5
60 x lpn
150 x lpn
40 x 10
0,6
11
DIMENSIONAL DRAWING IMR2 current transformers for cable max 30 mm or bus bar max 40 x 10 mm Version with secondary terminals Version with leaded cables LYc, length approximately 20 cm
Manufacturer reserves for itself the right to train the changes resulting from the technological progress.