Guide For Testing and Verification of Low Voltage Installations Short ANG Ver 1.0!20!750 XXX 01
Guide For Testing and Verification of Low Voltage Installations Short ANG Ver 1.0!20!750 XXX 01
Fuse: Z loop L-PE / Z line L-L, L-N IEC 60364-6 61.3.6.3., 61.3.11., equipment: IEC 61557- 3 Parameters / Limits are characteristics of particular built-in Fuse, designed for trip-out time of: 0.1s (Explosive), 0.2s (3Phase Circuits), 0.4s (1Phase systems) or 5s (fixed connections). Measured values of Impedances from the end of the circuit must be lower than Zs from the table. In (A) 2 4 6 10 16 20 Tip B Tip C Ia=5x Zs=() Ia=10x Zs=() In (A) (0,2 s) In (A) (0,2 s) 10 22 20 11 20 11 40 5,5 30 7,3 60 3,65 50 4,4 100 2,2 80 2,8 160 1,4 100 2,2 200 1,1 Tip G In Zs=() (A) (0,4 s) 16 13,7 32 6,8 47 4,6 82 2,6 110 2,0 147 1,4
RCD: Trip out time, Trip out Current IEC 60364-6 61.3.6.1., 61.3.7., equipment: IEC 61557- 6 RCD trip out at difrent Id (ms) RCD Slope range (from-to) RCD AC 1/2 x IN 1 x IN 2 x IN 5 x IN 0.2 1.0 x IN A General No trip t < 300 t < 150 t < 40 0.35 1.4 x IN B Selective No trip 130 x t < 500 60 x t < 200 50 x t < 150 0.5 2.0 x IN
More Parameters/Limits could be found in Metrel Handbooks and inside Eurotest/Smartec testers.
L1 L2 L3 N TT PE TT
L1 L2 L3 N PE
Limits: Where no RCD, select limit from the FUSE characteristics, test by Z loop. Where RCD: Nominal Differntial current IN (mA) 10 30 100 300 500 1000 R earth () max. (Uc<50 V) 5000 1666 500 166 100 50
IEC 60364-6 61.3.6.2., B.3., equipment: IEC 61557- 5 Limits: 2 above ground 10 whole system 20 underground per leg or 8% of Specific Earth Resistance Lightning system & Earth loops - Two clamps - test each loop