Professional Documents
Culture Documents
Catálogo Masterpact NT-NW 2009
Catálogo Masterpact NT-NW 2009
Masterpact NT and NW
LV power circuit breakers and switch-disconnectors
Catalogue 2009
Presentation
Masterpact NT and NW
All standards
Masterpact is compliant with international standards IEC 60947- and , IEC 6830 for type tropicalisation, UL489, ANSI, UL066, CCC and GOST.
5 performance levels > N - for standard applications with low short-circuit levels. > H - for industrial sites with high short-circuit levels or installations with two parallel-connected transformers. > H - high-performance for heavy industry where very high short-circuits can occur. > H3 - for incoming devices supplying critical applications requiring both high performance and a high level of discrimination. > L - for high current-limiting capability and a discrimination level (37 kA) as yet unequalled by any other circuit breaker of its
type; intended for the protection of cable-type feeders or to raise the performance level of a switchboard when the transformer power rating is increased.
Masterpact NT
630 to 1600 A
L1 150 kA H2 50 kA H1 42 kA NT06 NT08 NT10 NT12 NT16
Masterpact NW
800 to 4000 A
L1 150 kA H3 150 kA H2 100 kA H1 65 kA N1 42 kA NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40
4000 to 6300 A
H2 150 kA H1 100 kA NW40b NW50 NW63
Maximum security
The arc chutes absorb the energy released during breaking, thus limiting the stresses exerted on the installation. They filter and cool the gases produced, reducing effects perceptible from the outside. More than
Optimised volumes
Up to 4000 A, Masterpact NW circuit breakers are all the same size, the same as the old M08 to 3 range. From 4000 A to 6300 A, there is just one size.
60
Retrofit solutions > Special connections terminals are available to replace a fixed or a drawout Masterpact M08 to 32 with a Masterpact NW,
without modifying the busbars or the door cut-out.
> "Plug and Play" retrofit solution : this solution enables retrofitting of Masterpact M units with considerably reducing on-site
intervention time and getting the performance of last generation device.
The original Masterpact M chassis is kept (no intervention on the switchboard structure)
Masterpact M y 300 A
30 2
and
4
The retrofit solutions use a factory modified and adapted Masterpact NW which is installed in Masterpact Ms original chassis.
The materials used for Masterpact are not potentially dangerous to the environment and are marked to facilitate sorting for recycling.
Production facilities are nonpolluting in compliance with the ISO 400 standard.
Intuitive use
Micrologic control units are equipped with a digital LCD display used in conjunction with simple navigation buttons. Users can directly access parameters and settings. Navigation between screens is intuitive and the immediate display of values greatly simplifies settings. Text is displayed in the desired language. 6
Masterpact
General contents
Presentation
A-1
B-1
C-1
Electrical diagrams
D-1
E-1
F-1
TOOLS
schneider-electric.com The technical guide
This international site allows you to access all the Schneider Electric products in just clicks via comprehensive range datasheets, with direct links to: p complete library: technical documents, catalogs, FAQs, brochures p selection guides from the e-catalog. p product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, the list of country contacts
These technical guides help you comply with installation standards and rules i.e.: the electrical installation guide, the protection guide, the switchboard implementation guide, the technical booklets and the co-ordination tables all form genuine reference tools for the design of high performance electrical installations. For example, the LV protection co-ordination guide - discrimination and cascading - optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations.
Masterpact
Presentation
General overview
Detailed contents
A- A-4 A-6 A-8 A-0 A- A-4 A-8 A-0 A- A-4 A-5 A-6 A-8 A-30 A-3 A-3 A-35 A-36 A-37 A-39 A-4 A-43 A-44 A-45 A-47 A-49 A-50 A-5 B-1 C-1 D-1 E-1 F-1
COM option in Masterpact Overview of functions Masterpact in a communication network Masterpact and the MPS00 Micro Power Server Communication wiring system
Connections
Locking
Accessories
Presentation Mechanical interlocking Electrical interlocking Associated automatic controllers
Source-changeover systems
A-
General overview
Detailed contents
This chapter describes all the functions offered by Masterpact NT and NW devices. The two product families have identical functions implemented using the same or different components depending on the case.
page A-4
page A-10
DB03 DB04
Ammeter A .0 basic protection 5.0 selective protection 6.0 selective + earth-fault protection 7.0 selective + earth-leakage protection Power meter P 5.0 selective protection 6.0 selective + earth-fault protection 7.0 selective + earth-leakage protection Harmonic meter H 5.0 selective protection 6.0 selective + earth-fault protection 7.0 selective + earth-leakage protection b external sensor for earth-fault protection b rectangular sensor for earth-leakage protection b setting options (long-time rating plug): v low setting 0.4 to 0.8 x Ir v high setting 0.8 to x Ir v without long-time protection b external power-supply module b battery module.
page A-22
Communication
PB04347A55
page A-24
b COM option in Masterpact b Masterpact in a communication network b Masterpact and the Micro Power Server MPS00.
Connections
b rear connection (horizontal or vertical) b front connection b mixed connections b optional accessories v bare-cable connectors and connector shields v terminal shields v vertical-connection adapters v cable-lug adapters v interphase barriers v spreaders v disconnectable front-connection adapter v safety shutters, shutter locking blocks, shutter position indication and locking.
DB056 DB050 DB049 DB047
page A-31
A-
PB04348A55
Locking
b pushbutton locking by padlockable transparent cover b OFF-position locking by padlock or keylock b chassis locking in disconnected position by keylock b chassis locking in connected, disconnected and test positions b door interlock (inhibits door opening with breaker in connected position) b racking interlock (inhibits racking with door open) b racking interlock between crank and OFF pushbutton b automatic spring discharge before breaker removal b mismatch protection.
DB009 DB00
page A-35
Indication contacts
b standard or low-level contacts: v ON/OFF indication (OF) v fault trip indication (SDE) v carriage switches for connected (CE) disconnected (CD) and test (CT) positions b programmable contacts: v contacts (MC) v 6 contacts (M6C).
DB0 PB04353A55 DB0
page A-37
M2C contact.
OF contact.
Remote operation
b remote ON/OFF: v gear motor v XF closing or MX opening voltage releases v PF ready-to-close contact options: RAR automatic or RES electrical remote reset - BPFE electrical closing pushbutton b remote tripping function: v MN voltage release - standard - adjustable or non-adjustable delay v or second MX voltage release.
PB04349A55 DB03
page A-39
Gear motor.
DB04
Accessories
b b b b b auxiliary terminal shield operation counter escutcheon transparent cover for escutcheon escutcheon blanking plate.
DB05
page A-43
A-3
Masterpact NW
Standard applications
NW08...NW16 N1 NW08...NW40 H1 Circuit breaker for industrial sites with high short-circuit currents
Limiting circuit breaker Standard applications for protection of cable- with low short-circuit type feeders or currents upgraded transformer ratings 30 kA Left F D No Yes Yes A, P, H 4 kA Left F D Yes Yes Yes A, P, H
Icu/Ics at 440 V Icu/Ics at 000 V Icu/Ics at 500 V DC L/R < 5 ms Position of neutral Fixed Drawout Switch-disconnector version Front connection Rear connection Type of Micrologic control unit
Masterpact NT06 to NT16 installation characteristics Circuit breaker NT06, NT08, NT10
Type
Connection Drawout FC RC Fixed FC RC Dimensions (mm) H x W x D Drawout 3P 4P Fixed 3P 4P Weight (kg) (approximate) Drawout 3P/4P Fixed 3P/4P b b b b 3 x 88 x 77 3 x 358 x 77 30 x 76 x 96 30 x 346 x 96 30/39 4/8 b b b b b b b b
NT12, NT16
L1 H1
b b b b
H1
H2
H2
b b b b
Masterpact NW08 to NW63 installation characteristics Circuit breaker NW08, NW10, NW12, NW16
Type
Connection FC RC Fixed FC RC Dimensions (mm) H x W x D Drawout 3P 4P Fixed 3P 4P Weight (kg) (approximate) Drawout 3P/4P Fixed 3P/4P (1) Except 4000 Drawout b b b b b b b b b b b b b b b -
NW20
H10 H1
b b b b
N1
H1
H2
L1
H2
b b b b
H3
b b -
L1
b b -
H10
b -
439 x 44 x 395 439 x 556 x 395 35 x 44 x 97 35 x 537 x 97 90/0 60/80
A-4
Special applications
NW H10 H2 High-performance circuit breaker for heavy industry with high shortcircuit currents 00 kA Left or right F D Yes Yes up to 300 A Yes A, P, H H3 Incoming device with very high performance for critical applications 50 kA Left D Yes Yes up to 300 A Yes A, P, H L1 Limiting circuit breaker for protection of cable-type feeders or upgraded transformer ratings 50 kA Left D No Yes up to 300 A Yes A, P, H 000 V systems, e.g. mines and wind power NW H2 with NW10...NW40 corrosion N DC protection Environments with DC system high sulphur contents H DC DC system NW earthing switch Installation earthing
NW40b, NW50,NW63
H3
b (1) b -
H2
b (1) b b (1) b
H10
b -
H1
b b 479 x 786 x 395 479 x 06 x 395 35 x 767 x 97 35 x 997 x 97 5/300 0/60
H2
b b
A-5
PB04378A48
Common characteristics
Number of poles Rated insulation voltage (V) Impulse withstand voltage (kV) Rated operational voltage (V AC 50/60 Hz) Suitability for isolation Degree of pollution Ui Uimp Ue IEC 60947- IEC 60664- 3/4 000 690 3
Basic sweatchgear
Circuit-breaker as per IEC 60947-2
Rated current (A) Rating of 4th pole (A) Sensor ratings (A) Type of circuit breaker Ultimate breaking capacity (kA rms) V AC 50/60 Hz In at 40 C/50 C (1)
Icu
Rated service breaking capacity (kA rms) Utilisation category Rated short-time withstand current (kA rms) V AC 50/60 Hz Integrated instantaneous protection (kA peak 0 %) Rated making capacity (kA peak) V AC 50/60 Hz
Ics Icw
0/45 V 440 V 55 V 690 V % Icu 0.5 s s 3s 0/45 V 440 V 55 V 690 V
Icm
Break time (ms) between tripping order and arc extinction Closing time (ms)
Icw
Ultimate breaking capacity Icu (kA rms) with an external protection relay Maximum time delay: 350 ms Service life Mechanical without maintenance C/O cycles x 000 Type of circuit breaker Rated current In (A) without maintenance C/O cycles x 000 Electrical IEC 60947- Type of circuit breaker or switch-disconnector Rated operationnal current Ie (A) without maintenance C/O cycles x 000 Electrical IEC 60947-3 Type of circuit breaker or switch-disconnector Rated operationnal current Ie (A) Motor power C/O cycles x 000 Electrical IEC 60947-3 Annex M/IEC 60947-4- without maintenance
440 V (4) 690 V AC23A 440 V (4) 690V AC3 (5) 380/45 V (kW) 440 V (kW) 440 V (4) 690 V
(1) 50 C: rear vertical connected. Refer to temperature derating tables for other connection types. (2) See the current-limiting curves in the additional characteristics section. (3) SELLIM system. (4) Available for 480 V NEMA. (5) Suitable for motor control (direct-on-line starting).
A-6
Sensor selection
Sensor rating (A) 50 (1) Ir threshold setting(A) 00 to 50 (1) For circuit-breaker NT02, please consult us. 400 60 to 400 630 50 to 630 800 30 to 800 000 400 to 000 50 500 to 50 600 640 to 600
NT06
630 630 400 to 630 H1 H2 4 50 4 50 4 4 4 4 00 % B B 4 36 4 36 4 0 90 88 05 88 05 88 88 88 88 5 5 < 50 4 4 4 50 50 4
NT08
800 800 400 to 800 L1 (2) 50 30 00 5 A 0 0 x In (3) 330 86 0 5 9
NT10
000 000 400 to 000
NT12
50 50 630 to 50 H1 H2 4 50 4 50 4 4 4 4 00 % B B 4 36 4 36 4 0 90 88 05 88 05 88 88 88 88 5 5 < 50 4 4 4 50 50 4
NT16
600 600 800 to 600
50 00 5
HA 75 75 75 36 36 0 36
HA 75 75 75 36 36 0 36
.5 H1 H2 630 6 6 3 3 H1/H2/HA 630 6 3 H1/H2/HA 500 y 50 y 300 6 L1 3 H1 800 6 3 800 6 3 630 50 to 335 300 to 400 H2 6 3 L1 3 H1 1000 6 3 1000 6 3 800 335 to 450 400 to 500 H2 6 3 L1 3 H1 1250 6 3 1250 6 3 1000 450 to 560 500 to 630 H2 6 3 H1 3 1600 3 1000 450 to 560 500 to 630 H2 3
A-7
PB0443A35
Common characteristics
Number of poles Rated insulation voltage (V) Impulse withstand voltage (kV) Rated operational voltage (V AC 50/60 Hz) Suitability for isolation Degree of pollution Ui Uimp Ue IEC 60947- IEC 60664- 3/4 000/50 690/50 4 (000 V) / 3 (50 V)
Basic circuit-breaker
Circuit-breaker as per IEC 60947-2
Rated current (A) Rating of 4th pole (A) Sensor ratings (A)
PB04433A65
at 40 C / 50 C (1)
Icu
Rated service breaking capacity (kA rms) Utilisation category Rated short-time withstand current (kA rms) V AC 50/60 Hz Integrated instantaneous protection (kA peak 0 %) Rated making capacity (kA peak) V AC 50/60 Hz
Ics Icw
Icm
Break time (ms) between tripping order and arc extinction Closing time (ms)
Unprotected circuit-breaker
Tripping by shunt trip as per IEC 60947-2
Type of circuit breaker Ultimate breaking capacity (kA rms) V AC 50/60 Hz Rated service breaking capacity (kA rms) Rated short-time withstand current (kA rms) Icu Ics Icw 0...690 V % Icu s 3s
Overload and short-circuit protection External protection relay: short-circuit protection, maximum delay: 350 ms (4) Rated making capacity (kA peak) V AC 50/60 Hz Type of switch-disconnector Rated making capacity (kA peak) AC23A/AC3 category V AC 50/60 Hz Rated short-time withstand current (kA rms) AC23A/AC3 category V AC 50/60 Hz Icm 0...690 V
Earthing switch
Latching capacity (kA peak) Rating short time withstand (kA rms) Icw 60 Hz 50 Hz
440 V (5) 690 V 50 V AC23A 440 V (5) 690 V AC3 (6) 380/45 V (kW) 440 V (5) (kW) 690 V (kW) 440/690 V (5)
(1) 50 C: rear vertical connected. Refer to temperature derating tables for other connection types. (2) See the current-limiting curves in the additional characteristics section. (3) Equipped with a trip unit with a making current of 90 kA peak. (4) External protection must comply with permissible thermal constraints of the circuit breaker (please consult us). No fault-trip indication by the SDE or the reset button. (5) Available for 480 V NEMA. (6) Suitable for motor control (direct-on-line starting).
Type of circuit breaker or switch-disconnector Rated operational current Ie (A) C/O cycles x 000 Electrical without maintenance IEC 60947-3 Type of circuit breaker or switch-disconnector Rated operational current Ie (A) Motor power
without maintenance
A-8
Sensor selection
Sensor rating (A) Ir threshold setting(A) 50 (1) 400 00 60 to 50 to 400 (1) For circuit-breaker NW02 , please consult us. 630 50 to 630 800 30 to 800 000 400 to 000 50 500 to 50 600 630 to 600 000 800 to 000 500 000 to 500 300 50 to 300 4000 600 to 4000 5000 000 to 5000 6300 500 to 6300
NW20
000 000 000 to 000 H1 65 65 65 00 % B 65 36 43 43 43 5 < 70 65 65 H2 00 85 85 H3 50 30 00 L1 (2) 50 30 00 H10 50
50 50 05 5
50 50 05 5
50 50 05 5
65 65
00 85
50 00
00 85
50 00
50 00
00 85
50 00
50 00
HA 50 00 % 50 36 05
HF (3) 85 85 75 87
HA 55 00 % 55 55
NW08/NW10/NW12
NW16
HA 05 50 36 HF 87 85 50 HA10 05 50 50
NW20
HA 05 50 36 HF 87 85 75 HA10 05 50 50
NW25/NW32/NW40 NW40b/NW50/NW63
5 .5 N1/H1/H2 L1 800/1000/1250/1600 0 3 0 3 H1/H2/HA/HF 800/1000/1250/1600 0 0 H1/H2/HA/HF 800 1000 335 to 450 450 to 560 400 to 500 500 to 630 y 800 800 to 000 6
H10 0.5
0 0 H1/H2 H3 L1 2000 8 3 6 3 H1/H2/H3/HA/HF 2000 8 6 H1/H2/H3/HA/HF 2000 900 to 50 000 to 300 600 to 000
H10 0.5
H10 0.5
A-9
All Masterpact circuit breakers are equipped with a Micrologic control unit that can be changed on site. Control units are designed to protect Power circuits and loads. Alarms may be programmed for remote indications. Measurements of current, voltage, frequency, power and power quality optimise continuity of service and energy management.
Dependability
Integration of protection functions in an ASIC electronic component used in all Micrologic control units guarantees a high degree of reliability and immunity to conducted or radiated disturbances. On Micrologic A, P and H control units, advanced functions are managed by an independent microprocessor.
Accessories
Certain functions require the addition of Micrologic control unit accessories, described on page A-0. The rules governing the various possible combinations can be found in the documentation accessible via the Products and services menu of the www.schneider-electric.com web site.
Current protection
Micrologic 2: basic protection
Protection: long time + instantaneous
DB06
2.0 A
X Y Z
X: type of protection b for basic protection b 5 for selective protection b 6 for selective + earth-fault protection b 7 for selective + earth-leakage protection. Y: control-unit generation Identification of the control-unit generation. 0 signifies the first generation. Z: type of measurement b A for ammeter b P for power meter b H for harmonic meter.
PB0077-3
A-0
2.0 A
DB0
DB00
DB0
5.0 A
5.0 P
5.0 H
DB03
DB04
6.0 A
6.0 P
6.0 H
DB03
DB04
7.0 A
7.0 P
7.0 H
DB04
DB04
DB0
A-
Micrologic A control units protect power circuits. They also offer measurements, display, communication and current maximeters. Version 6 provides earth-fault protection, version 7 provides earth-leakage protection.
E4608
Micrologic A control units measure the true (rms) value of currents. They provide continuous current measurements from 0. to 0 In and are accurate to within .5 % (including the sensors). A digital LCD screen continuously displays the most heavily loaded phase (Imax) or displays the I, I, I3, IN, Ig,In, stored-current (maximeter) and setting values by successively pressing the navigation button. The optional external power supply makes it possible to display currents < 0 % In. Below 0.05 In, measurements are not significant. Between 0.05 and 0.2 In, accuracy is to within 0.5 % In + .5 % of the reading.
"Ammeter" measurements
Communication option
In conjunction with the COM communication option, the control unit transmits the following: b settings b all ammeter measurements b tripping causes b maximeter readings.
Protection
Protection thresholds and delays are set using the adjustment dials. Overload protection True rms long-time protection. Thermal memory: thermal image before and after tripping. Setting accuracy may be enhanced by limiting the setting range using a different long-time rating plug. Overload protection can be cancelled using a specific LT rating plug "Off". Short-circuit protection Short-time (rms) and instantaneous protection. Selection of It type (ON or OFF) for short-time delay. Earth-fault protection Residual or source ground return earth fault protection. Selection of It type (ON or OFF) for delay. Residual earth-leakage protection (Vigi). Operation without an external power supply. q Protected against nuisance tripping. k DC-component withstand class A up to 0 A. Neutral protection On three-pole circuit breakers, neutral protection is not possible. On four-pole circuit breakers, neutral protection may be set using a three-position switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/), neutral protection at Ir (4P 4d). Zone selective interlocking (ZSI) A ZSI terminal block may be used to interconnect a number of control units to provide total discrimination for short-time and earth-fault protection, without a delay before tripping.
Overload alarm
A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
1 2 3 4 5 6 7 8 9 10 11 12 13 long-time threshold and tripping delay overload alarm (LED) at 1,125 Ir short-time pick-up and tripping delay instantaneous pick-up earth-leakage or earth-fault pick-up and tripping delay earth-leakage or earth-fault test button long-time rating plug screw test connector lamp test, reset and battery test indication of tripping cause digital display three-phase bargraph and ammeter navigation buttons
Fault indications
LEDs indicate the type of fault: b overload (long-time protection Ir) b short-circuit (short-time Isd or instantaneous li protection) b earth fault or earth leakage (Ig or In) b internal fault (Ap). Battery power The fault indication LEDs remain on until the test/reset button is pressed. Under normal operating conditions, the battery supplying the LEDs has a service life of approximately 0 years.
Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation. For Micrologic 6.0 A and 7.0 A control units, the operation of earth-fault or earth-leakage protection can be checked by pressing the test button located above the test connector.
Note: Micrologic A control units come with a transparent leadseal cover as standard.
A-
Protection
Long time Current setting (A) Tripping between .05 and .0 x Ir Time setting Time delay (s) Accuracy: 0 to -30 % Accuracy: 0 to -0 % Accuracy: 0 to -0 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Instantaneous Pick-up (A) Isd = Ir x Accuracy: 0 % Time delay
Micrologic 2.0 A
0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 Other ranges or disable by changing long-time rating plug 0.5 4 8 6 0 4 50 00 00 300 400 500 600 .5 5 4 8 6 0 4 0.7(1) 5.5 8.3 3.8 6.6 0.7(2) 0.69 .38 .7 0 minutes before and after tripping
DB06 DB09 DB08 DB07
.5
.5
0
Ammeter
Continuous current measurements Display from 0 to 00 % of In Accuracy: .5 % (including sensors) Maximeters
Micrologic 2.0 A
I I3 IN I No auxiliary source (where I > 0 % In) I max I max I3 max IN max
Protection
Long time Current setting (A) Ir = In x Tripping between .05 and .0 x Ir Time setting Time delay (s) Accuracy: 0 to -30 % Accuracy: 0 to -0 % Accuracy: 0 to -0 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Short time Pick-up (A) Isd = Ir x Accuracy: 0 % Time setting tsd (s) Settings Time delay (ms) at 0 x Ir (It Off or It On) Instantaneous Pick-up (A) Accuracy: 0 % Time delay Earth fault Pick-up (A) Accuracy: 0 %
.5 0 0 80
0
It Off It On tsd (max resettable time) tsd (max break time) Ii = In x
0
5
off
Max resettable time: 0 ms Max break time: 50 ms Ig = In x In y 400 A 400 A < In < 50 A In u 50 A Settings Micrologic 6.0 A A B C 0.3 0.3 0.4 0. 0.3 0.4 500 640 70 0 0. 0. 0. 0. 0 80 40 80 40 00 Micrologic 7.0 A 0.5 60 60 40 40 40 00 30 30 30 D 0.5 0.5 800 0.3 0.3 30 30 3 350 350 500 E 0.6 0.6 880 0.4 0.4 350 500 5 800 800 000 F 0.7 0.7 960 G 0.8 0.8 040 H 0.9 0.9 0 J 00
Time setting tg (s) Time delay (ms) at In or 00 A (It Off or It On) Residual earth leakage (Vigi) Sensitivity (A) Accuracy: 0 to -0 % Time delay Dt (ms)
0
0
30
Ammeter
Continuous current measurements I I3 IN Ig Display from 0 to 00 % of In I IDn Accuracy: .5 % (including sensors) No auxiliary source (where I > 0 % In) Maximeters I max I max I3 max IN max Ig max IDn max Note: All current-based protection functions require no auxiliary source. The test / reset button resets maximeters, clears the tripping indication and tests the battery.
A-3
Micrologic P control units include all the functions offered by Micrologic A. In addition, they measure voltages and calculate power and energy values. They also offer new protection functions based on currents, voltages, frequency and power reinforce load protection in real time.
Protection ........................................................
Protection settings
The adjustable protection functions are identical to those of Micrologic A (overloads, short-circuits, earth-fault and earth-leakage protection). Fine adjustment Within the range determined by the adjustment dial, fine adjustment of thresholds (to within one ampere) and time delays (to within one second) is possible on the keypad or remotely using the COM option. IDMTL (Inverse Definite Minimum Time lag) setting Coordination with fuse-type or medium-voltage protection systems is optimised by adjusting the slope of the overload-protection curve. This setting also ensures better operation of this protection function with certain loads. Neutral protection On three-pole circuit breakers, neutral protection may be set using the keypad or remotely using the COM option, to one of four positions: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/), neutral protection at Ir (4P 4d) and neutral protection at ,6 Ir (4P 3d + ,6N). Neutral protection at ,6 Ir is used when the neutral conductor is twice the size of the phase conductors (major load imbalance, high level of third order harmonics). On four-pole circuit breakers, neutral protection may be set using a three-position switch or the keypad: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/), neutral protection at Ir (4P 4d). Neutral protection produces no effect if the long-time curve is set to one of the IDMTL protection settings.
DB0968
Load shedding and reconnection parameters may be set according to the power or the current flowing through the circuit breaker. Load shedding is carried out by a supervisor via the COM option or by an MC or M6C programmable contact.
Note: Micrologic P control units come with a non-transparent lead-seal cover as standard.
A-4
Protection
Long time (rms) Current setting (A) Ir = In x Tripping between .05 and .0 x Ir Time setting Time delay (s) Accuracy: 0 to -30 % Accuracy: 0 to -0 % Accuracy: 0 to -0 % IDMTL setting Curve slope Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Short time (rms) Pick-up (A) Isd = Ir x Accuracy: 0 % Time setting tsd (s) Settings Time delay (ms) at 0 Ir (It Off or It On) Instantaneous Pick-up (A) Accuracy: 0 % Time delay Earth fault Pick-up (A) Accuracy: 0 %
.5 0 0 80
0
It Off It On tsd (max resettable time) tsd (max break time) Ii = In x
0
5
off
Max resettable time: 0 ms Max break time: 50 ms Ig = In x In y 400 A 400 A < In < 50 A In u 50 A Settings Micrologic 6.0 P A B C 0.3 0.3 0.4 0. 0.3 0.4 500 640 70 0 0. 0. 0. 0. 0 80 40 80 40 00 Micrologic 7.0 P 0.5 60 60 40 40 40 00 30 30 30 D 0.5 0.5 800 0.3 0.3 30 30 3 350 350 500 E 0.6 0.6 880 0.4 0.4 350 500 5 800 800 000 F 0.7 0.7 960 G 0.8 0.8 040 H 0.9 0.9 0 J 00
Time setting tg (s) Time delay (ms) at In or 00 A (It Off or It On) Residual earth leakage (Vigi) Sensitivity (A) Accuracy: 0 to -0 % Time delay Dt (ms)
It Off It On tg (max resettable time) tg (max break time) IDn Settings Dt (max resettable time) Dt (max break time)
0
0
30
to 30 % x Uaverage to 40 s 00 to Umax between phases . to 0 s Umin to 00 between phases . to 0 s 5 to 500 kW 45 to Fmax Fmin to 440 Hz //3 or /3/ 0. to 0 s . to 5 s . to 5 s 0.3 s
(3) In y 400 A 30 % 400 A < In < 50 A 0 % In u 50 A 0 % (4) For 690 V applications, a step-down transformer must be used if the voltage exceeds the nominal value of 690 V by more than 0 %. Note: all current-based protection functions require no auxiliary source. Voltage-based protection functions are connected to AC power via a voltage measurement input built into the circuit breaker.
DB09
DB08
A-5
DB033
DB034
The Micrologic P control unit calculates in real time all the electrical values (V, A, W, VAR, VA, Wh, VARh, VAh, Hz), power factors and cosj factors. The Micrologic P control unit also calculates demand current and demand power over an adjustable time period. Each measurement is associated with a minimeter and a maximeter. In the event of tripping on a fault, the interrupted current is stored. The optional external power supply makes it possible to display the value with the circuit breaker open or not supplied. Instantaneous values The value displayed on the screen is refreshed every second. Minimum and maximum values of measurements are stored in memory (minimeters and maximeters). Currents
I rms I max rms A A A A V V V % W, Var, VA Wh, VARh, VAh E-fault E-fault 3 N E-leakage 3 N E-leakage
Measurements .........................................................
Default display.
DB035
DB704
Voltages U rms V rms U average rms U unbalance Power, energy P active, Q reactive, S apparent E active, E reactive, E apparent Display of a power.
Display of a voltage.
PF Hz
DB037
DB038
Demand metering The demand is calculated over a fixed or sliding time window that may be programmed from 5 to 60 minutes. According to the contract signed with the power supplier, an indicator associated with a load shedding function makes it possible to avoid or minimise the costs of overrunning the subscribed power. Maximum demand values are systematically stored and time stamped (maximeter). Currents
I demand I max demand A A A A W, Var, VA W, Var, VA E-fault E-fault Totals Totals 3 N E-leakage 3 N E-leakage
Display of a frequency.
Power
P, Q, S demand P, Q, S max demand
DB458A
Minimeters and maximeters Only the current and power maximeters may be displayed on the screen. Time-stamping Time-stamping is activated as soon as time is set manually or by a supervisor. No external power supply module is required (max. drift of hour per year). Reset An individual reset, via the keypad or remotely, acts on alarms, minimum and maximum data, peak values, the counters and the indicators. Additional measurements accessible with the COM option Some measured or calculated values are only accessible with the COM communication option: b I peak / 2, (I + I + I3)/3, I unbalance b load level in % Ir b total power factor. The maximeters and minimeters are available only via the COM option for use with a supervisor.
Power View software.
Additional info Accuracy of measurements (including sensors): b voltage (V) 0.5 % b current (A) 1.5 % b frequency (Hz) 0.1 % b power (W) and energy (Wh) 2 %.
A-6
DB704
DB7040
DB0970A
All the other events are recorded in a third history file which is only accessible through the communication network. b Event log history (only accessible through the communication network) v modifications to settings and parameters v counter resets v system faults: v fallback position v thermal self-protection v loss of time v overrun of wear indicators v test-kit connections v etc.
Note: All the events are time stampled: time-stamping is activated as soon as time is set manually or by a supervisor. No external power supply module is required (max. drift of 1 hour per year).
Micrologic H control units include all the functions offered by Micrologic P. Integrating significantly enhanced calculation and memory functions, the Micrologic H control unit offers in-depth analysis of power quality and detailed event diagnostics. It is intended for operation with a supervisor.
In addition to the Micrologic P functions, the Micrologic H control unit offers: b in-depth analysis of power quality including calculation of harmonics and the fundamentals b diagnostics aid and event analysis through waveform capture b enhanced alarm programming to analyse and track down a disturbance on the AC power system.
Measurements ................................................................................
The Micrologic H control unit offers all the measurements carried out by Micrologic P, with in addition: b phase by phase measurements of: v power, energy v power factors b calculation of: v current and voltage total harmonic distortion (THD) v current, voltage and power fundamentals v current and voltage harmonics up to the 3st order. Instantaneous values displayed on the screen Currents
I rms I max rms A A A A V V V % W, Var, VA Wh, VARh, VAh E-fault E-fault 3 N E-leakage 3 N E-leakage
DB7437
Voltages
U rms V rms U average rms U unbalance 3 3 N N 3N (U + U3 + U3) / 3
Power, energy
P active, Q reactive, S apparent E active, E reactive, E apparent Totals Totals consumed - supplied Totals consumed Totals supplied Total 3
Power factor
PF Hz
Frequencies
F
Power-quality indicators
Total fundamentals U I P Q S THD % U I U and Iharmonics Amplitude 3 5 7 9 3 Harmonics 3, 5, 7, 9, 11 and 13, monitored by electrical utilities, are displayed on the screen.
Demand measurements Similar to the Micrologic P control unit, the demand values are calculated over a fixed or sliding time window that may be set from 5 to 60 minutes. Currents
I demand I max demand A A A A W, Var, VA W, Var, VA E-fault E-fault Totals Totals 3 N E-leakage 3 N E-leakage
Power
P, Q, S demand P, Q, S max demand
Note: Micrologic H control units come with a non-transparent lead-seal cover as standard.
A-8
DB05
Waveform capture The Micrologic H control unit stores the last 4 cycles of each instantaneous current or voltage measurement. On request or automatically on programmed events, the control unit stores the waveforms. The waveforms may be displayed in the form of oscillograms by a supervisor via the COM option. Definition is 64 points per cycle. Pre-defined analogue alarms (1 to 53) Each alarm can be compared to user-set high and low thresholds. Overrun of a threshold generates an alarm. An alarm or combinations of alarms can be linked to programmable action such as selective recording of measurements in a log, waveform capture, etc. Event log and maintenance registers The Micrologic H offers the same event log and maintenance register functions as the Micrologic P. In addition, it produces a log of the minimums and maximums for each real-time value.
DB097A
Safety Measurement functions are independent of the protection functions. The high-accuracy measurement module operates independently of the protection module. Simplicity and multi-language Navigation from one display to another is intuitive. The six buttons on the keypad provide access to the menus and easy selection of values. When the setting cover is closed, the keypad may no longer be used to access the protection settings, but still provides access to the displays for measurements, histories, indicators, etc. Micrologic is also multi-language, including the following languages: English, Spanish, Portuguese, Russian, Chinese, French, German;;; Intelligent measurement Measurement-calculation mode: b energies are calculated on the basis of the instantaneous power values, in two manners: v the traditional mode where only positive (consumed) energies are considered v the signed mode where the positive (consumed) and negative (supplied) energies are considered separately b measurement functions implement the new zero blind time concept which consists in continuously measuring signals at a high sampling rate. The traditional blind window used to process samples no longer exists. This method ensures accurate energy calculations even for highly variable loads (welding machines, robots, etc.). Always powered All current-based protection functions require no auxiliary source. Voltage-based protection functions are connected to AC power via a voltage measurement input built into the circuit breaker. Stored information The fine setting adjustments, the last 100 events and the maintenance register remain in the control-unit memory even when power is lost.
Log.
A-9
DB054
External sensors
External sensor for earth-fault and neutral protection The sensors, used with the 3P circuit breakers, are installed on the neutral conductor for: b neutral protection (with Micrologic P and H) b residual type earth-fault protection (with Micrologic A, P and H).. The rating of the sensor (CT) must be compatible with the rating of the circuit breaker: b NT06 to NT6: TC 400/600 b NW08 to NW0: TC 400/000 b NW5 to NW40: TC 000/4000 b NW40b to NW63: TC 4000/6300. For oversized neutral protection the sensor rating must be compatible with the measurement range: .6 x IN (available up to NW 40 and NT 6). Rectangular sensor for earth-leakage protection The sensor is installed around the busbars (phases + neutral) to detect the zerophase sequence current required for the earth-leakage protection. Rectangular sensors are available in two sizes. Inside dimensions (mm) b 80 x 5 up to 600 A for Masterpact NT and NW b 470 x 60 up to 300 A for Masterpact NW. External sensor for source ground return protection The sensor is installed around the connection of the transformer neutral point to earth and connects to the Micrologic 6.0 control unit via an MDGF module to provide the source ground return (SGR) protection. Voltage measurement inputs Voltage measurement inputs are required for power measurements (Micrologic P or H) and for earth-leakage protection (Micrologic 7...). As standard, the control unit is supplied by internal voltage measurement inputs placed downstream of the pole for voltages between 0 and 690 V AC. On request, it is possible to replace the internal voltage measurement inputs by an external voltage input (PTE option) which enables the control unit to draw power directly from the distribution system upstream of the circuit breaker. An 3 m cable with ferrite comes with this PTE option.
Rectangular sensor.
0633779A
Four interchangeable plugs may be used to limit the long-time threshold setting range for higher accuracy. The time delay settings indicated on the plugs are for an overload of 6 Ir (for further details, see the characteristics on page A-3 and page A-5). As standard, control units are equipped with the 0.4 to plug. Setting ranges
Standard Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 Low-setting option Ir = In x 0.4 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.8 High-setting option Ir = In x 0.80 0.8 0.85 0.88 0.90 0.9 0.95 0.98 Off plug No long-time protection (Ir = In for Isd setting) Important: long-time rating plugs must always be removed before carrying out insulation or dielectric withstand tests.
PB006-3A
The external power-supply module makes it possible to use the display even if the circuit breaker is open or not supplied (for the exact conditions of use, see the electrical diagrams part of this catalogue). This module powers both the control unit (00 mA) and the MC and M6C programmable contacts (00 mA). If the COM communication option is used, the communication bus requires its own 4 V DC power supply, independent with respect to that of the Micrologic control unit. With the Micrologic A control unit, this module makes it possible to display currents of less than 0 % of In. With the Micrologic P and H, it can be used to display fault currents after tripping. Characteristics b power supply: v 0/30, 00/40, 380/45 V AC (+0 % -5 %) v 4/30, 48/60, 00/5 V DC (+0 % -0 %) b output voltage: 4 V DC 5 %, 00 mA. b ripple < % b dielectric withstand : 3.5 kV rms between input/output, for minute b overvoltage category: as per IEC 60947- cat. 4.
A-0
PB0077-4
Battery module
The battery module maintains display operation and communication with the supervisor if the power supply to the Micrologic control unit is interrupted. It is installed in series between the Micrologic control unit and the AD module. Characteristics b battery run-time: 4 hours (approximately) b mounted on vertical backplate or symmetrical rail.
PB00774-3
PB0078-3
M2C.
M6C.
MC: 4 V DC power supplied by control unit (consumption 00 mA). M6C: external 4 V DC power supply required (consumption 00 mA).
PB00775-3
Spare parts
Lead-seal covers A lead-seal cover controls access to the adjustment dials. When the cover is closed: b it is impossible to modify settings using the keypad unless the settings lockout pin on the cover is removed b the test connector remains accessible b the test button for the earth-fault and earth-leakage protection function remains accessible. Characteristics b transparent cover for basic Micrologic and Micrologic A control units b non-transparent cover for Micrologic P and H control units. Spare battery A battery supplies power to the LEDs identifying the tripping causes. Battery service life is approximately ten years. A test button on the front of the control unit is used to check the battery condition. The battery may be replaced on site when discharged.
Lead-seal cover.
PB00837-68
Test equipment
Hand-held test kit The hand-held mini test kit may be used to: b check operation of the control unit and the tripping and pole-opening system by sending a signal simulating a short-circuit b supply power to the control units for settings via the keypad when the circuitbreaker is open (Micrologic P and H control units). Power source: standard LR6-AA battery. Full function test kit The test kit can be used alone or with a supporting personal computer. The test kit without PC may be used to check: b the mechanical operation of the circuit breaker b the electrical continuity of the connection between the circuit breaker and the control unit b operation of the control unit: v display of settings v automatic and manual tests on protection functions v test on the zone-selective interlocking (ZSI) function v inhibition of the earth-fault protection v inhibition of the thermal memory. The test kit with PC offers in addition: b the test report (software available on request).
Portable test kit.
A-
GetnSet is a portable data acquisition and storage accessory that connects directly to the Micrologic control units of Masterpact circuit breakers to read important electrical installation operating data and Masterpact protection settings. This information is stored in the GetnSet internal memory and can be transferred to a PC via USB or Bluetooth for monitoring and analysis.
GetnSet() is a portable data acquisition and storage device that works like a USB drive, letting users manually transfer data to and from a Masterpact circuit breaker or PC. GetnSet can download operating data from Masterpact and download or upload settings. Downloadable operating data include measurements, the last 3 trip history records and contact wear status. Accessible settings include protection thresholds, external relay assignment modes and pre-defined alarm configurations if applicable.
PB0407
DB766
1 2 3 4 5 6 7
DB7440
On/Off batterie indicator Download settings Download operating parameters Upload settings USB indicator Bluetooth indicator
Electrical installation information such as energy measurements and contact wear status is increasingly important to help reduce operating expenses and increase the availability of electrical power. Such data is often available from devices within the installation, but needs to be gathered and aggregated to allow analysis and determine effective improvement actions. With GetnSet, this operating data can be easily read and stored as .dgl files in the internal memory. It can then be transferred to a PC via a USB or Bluetooth link and imported in an Excel spreadsheet. The provided Excel spreadsheet can be used to display the operating data from several breakers in order to: b analyse changes in parameters such as energy, power factor and contact wear b compare the values of parameters between circuit breakers b create graphics and reports using standard Excel tools
Micrologic
A P P P P H H H H H
A-
DB744
GetnSet can also be used to back up circuit breaker settings and restore them on the same device or, under certain conditions, copy them to any Masterpact circuit breaker equipped with the same type of Micrologic control unit. This concerns only advanced settings, as other parameters must be set manually using the dials on the Micrologic control unit. b When commissioning the installation, safeguard the configuration parameters of your electrical distribution system by creating a back-up of circuit breaker settings so that they can be restored at any time. b The settings read by GetnSet can be transferred to a PC and are compatible with RSU software (Remote Setting Utility). Protection configurations can also be created on a PC using this software, copied to GetnSet's internal memory and uploaded to a Masterpact circuit breaker with a compatible Micrologic trip unit and dial settings. The procedure includes several steps. b Plug GetnSet into the receptacle on the front of the Micrologic control unit of a Masterpact circuit breaker. b On the keypad, select the type of data (operating data or settings) and the transfer direction (download or upload). This operation can be done as many times as required for the entire set of Masterpact circuit breakers. b Downloaded data is transferred to the GetnSet internal memory and a file is created for each Masterpact device (either an .rsu file for settings or a.dgl file for operating data). b Data can be transferred between GetnSet and a PC via a USB or Bluetooth connection. b Operating data can be imported in an Excel spreadsheet and protection settings can be read with RSU (remote setting utility) software. b Battery-powered to power a Micrologic control unit even if the breaker has been opened or tripped. This battery provides power for an average of hour of use, enough for more than 00 download operations. b Can be used on Masterpact circuit breakers equipped or not equipped with a Modbus "device" communication module. b Portable, standalone accessory eliminating the need for a PC to connect to a Masterpact circuit breaker. b No driver or software required for GetnSet connection to a PC. b Can be used with many circuit breakers, one after the other. b Embedded memory sized to hold data from more than 5000 circuit breakers. b Supplied with its battery, a cable for connection to Micrologic trip units, a USB cable for connection to a PC and a battery charger.
Operating procedure
Features
Compatibility
b Micrologic control units A, P, H b PC with USB port or Bluetooth link and Excel software
Technical characteristics
Charger power supply Charger power consumption Battery Operating temperature GetnSet dimensions 00 40 V; aA; 50 60 Hz Max 00 W 3.3 V DC; 9mAh; Li-Ion -0 to +60 C 95 x 60 x 35 mm
A-3
Communication
The COM option is required for integration of the circuit breaker or switch-disconnector in a supervision system. Masterpact uses the Modbus communications protocol for full compatibility with the supervision management systems. An external gateway is available for communication on other networks: b Ion Enterprise (power management system) b Ethernet gateway (MPS00/EGX) b Ethernet b Profibus. Eco COM is limited to the transmission of metering data and does not allow the control of the circuit breaker.
For fixed devices, the COM option is made up of: b a device communication module, installed behind the Micrologic control unit and supplied with its set of sensors (OF, SDE ,PF and CH micro-contacts) and its kit for connection to XF and MX communicating voltage releases. For drawout devices, the COM option is made up of: b a device communication module, installed behind the Micrologic control unit and supplied with its set of sensors (OF, SDE, PF and CH micro-contacts) and its kit for connection to XF and MX communicating voltage releases b a chassis communication module supplied separately with its set of sensors (CE, CD and CT contacts). Status indication by the COM option is independent of the device indication contacts. These contacts remain available for conventional uses. Digipact or Modbus Device communication module This module is independent of the control unit. It receives and transmits information on the communication network. An infra-red link transmits data between the control unit and the communication module. Consumption: 30 mA, 4 V. Digipact or Modbus chassis communication module This module is independent of the control unit. With Modbus chassis communication module, this module makes it possible to address the chassis and to maintain the address when the circuit breaker is in the disconnected position. Consumption: 30 mA, 4 V. XF and MX1 communicating voltage releases The XF and MX communicating voltage releases are equipped for connection to the device communication module. The remote-tripping function (MX or MN) are independent of the communication option. They are not equipped for connection to the device communication module.
PB0078-6
PB0080B-7
DB7036
1 2 3 4 5 6
Device communication module. Chassis communication module (option). OF, SDE, PF and CH communicating device sensors. CE, CD and CT communicating chassis sensors. MX1 and XF communicating release. Control unit.
A-4
Overview of functions
056484N-60
The Masterpact circuit breakers and switch-disconnectors are compatible with the Digipact or Modbus COM option. The COM option may be used to: b identify the device b indicate status conditions b control the device. Depending on the different types of Micrologic (A, P, H) control units, the COM option also offers: b setting of the protection and alarms functions b analysis of the AC-power parameters for operating-assistance and maintenance purposes.
Switch-disconnector Circuit breaker with with communication communication bus bus Modbus Modbus
Device identification
Address Rating Type of device Type of control unit Type of long-time rating plug b b b (1) b b A A A A A A A A A P P P P P P P P P P H H H H H H H H H H
Status indications
ON/OFF OF Spring charged CH Ready to close PF Fault-trip SDE Connected/disconnected/test position CE/CD/CT
Controls
ON/OFF MX/XF Spring charging Reset of the mechanical indicator b A P H
Fault readings
Type of fault Interrupted current
Waveform capture
On faults On demand or programmed
Indicators
Counter operation A P H Contact wear P H Maintenance register P H Note: see the description of the Micrologic control units for further details on protection and alarms, measurements, waveform capture, histories, logs and maintenance indicators. (1) With modbus it is possible to monitor the PF status please see the instruction bulletin COMBT32AK at page 51/Register 661 documentation. A: Micrologic with ammeter P: Micrologic Power H: Micrologic Harmonics
A-5
Communication
b Modbus is the most widely used communication protocol in industrial networks. b Masterpact, Compact NSX, PowerLogic and Sepam products all operate with this protocol. A Modbus network is generally implemented on an LV or MV switchboard scale.
DB099
Modbus
Firewall
Internet
Modbus
Modbus
FDM121
Masterpact
Compact NSX
Sepam
DB6
A Modbus TCP gateway can be used to connect the Modbus network to ethernet. The gateway has the two main functions: b access to the company intranet (Ethernet) by converting Modbus frames to the TCP/IP Modbus protocol, b optional web-page server for the information from the devices. Examples include MPS00, EGX400 and EGX00.
Web page.
Gateway
MPS100 b Plug and play device. It comes loaded with a web-page application for graphic display of currents and voltages and viewing of circuit-breaker status and power and energy values. To use the application, simply declare the Modbus addresses of the connected slaves. Automatically recognised devices include all Masterpact and Compact NSX Micrologic trip units and the PM500/700/800 and PM9c power monitoring units. b Can be used for automatic alarm notification via a messaging server available on the site intranet or via mobile phones (e-mail converted into SMS). b Can be used for logging of data that can be automatically sent as e-mail attachments, e.g. a weekly consumption report.
A-6
Number of devices The maximum number of devices that may be connected to the Modbus bus depends on the type of device (Masterpact with Modbus COM, Power Meter, Sepam, Vigilohm, etc.), the baud rate (900 is recommended), the volume of data exchanged and the desired response time. The RS485 physical layer offers up to 3 connection points on the bus ( master, 3 slaves). A fixed device requires only one connection point (communication module on the device). A drawout device uses two connection points (communication modules on the device and on the chassis). The number must never exceed 31 fixed devices or 15 drawout devices. Length of bus The maximum recommended length for the Modbus bus is 00 meters. Bus power source A 4 V DC power supply is required (less than 0 % ripple, insulation class II).
Communication interface
The Modbus bus may be connected to the central processing device in any of three manners: b direct link to a PLC. The communication interface is not required if the PLC is equipped with a Modbus port b direct link to a computer. The Modbus (RS485) / Serial port (RS3) communication interface is required b connection to a TCP/IP (Ethernet) network. The Modbus (RS485) / TCP/IP (Ethernet) communication interface is required.
Devices
Circuit breakers equipped with Micrologic control units may be connected to either a Modbus communication bus. The information made available depends on the type of Micrologic control unit (A, P or H) and on the type of communication bus (Modbus). Switch-disconnectors can be connected to the Modbus communication bus. The information made available is the status of the switch-disconnector.
Software
To make use of the information provided by the communicating devices, software with a Modbus driver must be used.
Micrologic utilities
This is a set of software that may be used with a PC to: b display the variables (I, U, P, E, etc.) with the RDU (Remote Display Utility) b read/write the settings with the RSU (Remote Setting Utility) b remotely control (ON / OFF) the device with the RCU (Remote Control Utility). Micrologic utilities are available upon request
Communication
The MPS00 Micro Power Server: b notifies maintenance staff when any preset alarm or trip is activated by the Micrologic trip unit, automatically sending an email and/or SMS b data logs are periodically forwarded by e-mail b the e-mails are sent via an Ethernet local area network (LAN) or remotely via modem.
Micro Power Server is designed for unattended operation within the main LV switchboard
The MPS00 is a self-contained facility information server that serves as a standalone device for power system monitoring. It is used to transfer power system information via a standard web browser over an Ethernet local area network (LAN) or via modem, making it possible to view power system information on a PC with an Ethernet connection. In either capacity, the Micro Power Server functions as a web server for Micrologic trip unit and Power Meter supervision, automatically notifying (e-mail and/or SMS) maintenance staff when any preset alarm or trip is activated in the Micrologic trip unit.
PB00804-60
PB0083-4
Benefits
MPS100 Micro Power Server.
b view your main LV switchboard without installing software on your local PC, eliminating the need for a dedicated PC with specific software b Micro Power Server allows centralised monitoring, so you no longer waste precious time walking around the facility to collect data b view your main LV switchboard via a modem connection (GSM or switched network), avoiding the need for a LAN b maintenance people are automatically notified at any time, wherever they are, so you do not have to stay in front of a monitor all day long b data logs can be periodically forwarded by sending e-mails to the relevant people (maintenance, accounting, application service provider) automatically b possibility to monitor/notify six external events (limit switches, auxiliary switches...) b back-up of Micrologic trip unit settings in the memory of the MPS00, so you know where to retrieve it when necessary.
PB00799-68
Main LV switchboard.
PB00877A-67
Monitoring of your main LV switchboard via embedded web pages in the MPS100 accessible with a standard web browser.
A-8
Typical architecture
PB00799-34
DB0380
Features
b access to the power system via a standard PC web browser b real-time data displayed with an intuitive and user friendly interface (dashboard) b Ethernet Modbus TCP/IP connectivity directly to the LAN or via modem (Point to Point Protocol services) b SMTP (Simple Mail Transfer Protocol) client (capacity to send e-mail) b local logging of data such as energy, power, current b set-up and system configuration through MPS100 embedded HTML pages b user interface translatable in any language, factory settings in English and French b 6 inputs/ outputs (no-volt contact) b DHCP (Dynamic Host Configuration Protocol) client.
Power Meter.
Technical characteristics
Power supply 4 V DC 5 %, consumption = 50 mA Operating temperature 0 to +50 C Rugged compact metal housing 35 x 8 x 5 mm (H x W x D) Additional information available at: http://94..45.4/mkt/microser.nsf User name: MPS, Password: MPS00
A-9
Communication
DB5555
Wiring system The wiring system is designed for low-voltage power switchboards. Installation requires no tools or special skills. The prefabricated wiring ensures both data transmission (ModBus protocol) and 4 V DC power distribution for the communications modules on the Micrologic control units.
DB703
CCP 303: Connection cable between Masterpact or Compact and junction block.
DB7030
Masterpact circuit breakers equipped with Micrologic control units and the ModBus COM option.
CCR 301: Roll of RS 485 cable (2 RS 485 wires + 2 power supply wires).
DB7035
DB5556
CSD 309: SubD 9-pin connector for colour-coded connection of wires to screw terminals.
Masterpact circuit breakers equipped with Micrologic control units and the ModBus eco COM option.
A-30
Connections
Overview of solutions
Three types of connection are available: b vertical or horizontal rear connection b front connection b mixed connection. The solutions presented are similar in principle for all Masterpact NT and NW fixed and drawout devices.
Rear connection
Horizontal
PB04354A40 PB04355A40
Vertical
Simply turn a horizontal rear connector 90 to make it a vertical connector. For the 6300 A circuit breaker, only vertical connection is available.
Front connection
PB04356A40
Mixed connection
PB04357A40 PB04358A40
PB04359A40
Note: Masterpact circuit breakers can be connected indifferently with bare-copper, tinned-copper and tinned-aluminium conductors, requiring no particular treatment.
A-3
Connections
Accessories
Type of accessory
Drawout
DB056
Front connection
Rear connection
Front connection
Interphase barriers
DB048 DB049 DB049 DB049
(1)
(1)
(2)
(2)
Spreaders
DB050 DB050
standard
DB05
standard
DB055
(3)
DB055
(4)
(1) Mandatory for voltages > 500 V. (2) Except for an NW40 equipped for horizontal rear connection, and for fixed NW40b-NW63. (3) Mandatory for 1000 V and for fixed NT front-connection versions with vertical-connection adapters oriented towards the front. (4) Mandatory for 1000 V.
A-3
DB054
PB04360A30
PB0436A30
PB04350A30
PB0436A30
Spreaders (option)
Mounted on the front or rear connectors, spreaders are used to increase the distance between bars in certain installation configurations.
DB7039
A-33
Connections
Accessories
PB04363A350
PB04364A50
DB058
A-34
Locking
On the device
DB059
1 Reset button for mechanical trip indication. 2 OFF pushbutton. 3 OFF position lock. 4 Electrical closing pushbutton. 5 ON pushbutton. 6 Springs charged indication. 7 Pushbutton locking. 8 Contact position indication. 9 Operation counter.
PB008-3
A-35
Locking
On the chassis
DB060
Mismatch protection. Door interlock. Racking interlock. Keylock locking. Padlock locking. Position indicator. Chassis front plate (accessible with cubicle door closed). 8 Racking-handle entry. 9 Reset button. 10 Racking-handle storage. 1 2 3 4 5 6 7
PB04366A3
PB04367A34
Door interlock.
PB04368 A3
Racking interlock between crank and OFF pushbutton IBPO (for NW only)
Racking interlock.
PB0085-3R_SE
This option makes it necessary to press the OFF pushbutton in order to insert the racking handle and holds the device open until the handle is removed.
Mismatch protection ensures that a circuit breaker is installed only in a chassis with compatible characteristics. It is made up of two parts (one on the chassis and one on the circuit breaker) offering twenty different combinations that the user may select.
A-36
Indication contacts
Indication contacts are available: b in the standard version for relay applications b in a low-level version for control of PLCs and electronic circuits. MC and M6C contacts may be programmed via the Micrologic P and H control units.
Standard V AC 40/380 480 690 4/48 5 50 4/48 40 380 4/48 5 50
PB00806-3
PB00807-0
V DC
PB0080-3
Standard V AC 40/380 480 690 4/48 5 50 4/48 40 380 4/48 5 50
V DC
V DC
PB0086-3
V DC
A-37
Indication contacts
PB0087-3
PB00778-5
Standard V AC 40 380 480 690 4/48 5 50 4/48 40 380 4/48 5 50
Low-level V AC
V DC
These contacts, used with the Micrologic P and H control units, may be programmed via the control unit keypad or via a supervisory station with the COM communication option. They require an external power supply module. They indicate: b the type of fault b instantaneous or delayed threshold overruns. b They may be programmed: b with instantaneous return to the initial state b without return to the initial state b with return to the initial state following a delay. Characteristics M2C/M6C
Minimum load Breaking capacity (A) p.f.: 0.7 V AC V DC 40 380 4 48 5 50 00 mA/4 V 5 3 .8 .5 0.4 0.5
DB7038
A-38
DB070
Remote operation
Remote ON / OFF
Two solutions are available for remote operation of Masterpact devices: b a point-to-point solution b a bus solution with the COM communication option.
The remote ON / OFF function is used to remotely open and close the circuit breaker. It is made up of: b an electric motor MCH equipped with a springs charged limit switch contact CH b two voltage releases: v a closing release XF v an opening release MX. Optionally, other functions may be added: b a ready to close contact PF b an electrical closing pushbutton BPFE b remote RES following a fault. A remote-operation function is generally combined with: b device ON / OFF indication OF b fault-trip indication SDE.
PB04349A68
Note: an opening order always takes priority over a closing order. If opening and closing orders occur simultaneously, the mechanism discharges without any movement of the main contacts. The circuit breaker remains in the open position (OFF). In the event of maintained opening and closing orders, the standard mechanism provides an anti-pumping function by blocking the main contacts in open position. Anti-pumping function. After fault tripping or intentional opening using the manual or electrical controls, the closing order must first be discontinued, then reactivated to close the circuit breaker. When the automatic reset after fault trip (RAR) option is installed, to avoid pumping following a fault trip, the automatic control system must take into account the information supplied by the circuit breaker before issuing a new closing order or blocking the circuit breaker in the open position (information on the type of fault, e.g. overload, short-time fault, earth fault, earth leakage, short-circuit, etc.).
Note: MX communicating releases are of the impulse type only and cannot be used to lock a circuit breaker in OFF position. For locking in OFF position, use the remote tripping function (2nd MX or MN). When MX or XF communicating releases are used, the third wire (C3, A3) must be connected even if the communication module is not installed. When the control voltage (C3-C1 or A3-A1) is applied to the MX or XF releases, it is necessary to wait 1.5 seconds before issuing an order. Consequently, it is advised to use standard MX or XF releases for applications such as source-changeover systems.
A-39
Remote operation
Remote ON / OFF
PB00797-3
PB00808-3
DB7037
Characteristics
Power supply V AC 50/60 Hz V DC Operating threshold Consumption (VA or W)
XF
MX
4 - 48 - 00/30 - 00/50 - 77 - 380/480 - 4/30 - 48/60 - 00/30 - 00/50 0.7 to . Un 0.85 to . Un Hold: 4.5 Hold: 4.5 Pick-up: 00 (00 ms) Pick-up: 00 (00 ms) Circuit-breaker response time at Un 55 ms 0 (Masterpact NT) 50 ms 0 70 ms 0 (NW y 4000 A) 80 ms 0 (NW > 4000 A)
PB00809-6
PB0088-6
V DC
A-40
PB00798-56
Automatic reset after fault trip RAR Following tripping, a reset of the mechanical indicator (reset button) is no longer required to enable circuit-breaker closing. The mechanical (reset button) and electrical SDE indications remain in fault position until the reset button is pressed. The use of XF closing release is compulsory with this option.
A-4
Remote operation
Remote tripping
PB04369A68
This function opens the circuit breaker via an electrical order. It is made up of: b a shunt release second MX b or an undervoltage release MN b or a delayed undervoltage release MNR: MN + delay unit. These releases (nd MX or MN) cannot be operated by the communication bus. The delay unit, installed outside the circuit breaker, may be disabled by an emergency OFF button to obtain instantaneous opening of the circuit breaker. Wiring diagram for the remote-tripping function
DB07 DB075 DB788
DB00809-6
When energised, the MX voltage release instantaneously opens the circuit breaker. A continuous supply of power to the second MX locks the circuit breaker in the OFF position. Characteristics
Power supply V AC 50/60Hz V DC 4 - 48 - 00/30 - 00/50 - 77- 380/480 - 4/30 - 48/60 - 00/30 - 00/50 0.7 to . Un 0.85 to . Un Pick-up: 00 (80 ms) 50 ms 0 Hold: 4.5
Operating threshold Permanent locking function Consumption (VA or W) Circuit-breaker response time at Un
The MN release instantaneously opens the circuit breaker when its supply voltage drops to a value between 35 % and 70 % of its rated voltage. If there is no supply on the release, it is impossible to close the circuit breaker, either manually or electrically. Any attempt to close the circuit breaker has no effect on the main contacts. Circuitbreaker closing is enabled again when the supply voltage of the release returns to 85 % of its rated value. Characteristics
V AC 50/60 Hz V DC Operating threshold Opening Closing Consumption (VA or W) MN consumption with delay unit (VA or W) Circuit-breaker response time at Un Power supply 4 - 48 - 00/30 - 00/50 - 380/480 4/30 - 48/60 - 00/30 - 00/50 0.35 to 0.7 Un 0.85 Un Pick-up: 00 (00 ms) Hold: 4.5 Pick-up: 00 (00 ms) Hold: 4.5 40 ms 5 for NT 90 ms 5 for NW
MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of the MN release can be delayed. This function is achieved by adding an external delay unit in the MN voltage-release circuit. Two versions are available, adjustable and non-adjustable. Characteristics
Power supply V AC 50-60 Hz /DC Operating threshold Delay unit consumption Circuit-breaker response time at Un Non-adjustable 00/30 - 00/50 Adjustable 48/60 - 00/30 - 00/50 - 380/480 Opening 0.35 to 0.7 Un Closing 0.85 Un Pick-up: 00 (00 ms) Hold: 4.5 Non-adjustable 0.5 s Adjustable 0.5 s - 0.9 s - .5 s - 3 s
A-4
Accessories
PB104740
Optional equipment mounted on the chassis, the shield prevents access to the terminal block of the electrical auxiliaries.
PB104382A32
The operation counter sums the number of operating cycles and is visible on the front panel. It is compatible with manual and electrical control functions. This option is compulsory for all the source-changeover systems.
DB101173
Escutcheon CDP
Optional equipment mounted on the door of the cubicle, the escutcheon increases the degree of protection to IP 40 (circuit breaker installed free standing: IP30) . It is available in fixed and drawout versions.
Used with the escutcheon, this option closes off the door cut-out of a cubicle not yet equipped with a device. It may be used with the escutcheon for both fixed and drawout devices.
Optional equipment mounted on the escutcheon, the cover is hinged and secured by a screw. It increases the degree of protection to IP54, IK10. It adapts to drawout devices.
A-43
Source-changeover systems
Presentation
PB00843A
PB00844A
Tertiaire : b salles d'oprations des hpitaux b dispositifs de scurit d'immeubles de grande hauteur b salles d'ordinateurs (banques, assurances...) b systmes d'clairage de centres commerciaux...
PB00845A
Communication option
The communication option must not be used to control the opening or closing of source-changeover system circuit breakers. It should be used only to transmit measurement data or circuit-breaker status. The eco COM option is perfectly suited to these equipments.
Industry: b assembly lines b engine rooms on ships b critical auxiliaries in thermal power stations
PB00846A PB00847A
Infrastructures: b port and railway installations b runway lighting systems b control systems on military sites
A-44
Mechanical interlocking
DB057
Interlocking of two Compact NS630b to 1600 or two Masterpact NT and NW devices using connecting rods
The two devices must be mounted one above the other (either 2 fixed or 2 withdrawable/drawout devices). Combinations are possible between Compact NS630b to NS600 devices and between Masterpact NT and Masterpact NW devices. Installation This function requires: b an adaptation fixture on the right side of each circuit breaker or switchdisconnector b a set of connecting rods with no-slip adjustments. The adaptation fixtures, connecting rods and circuit breakers or switchdisconnectors are supplied separately, ready for assembly by the customer. The maximum vertical distance between the fixing planes is 900 mm.
Possible combinations of Normal and Replacement source circuit breakers
Normal N
Replacement R
NS630b to NS1600 NT06 to NT16 NW08 to NW40 NW40b to NW63
NS630b to NS1600 Ratings 50... 600 A NT06 to NT16 Ratings 50... 600 A NW08 to NW40 Ratings 30... 4000 A NW40b to NW63 Ratings 4000... 6300 A
b b b b b b b b b b
A-45
Source-changeover systems
Mechanical interlocking
PB100842_68_SE
For cable interlocking, the circuit breakers may be mounted one above the other or side-by-side. The interlocked devices may be fixed or drawout, three-pole or four-pole, and have different ratings and sizes. Interlocking between two devices (Masterpact NT and NW) This function requires: b an adaptation fixture on the right side of each device b a set of cables with no-slip adjustments b the use of a mechanical operation counter CDM is compulsory. The maximum distance between the fixing planes (vertical or horizontal) is 2000 mm. Interlocking between three devices (Masterpact NW only) This function requires: b a specific adaptation fixture for each type of interlocking, installed on the right side of each device b two or three sets of cables with no-slip adjustments b the use of a mechanical operation counter CDM is compulsory. The maximum distance between the fixing planes (vertical or horizontal) is 1000 mm. Installation The adaptation fixtures, sets of cables and circuit breakers or switch-disconnectors are supplied separately, ready for assembly by the customer. Installation conditions for cable interlocking systems: b cable length: 2.5 m b radius of curvature: 100 mm b maximum number of curves: 3.
Possible combinations of Normal and Replacement source circuit breakers
Normal N
NT06 to NT16 Ratings 250... 1600 A NW08 to NW40 Ratings 320... 4000 A NW40b to NW63 Ratings 4000... 6300 A
Replacement R
NT06 to NT16 b b b NW08 to NW40 b b b NW40b to NW63 b b b
All combinations of two Masterpact NT and Masterpact NW devices are possible, whatever the rating or size of the devices.
Possible combinations of three device NT06 to NT16 NT06 to NT16 Ratings 250... 1600 A NW08 to NW40 Ratings 320... 4000 A NW40b to NW63 Ratings 4000... 6300 A NW08 to NW40 NW40b to NW63
b b
b b
A-46
Electrical interlocking
Electrical interlocking is used with the mechanical interlocking system. It electrically interlocks the two circuit breakers and implements the time delays required for proper operation of the system. An automatic controller may be added to take into account information from the distribution system.
Electrical interlocking is carried out by an electrical control device. For Masterpact, this function can be implemented in one of two ways: b using the IVE unit b by an electrician based on the diagrams presented in the Electrical diagrams part of this catalogue. b external connection terminal block: v inputs: circuit breaker control signals v outputs: status of the SDE contacts on the Normal and Replacement source circuit breakers b 2 connectors for the two Normal and Replacement source circuit breakers: v inputs: - status of the OF contacts on each circuit breaker (ON or OFF) - status of the SDE contacts on the Normal and Replacement source circuit breakers v outputs: power supply for operating mechanisms b control voltage: v 24 to 250 V DC v 48 to 415 V 50/60 Hz - 440 V 60 Hz. The IVE unit control voltage must be same as that of the circuit breaker operating mechanisms.
DB101573
IVE unit.
Necessary equipment
For Masterpact NT and NW, each circuit breaker must be equipped with: b a remote-operation system made up of: v MCH gear motor v MX or MN opening release v XF closing release v PF ready to close contact v CDM mechanical operation counter b an available OF contact b one to three CE connected-position contacts (carriage switches) on drawout circuit
A-47
Source-changeover systems
Standard configuration
Diagram no.
51201139 51201140 51201141 51201142 51201143 51201144 51156226 51156227 51156904 51156905 51156903
Masterpact NW only
Types of mechanical interlocking
3 devices: 2 Normal sources and 1 Replacement source
DB0575
Diagram no.
51156906 51156907
3 devices: 2 Normal sources and 1 Replacement source with source selection QN1 QN2 QR 0 0 0 0 0 0 0 0 0 0 3 devices: 3 sources, only one device
DB0576
b automatic control with engine generator set: v without lockout after fault (with MN) v with lockout after fault (with MN)
51156908 51156909
DB0577
QS2 0 0 0
QS3 0 0 0
b electrical interlocking: v without lockout after fault v with lockout after fault
51156910 51156911
DB0578
QS1 QC QS2 b electrical interlocking: 0 0 0 v without lockout after fault 0 v with lockout after fault 0 b automatic control with lockout after fault 0 (1) 0 0 (1) 0 0 (1) possible by forcing operation Lockout after fault option. This option makes it necessary to manually reset the device following fault tripping.
A-48
By combining a remote-operated source-changeover system with an integrated BA or UA automatic controller, it is possible to automatically control source transfer according to userselected sequences. These controllers can be used on source-changeover systems comprising circuit breakers. For source-changeover systems comprising 3 circuit breakers, the automatic control diagram must be prepared by the installer as a complement to to diagrams provided in the electrical diagrams section of this catalogue.
Controller
Compatible circuit breakers
BA
UA
4-position switch
Automatic operation Forced operation on Normal source Forced operation on Replacement source Stop (both Normal and Replacement sources off)
Automatic operation
Monitoring of the Normal source and automatic transfer Generator set startup control Delayed shutdown (adjustable) of generator set Load shedding and reconnection of non-priority circuits Transfer to the Replacement source if one of the phases of the Normal phase is absent
Test
By opening the P5M circuit breaker supplying the controller By pressing the test button on the front of the controller b b b b b b b b b
Indications
PB00855_SE
Circuit breaker status indication on the front of the controller: on, off, fault trip Automatic mode indicating contact
Other functions
Selection of type of Normal source (single-phase or three-phase) (1) Voluntary transfer to Replacement source (e.g. energy management commands) During peak-tariff periods (energy management commands) forced operation on Normal sourceif Replacement source not operational Additional contact (not part of controller). Transfer to Replacement source only if contact is closed. (e.g. used to test the frequency of UR). Setting of maximum startup time for the replacement source b
Options
BA controller. Communication option
Power supply
PB00856_SE
0 V 0 to 40 V 50/60 Hz 380 to 45 V 50/60 Hz and 440 V 60 Hz 0.35 Un y voltage y 0.7 Un 0.5 Un y voltage y 0.7 Un voltage u 0.85 Un
b b b
b b b
Operating thresholds
Undervoltage Phase failure Voltage presence b b b b b
IP degree of protection (EN 60529) and IK degree of protection against external mechanical impacts (EN 50102)
Front Side Connectors Front UA controller. IP40 IP30 IP0 IK07 b b b b b b b b
b b b AC DC Utilisation category (IEC 947-5-) AC AC3 AC4 AC5 DC DC3 Operational current (A) 4 V 8 7 5 5 8 48 V 8 7 5 5 0 V 8 6 4 4 0.6 0/40 V 8 6 4 3 50 V 0.4 380/45 V 5 440 V 4 660/690 V (1) For example, 220 V single-phase or 220 V three-phase. (2) The controller is powered by the ACP auxiliaries control plate. The same voltage must be used for the ACP plate, the IVE unit and the circuit-breaker operating mechanisms. If this voltage is the same as the source voltage, then the Normal and Replacement sources can be used directly for the power supply. If not, an isolation transformer must be used.
A-49
PB04383A50
The Masterpact NW range complies with the main standards and certifications:
b IEC 60947- and 60947- b IEC 6830 (damp heat) and IEC 685 severity level (salt mist) b IEC 60068--4 and IEC 60068--43 for corrosive environments: v SO2 : tested to IEC 60068-2-42 in a 3C4 environment as defined by IEC 607-3-3 v H2S: tested to IEC 60068-2-43 in a 3C3 environment as defined IEC 60721-3-3.
Maximum safety
The Masterpact NW range with corrosion protection offers the same safety features as the standard version: b positive contact indication b high impulse withstand voltage ( kV) b suitable for isolation in compliance with IEC 60947-, as indicated by the disconnector symbol on the front face: b Front face insulation class , allowing class installations with breaker control from outside.
A-50
Horizontal connection
4th pole rating Rated utlimate breaking capacity Rated service breaking capacity Break time (ms)
000 000 000 000 000 000 000 000 000 000 000 00 85 00 %
50 50 50 50 50 50 50 50 50 50 50 00 85 00 %
600 600 600 550 500 600 550 500 450 400 600 00 85 00 %
000 000 000 900 800 000 900 800 700 600 000 00 85 00 %
500 500 500 500 500 500 500 500 400 300 500 00 85 00 %
4000 4000 4000 4000 4000 4000 4000 4000 4000 3900 4000 00 85 00 %
H H
Drawout device
800 to 300 A 4000 A
L (mm)
3P 44 786 4P 556 06
H (mm)
439 479
P (mm)
395 395
Connection b Power circuits: v vertical rear connection v horizontal rear connection (except for 300 A) b Auxiliaries connected to terminal block on circuit breaker front face.
A-5
The Masterpact Earthing Switch can be racked into any compatible Masterpact NW chassis in place of a Masterpact circuit breaker. It is used to interconnect and earth the phase and neutral conductors of an electrical installation to ensure the safety of personnel during servicing. It can be locked in earthed position.
Main characteristics
Rated insulation voltage Rated operational voltage Rated current Latching capacity Rated short-time withstand current Compatibility Remote indication 000 V 690 V 800 to 4000 A 35 kA peak 60 kA/s 50 kA/3s Compatible with drawout NW08 to NW40 circuit breakers, types N/H/NA/HA, 3-pole and 4-pole rear connected versions ON/OFF indication contacts that can be used according to the chassis auxiliary wiring
PB0446A50
The Earthing Switch is compatible with Masterpact NW08 to NW40 type N1, H1, NA and HA circuit breakers in both 3-pole and 4-pole versions. It has two parts: b a chassis earthing kit for installation on the Masterpact NW chassis. Two different versions are available for 3-pole and 4-pole chassis. b the Earthing Switch itself, which is a specific Masterpact NW device that can be racked into any chassis equipped with an earthing kit, in place of the circuit breaker. Two versions are available (3-pole and 4-pole). An earthing kit must be installed on the chassis of each circuit breaker protecting a circuit that may require earthing while work is being carried out. However, a single earthing switch is often sufficient for an entire installation if only one circuit is to be serviced at any given time. The standard Earthing Switch comes with the short-circuit bar installed across the bottom (downstream) connections for earthing of the upstream portion of the circuit. The user can easily move the short-circuit bar to the top connections upstream if the downstream portion of the circuit needs to be earthed. Earthing kit (for chassis)
DB5557 DB5558
DB5559
DB5560
With short-circuit bar on the top connections. With short-circuit bar on the bottom connections.
DB556
A-5
Typical applications
The earthing switch is used to protect maintenance personnel working on an installation against the risk of accidental connection of a parallel source or energisation by reverse power. Protection is provided by earthing the part of the installation that is to be worked on.
Application n1
Earthing of one section of a coupled busbar arrangement
DB0865
When working on section B, the bus coupler is normally open. To protect personnel in the event of accidental closing of this device, an earthing switch with the upstream terminals earthed is installed in place of the circuit breaker at B. In this way section B will remain at earth potential under all circumstances and the personnel can work in complete safety.
Application n2
Earthing an outgoer
DB0866
When working on outgoer C, installation of an earthing switch with the upstream terminals earthed (in place of the circuit breaker at C) ensures complete safety even if all the other devices on the installation are closed.
Application n3
Earthing of an MV/LV transformer
DB0867
When working on an MV/LV transformer, upstream earthing is carried out by means of the usual medium voltage and high voltage procedures. Installation of an earthing switch with the downstream terminals earthed (in place of the circuit breaker at B) maintains the part of the installation between the upstream MV circuit breaker and the downstream LV circuit breaker at earth potential. In this way, the personnel can work in complete safety even if the rest of the installation is energised.
A-53
A-54
DB5563
A-55
TOOLS
schneider-electric.com CAD software and tools
This international site allows you to access all the Schneider Electric products in just clicks via comprehensive range datasheets, with direct links to: p complete library: technical documents, catalogs, FAQs, brochures p selection guides from the e-catalog. p product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, the list of country contacts
The CAD software and tools enhance productivity and safety. They help you create your installations by simplifying product choice through easy browsing in the Schneider Electric offers. Last but not least, they optimise use of our products while also complying with standards and proper procedures.
Masterpact
Installation recommendations
Operating conditions Installation in switchboard Door interlock catch Control wiring Power connection Recommended busbars drilling
Masterpact NT06 to NT6 Masterpact NW08 to NW63
Busbar sizing Temperature derating Power dissipation and input / output resistance Derating in switchboards Substitution kit
Fixed / drawout devices 800 to 300 A Dimensions and connection Electrical diagrams Additional characteristics Catalogue numbers and order form
B-4 B-5
B-
Installation recommendations
Operating conditions
Ambient temperature
Masterpact devices can operate under the following temperature conditions: b the electrical and mechanical characteristics are stipulated for an ambient temperature of -5 C to +70 C b circuit-breaker closing is guaranteed down to -35 C. Storage conditions are as follows: b -40 to +85 C for a Masterpact device without its control unit b -5 C to +85 C for the control unit.
DB04
Vibrations
Masterpact devices are guaranteed against electromagnetic or mechanical vibrations. Tests are carried out in compliance with standard IEC 60068--6 for the levels required by merchant-marine inspection organisations (Veritas, Lloyds, etc.): b to 3. Hz: amplitude mm b 3. to 00 Hz: constant acceleration 0.7 g. Excessive vibration may cause tripping, breaks in connections or damage to mechanical parts.
DB044
B-
Altitude
DB045
At altitudes higher than 2000 metres, the modifications in the ambient air (electrical resistance, cooling capacity) lower the following characteristics as follows:
Altitude (m) Dielectric resistance voltage (V) Average insulation level (V) Maximum utilisation voltage (V) Average thermal current (A) at 40 C 000 3500 000 690 x In 3000 350 900 590 0.99 x In 4000 500 700 50 0.96 x In 5000 00 600 460 0.94 x In
Electromagnetic disturbances
Masterpact devices are protected against: b overvoltages caused by devices that generate electromagnetic disturbances b overvoltages caused by atmospheric disturbances or by a distribution-system outage (e.g. failure of a lighting system) b devices emitting radio waves (radios, walkie-talkies, radar, etc.) b electrostatic discharges produced by users. Masterpact devices have successfully passed the electromagnetic-compatibility tests (EMC) defined by the following international standards: b IEC 60947-, appendix F b IEC 60947-, appendix B (trip units with earth-leakage function). The above tests guarantee that: b no nuisance tripping occurs b tripping times are respected.
DB046
B-3
Installation recommendations
Installation in switchboard
Possible positions
DB047 DB048 DB049 DB043
Power supply
Masterpact devices can be supplied either from the top or from the bottom without reduction in performance, in order to facilitate connection when installed in a switchboard.
DB0430
DB043
Mounting on rails.
DB0433
B-4
Partitions
Sufficient openings must be provided in partitions to ensure good air circulation around the circuit breaker; Any partition between upstream and downstream connections of the device must be made of nonmagnetic material. For high currents, of 500 A and upwards, the metal supports or barriers in the immediate vicinity of a conductor must be made of non-magnetic material A. Metal barriers through which a conductor passes must not form a magnetic loop.
DB0434
Busbars (NT)
For live busbars installed immediately above the circuit breaker (respecting the 00 mm safety clearance), the distance between bars must be 65 mm minimum. In a 000 V system, the bars must be insulated.
DB03879 DB0438
Interphase barrier
If the insulation distance between phases is not sufficient (y 4 mm), it is advised to install phase barriers (taking into account the safety clearances). Mandatory for a Masterpact NT > 500 V.
DB0435
B-5
Installation recommendations
Dimensions (mm)
Type NT08-6 (3P) NT08-6 (4P) NW08-40 (3P) NW08-40 (4P) NW40b-63 (3P) NW40b-63 (4P) (1) 35 05 5 330 660 775 (2) 68 68 5 5 5 5
(2) 3 03
Note: the door interlock can either be mounted on the right side or the left side of the breaker. : datum.
B-6
Control wiring
24 V DC power-supply module
External 24 V DC power-supply module for Micrologic (F1-, F2+) b do not connect the positive terminal (F+) to earth b the negative terminal (F-) can be connected to earth, except in IT systems b a number of Micrologic control units and M6C modules can be connected to the same 4 V DC power supply (the consumption of a Micrologic control unit or an M6C module is approximately 00 mA) b do not connect any devices other than a Micrologic control unit or an M6C module b the maximum length for each conductor is ten metres. For greater distances, it is advised to twist the supply wires together b the 4 V DC supply wires must cross the power cables perpendicularly. If this is difficult, it is advised to twist the supply wires together b the technical characteristics of the external 4 V DC power-supply module for Micrologic control units are indicated on page A-0 Communication bus b do not connect the positive terminal (E) to earth b the negative terminal (E) can be connected to earth b a number of device or chassis communication modules can be connected to the same 4 V DC power supply (the consumption of each module is approximately 30 mA) b the 4 V DC (E, E) power supply for the communication bus must be separate from the external 4 V DC power-supply module for Micrologic control units (F-, F+). E1 E2 E3 E4 E5 E6 B/Tx+ A/RxB/Rx+ + A/TxTo create a two-wire Modbus communication bus, simply connect Tx- with Rx- and Tx+ with Rx+. To connect a Modbus slave (Micrologic) to a Modbus master (PLC), connect: the slave Tx- to the master Rxthe slave Rx- to the master Tx+ + the slave Tx to the master Rx the slave Rx+ to the master Tx+.
Wiring of ZSI: it is recommended to use twisted shielded cable. The shield must be connected to earth at both ends. B-7
Installation recommendations
Power connection
Cables connections
If cables are used for the power connections, make sure that they do not apply excessive mechanical forces to the circuit breaker terminals. For this, make the connections as follows: b extend the circuit breaker terminals using short bars designed and installed according to the recommendations for bar-type power connections: v for a single cable, use solution B opposite v for multiple cables, use solution C opposite b in all cases, follow the general rules for connections to busbars: v position the cable lugs before inserting the bolts v the cables should firmly secured to the framework E.
DB0448 DB0449
Busbars connections
The busbars should be suitably adjusted to ensure that the connection points are positioned on the terminals before the bolts are inserted B The connections are held by the support which is solidly fixed to the framework of the switchboard, such that the circuit breaker terminals do not have to support its weight C. (This support should be placed close to the terminals).
DB045 DB045
DB0453
DB0450
Electrodynamic stresses The first busbar support or spacer shall be situated within a maximum distance from the connection point of the breaker (see table below). This distance must be respected so that the connection can withstand the electrodynamic stresses between phases in the event of a short circuit.
Maximum distance A between busbar to circuit breaker connection and the first busbar support or spacer with respect to the value of the prospective short-circuit current. Isc (kA) Distance A (mm) 30 350 50 300 65 50 80 50 00 50 50 50
B-8
Clamping
Correct clamping of busbars depends amongst other things, on the tightening torques used for the nuts and bolts. Over-tightening may have the same consequences as under-tightening. For connecting busbars (Cu ETP-NFA5-00) to the circuit breaker, the tightening torques to be used are shown in the table below. These values are for use with copper busbars and steel nuts and bolts, class 8.8. The same torques can be used with AGS-T5 quality aluminium bars (French standard NFA 0-04 or American National Standard H-35-). Examples
DB0455 DB0456 DB0457 DB0454
1 2 3 4 5 6
Terminal screw factory-tightened to 16 Nm (NW), 13 Nm (NT). Breaker terminal. Busbar. Bolt. Washer. Nut.
Isolation distance
DB046
Dimensions (mm)
Ui 600 V 000 V X min 8 mm 4 mm
Busbar bending When bending busbars maintain the radius indicated below(a smaller radius would cause cracks).
DB046
Dimensions (mm)
e 5 0 Radius of curvature r Min 5 5 Recommended 7.5 8 to 0
B-9
Installation recommendations
Rear connection
DB0463 DB0463
DB0466
DB0467
DB0480
DB0468
DB047
Front connection
DB0463 DB0463
Top connection
Bottom connection
DB0483
DB048
B-0
DB048
DB0469
NW40b to NW50
DB0473
DB0474
DB0477
Top connection
Bottom connection
DB0478
DB0479
DB0475
B-
Installation recommendations
Busbar sizing
Basis of tables: b maximum permissible busbars temperature: 00 C b Ti: temperature around the circuit breaker and its connection b busbar material is unpainted copper.
Masterpact
b.30 x 0 b.30 x 5 b.30 x 0 b.40 x 5 b.40 x 0 b.40 x 0 b.50 x 5 b.50 x 0 b.50 x 0 3b.50 x 5 b.50 x 0 b.63 x 0 3b.50 x 5 b.50 x 0 b.40 x 0 b.40 x 0 b.80 x 5 b.40 x 0 3b.63 x 5 b.50 x 0 NT6 ou NW6 400 3b.80 x 5 b.63 x 0 NT6 ou NW6 600 b.63 x 0 3b.80 x 5 b.63 x 0 NW0 800 b.63 x 0 NW0 000 b.80 x 0 3b.00 x 5 b.80 x 0 NW5 00 b.80 x 0 4b.00 x 5 b.80 x 0 b.00 x 0 NW5 500 4b.00 x 5 b.00 x 0 NW3 800 3b.80 x 0 4b.00 x 5 3b.80 x 0 3b.80 x 0 6b.00 x 5 3b.00 x 0 NW3 3000 NW3 300 3b.00 x 0 8b.00 x 5 3b.00 x 0 NW40 3800 4b.00 x 0 5b.00 x 0 NW40 4000 5b.00 x 0 5b.00 x 0 NW50 4500 6b.00 x 0 6b.00 x 0 NW50 5000 7b.00 x 0 7b.00 x 0 With Masterpact NT, it is recommanded to use 50 mm wideness bars (see Recommended busbars drilling).
Example
Conditions: b drawout version b horizontal busbars b Ti: 50 C b service current: 800 A. Solution: For Ti = 50 C, use an NW0 which can be connected with three 80 x 5 mm bars or two 63 x 0 mm bars.
Note: the values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test.
B-
Basis of tables: b maximum permissible busbars temperature: 00 C b Ti: temperature around the circuit breaker and its connection b busbar material is unpainted copper.
Masterpact
NT06 NT06 NT08 ou NW08 NT0 ou NW0 NT ou NW NT6 ou NW6 NT6 ou NW6 NW0 NW0 NW5 NW5 NW3 NW3 NW3 NW40 NW40 NW50 NW50 NW63 NW63
Example
Conditions: b drawout version b vertical connections b Ti: 40 C b service current: 00 A. Solution : For Ti = 40 C use an NT or NW which can be connected with two 63 x 5 mm bars or with one 63 x 0 mm bar.
Note: the values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test.
B-3
Installation recommendations
Temperature derating
The table below indicates the maximum current rating, for each connection type, as a function of Ti around the circuit breaker and the busbars. Circuit breakers with mixed connections have the same derating as horizontally connected breakers. For Ti greater than 60 C, consult us. Ti: temperature around the circuit breaker and its connection.
Version Connection Temp. Ti NT06 H/H/L NT08 H/H/L NT0 H/H/L NT H/H NT6 H/H NW08 N/H/L NW0 N/H/L NW N/H/L NW6 N/H/L NW0 H/H/H3 NW0 L NW5 H/H/H3 NW3 H/H/H3 NW40 H/H/H3 NW40b H/H NW50 H/H NW63 H/H Drawout Front or rear horizontal 40 45 50 55 630 800 000 50 600 800 000 50 600 000 000 500 300 4000 4000 5000 Fixed Front or rear horizontal 40 45 50 55 630 800 000 50 600 800 000 50 600 000 500 300 4000 4000 5000
60
Rear vertical 40 45 50 630 800 000 50 600 800 000 50 600 000 000 500 300 4000 4000 5000 6300
55
60
60
Rear vertical 40 45 50 630 800 000 50 600 800 000 50 600 000 500 300 4000 4000 5000 6300
55
60
560 50
550
980 890 900 850 800 300 3000 900 3900 3750 3650
90
3850
3900 3800
600
B-4
Derating in switchboards
Basis of tables
b switchboard dimensions b number of circuit-breakers installed b type of breaker connections b drawout versions b ambient temperature outside of the switchboard: Ta (IEC 60439-).
Masterpact NT06-16 H1/H2/L1 (switchboard 000 x 400 x 400) - area of outlet vents: 50 cm
Type
Switchboard composition 4 3 2 1 Connection type Busbar dimensions (mm) Ventilated switchboard ( IP31)
DB08437
NT06 H1/H2/L1
NT08 H1/H2/L1
NT10 H1/H2/L1
NT12 H1/H2
NT16 H1/H2
b. 50 x 5
3b. 63 x 5 3b. 50 x 5
630
800
800
50
50
Ta = 35 C
Ta = 45 C
630
800
800
000/950
000/000
50
50
330
440
Ta = 55 C
630
800
800
000/890
000/960
00
50
50
340
(1) Area of outlet vents: 150 cm. (2) Area of intlet vents: 150 cm. Non ventilated switchboard 4 ( IP54) 3 630 Ta = 35 C 2 1 4 3 630 Ta = 45 C 2 1 4 3 630 Ta = 55 C 2 1
630
800
800
000/960
000/000
50
50
330
400
DB0495
630
800
800
000/90
000/980
0
50
60
330
630
800
800
000/860
000/930
50
30
00
60
Note: the values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. The values indicated for the cross-sectional area of the vents should be considered as general indications only given that the thermal performance of a switchboard with natural ventilation depends on many parameters, e.g. shape, porosity and location of vents and air flow within the switchboard.
B-5
Installation recommendations
Derating in switchboards
Masterpact NT06-08 H1/H2/L1 (switchboard 300 x 00 x 500) - area of outlet vents: 300 cm
Type
Switchboard composition 5 4 3 2 1 Connection type Busbar dimensions (mm) Ventilated switchboard ( IP31)
DB08444
NT06 H1/H2/L1
NT08 H1/H2/L1
b. 40 x 5 5 4 3 2 630 1 5 4 3 2 630 1 5 4 3 2 630 1 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630
b. 50 x 5 800 800 800 800 800 800 800 800 800 800 800 800
Ta = 35 C
630
630 630
800
800
800 800
Ta = 45 C
630
630 630
800
800
800 800
Ta = 55 C
630
630 630
800
800
800 800
(1) Area of outlet vents: 300 cm. (2) Area of intlet vents: 300 cm. Non ventilated switchboard ( IP54) Ta = 35 C
DB0489
Ta = 45 C
Ta = 55 C
630
630 630
630 630 630 630 630 630 630 630 630 630 630 630
630
630 630
630
630 630
630 630 630 630 630 630 630 630 630 630 630 630 630 630 630
800
800
800 800
800 800 800 800 800 800 800 800 800 800 800 800
800
800
800 800
800
800
800 800
Note: the values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. The values indicated for the cross-sectional area of the vents should be considered as general indications only given that the thermal performance of a switchboard with natural ventilation depends on many parameters, e.g. shape, porosity and location of vents and air flow within the switchboard.
B-6
Masterpact NT10-16 H1/H2/L1 (switchboard 300 x 00 x 500) - area of outlet vents: 300 cm
Type
Switchboard composition 5 4 3 2 1 Connection type Busbar dimensions (mm) Ventilated switchboard ( IP31)
DB08444
NT10 H1/H2/L1
NT12 H1/H2
NT16 H1/H2
3b. 63 x 5 3b. 50 x 5
50 50 50
3b. 80 x 5 3b. 63 x 5
Ta = 35 C
50
50
50 50
460
600
500 550
Ta = 45 C
50
50
50 50
400
500
40 480
Ta = 55 C
000 /90 000 /950 000 /930 000 /900 000/000 000 /970 000 /950
50
50
50 50
300
400
330 370
(1) Area of outlet vents: 300 cm. (2) Area of intlet vents: 300 cm. Non ventilated switchboard ( IP54) Ta = 35 C
DB0489
Ta = 45 C
Ta = 55 C
5 4 000 /950 000/000 000 /960 3 2 000/000000/000000/000 000 /970 5 000 /900 4 3 000 /950 000 /90 2 000 /950 000/000 000 /960 000 /930 5 4 000 /850 3 000 /900 000 /860 2 000 /880 000 /970 000 /90 000 /870
50
50
50 50
400
500
370 400
50
50
50 50
350
430
300 30
0
50
00 0
50
350
0 50
Note: the values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. The values indicated for the cross-sectional area of the vents should be considered as general indications only given that the thermal performance of a switchboard with natural ventilation depends on many parameters, e.g. shape, porosity and location of vents and air flow within the switchboard.
B-7
Installation recommendations
Derating in switchboards
Masterpact NW08-10 N/H/L (switchboard 300 x 800 x 900) - area of outlet vents: 350 cm
Type
Switchboard composition 4 3 2 1 Connection type Busbar dimensions (mm) Ventilated switchboard ( IP31)
DB08438
NW08 N/H/L
NW10 N/H/L
b. 50 x 5 4 3 2 1 800 4 3 2 1 800 4 3 2 1 800 800 800 800 800 800 800 800 800 800 800 800 800
3b. 63 x 5 b. 63 x 5 800 800 800 800 800 800 800 800 800 000 000 000 000 000 000 000 000 000
Ta = 35 C
800
800 800
000
000
000 000
Ta = 45 C
800
800 800
000
000
000 000
Ta = 55 C
800
800 800
000
000
000 000
(1) Area of outlet vents: 350 cm. (2) Area of intlet vents: 350 cm. Non ventilated switchboard ( IP54)
DB049
Ta = 35 C
Ta = 45 C
Ta = 55 C
800
800 800
800
800 800
800
800 800
800 800 800 800 800 800 800 800 800 800 800 800
000
000
000 000
000
000
000 000
000
000
000 000
Note: the values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. The values indicated for the cross-sectional area of the vents should be considered as general indications only given that the thermal performance of a switchboard with natural ventilation depends on many parameters, e.g. shape, porosity and location of vents and air flow within the switchboard.
B-8
Masterpact NW12-16 N/H/L (switchboard 300 x 800 x 900) - area of outlet vents: 350 cm
Type
Switchboard composition 4 3 2 1 Connection type Busbar dimensions (mm) Ventilated switchboard ( IP31)
DB08438
NW12 N1
NW12 H/L
NW16 N1
NW16 H/L
3b. 63 x 5 3b. 50 x 5 4 3 2 1 50 4 3 2 1 50 4 3 2 1 50 50 50 50 50 50 50 50 50 50
3b. 63 x 5 3b. 50 x 5 50 50 50 50 50 50 50 50 50
3b. 80 x 5 3b. 63 x 5
3b. 80 x 5 3b. 63 x 5
Ta = 35 C
50
50 50
50
50
50 50
550
600
600 600
600
600
600 600
Ta = 45 C
50
50 50
50
50
50 50
470
600
500 600
600
600
600 600
Ta = 55 C
50
50 50
50
50
50 50
380
500
380 500
50
600
470 600
(1) Area of outlet vents: 350 cm. (2) Area of intlet vents: 350 cm. Non ventilated switchboard ( IP54)
DB049
Ta = 35 C
Ta = 45 C
Ta = 55 C
50
50 50
50
50
50 50
440
550
45 550
600
600
600 600
50
0 50
50
50
50 50
360
470
360 470
500
600
500 600
00
40 00
50
50
50 50
80
380
80 380
400
50
400 50
Note: the values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. The values indicated for the cross-sectional area of the vents should be considered as general indications only given that the thermal performance of a switchboard with natural ventilation depends on many parameters, e.g. shape, porosity and location of vents and air flow within the switchboard.
B-9
Installation recommendations
Derating in switchboards
Masterpact NW20-40 N/H/L (switchboard 300 x 800 x 900) - area of outlet vents: 350 cm
Type
Switchboard composition 4 3 2 1 Connection type Busbar dimensions (mm) Ventilated switchboard ( IP31)
DB08438
NW20 H1/H2/H3
NW20 L1
NW25 H1/2/3
NW32 H1/2/3
NW40 H1/2/3
Ta = 35 C
Ta = 45 C
Ta = 55 C
4b. 00 x 5
3b. 00 x 0
4b. 00 x 0
000
000
375
500
3040
300
330
3700
000 000
80
960
750 90
50
380
880
300
360
3500
000 000
700
850
640 800
00
50
690
900
960
380
(1) Area of outlet vents: 350 cm. (2) Area of intlet vents: 350 cm. Non ventilated switchboard ( IP54)
DB049
Ta = 35 C
Ta = 45 C
Ta = 55 C
000
000 000
800
900
750 890
5
75
650
850
3040
330
960
900 960
680
80
660 800
000
50
550
700
880
30
90
780 90
590
700
550 700
900
00
370
530
70
960
Note: the values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. The values indicated for the cross-sectional area of the vents should be considered as general indications only given that the thermal performance of a switchboard with natural ventilation depends on many parameters, e.g. shape, porosity and location of vents and air flow within the switchboard.
B-0
Masterpact NW40b-63 H1/H2 (switchboard 2300 x 1400 x 1500) - area of outlet vents: 500 cm
Type NW40b H1/H2 NW50 H1/H2 NW63 H1/H2
Switchboard composition 4 3 2 1 Connection type Busbar dimensions (mm) Ventilated switchboard ( IP31) Ta = 35 C 5b. 100 x 10 4 3 2 4000 4000 1 4 3 2 4000 4000 1 4 3 2 4000 4000 1 7b. 100 x 10 8b. 100 x 10
4700
5000
5850
DB108445
Ta = 45 C
4450
4850
5670
Ta = 55 C
4200
4600
5350
(1) Area of outlet vents: 500 cm. (2) Area of intlet vents: 500 cm. Non ventilated switchboard ( IP54) Ta = 35 C
DB101492
Ta = 45 C
Ta = 55 C
4000
4350
4650
5290
4000
4100
4400
5040
3840
3850
4150
4730
Note: the values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. The values indicated for the cross-sectional area of the vents should be considered as general indications only given that the thermal performance of a switchboard with natural ventilation depends on many parameters, e.g. shape, porosity and location of vents and air flow within the switchboard.
B-21
Installation recommendations
Substitution kit
It is possible to replace a Masterpact (M08 to M32) with a new Masterpact (NW08 to NW32) with the same power rating. Substitution is possible for the following types of circuit breakers: b N1, H1, H2 for both fixed and drawout versions b L for drawout versions up to 000 A.
Mounting diagram
Fixed version Drawout version
DB7050
: Masterpact NW : Masterpact M
Fixing points are identical for Masterpact (M08 to M32) and Masterpact (NW08 to NW32), except for the four-pole chassis.
Door cut-out
b without an escutcheon, the cut-out is identical (70 x 35 mm) b with the former escutcheon, the cut-out is identical (70 x 35 mm) b with the new escutcheon, the cut-out is different. Drawout version
Fixed version
DB7048
Power connection
Select a set of retrofit connectors to replace the standard connectors and avoid any modifications to the busbars (see the retrofit section in orders and quotations).
Note: (1) Without escutcheon. (2) With escutcheon. References X and Y represent the symmetry planes for threepole devices.
B-
DB7047
DB7049
Electrical diagrams
Correspondences between Masterpact NW and Masterpact M terminal blocks. Power Control unit Remote operation
DB705
Indication contacts
Chassis contacts
DB705
Different than Masterpact M. (1) The current transformer for the external neutral must be replaced.
B-3
TOOLS
schneider-electric.com Training
This international site allows you to access all the Schneider Electric products in just clicks via comprehensive range datasheets, with direct links to: p complete library: technical documents, catalogs, FAQs, brochures p selection guides from the e-catalog. p product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, the list of country contacts
Training allows you to acquire the Schneider Electric expertise (installation design, work with power on, etc.) for increased efficiency and a guarantee of improved customer service. The training catalogue includes beginners courses in electrical distribution, knowledge of MV and LV switchgear, operation and maintenance of installations, design of LV installations to give but a few examples.
Masterpact
1 A-1 B-1
C-
Dimensions
DB088 DB089
Safety clearances
DB093 DB094 DB095
Door cutout
DB789
For 1000 V
Parts Insulated 0 0 Metal 00 50 Energised 500 (3) 00 (3)
A B
A B
(3) With a minimum distance between bars of 65 mm (A and B) if the bars are not insulated. Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 50 mm is required to remove the arc chutes. An overhead clearance of 20 mm is required to remove the terminal block.
C-
Connections
Horizontal rear connection
DB097 DB098 DB099 DB000
Detail
Detail
o
View A detail.
Front connection
DB005 DB006
Detail
Top connection
DB008
Bottom connection
View A detail.
Note: recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.
C-3
Connections
Front connection with spreaders
DB00 DB0 DB057 DB058
Detail
Detail
DB07
View A detail.
: datum.
C-4
Connections
Front connection via vertical connection adapters
DB0 DB03 DB03 DB05
Detail
View A detail.
Front connection via vertical connection adapters fitted with cable-lug adapters
DB06 DB07 DB033 DB09
Detail
View A detail.
Note: recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.
C-5
Dimensions
DB034 DB035
Safety clearances
DB056 DB039 DB040
Door cutout
DB04
A B C
C-6
Connections
Horizontal rear connection
DB04 DB043 DB044 DB000
Detail
Detail
View A detail.
Front connection
DB05 DB05 DB054
Detail
Top connection
DB055
Bottom connection
View A detail. Note: recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.
C-7
Connections
Front connection with spreaders
DB057 DB058 DB065
DB066
View A detail.
: datum.
C-8
Connections
Front connection via vertical connection adapters fitted with cable-lug adapters
DB06 DB06 DB064 DB09
View A detail.
Note: recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.
C-9
Dimensions
DB067 DB068
Mounting detail
Safety clearances
DB07 DB07 DB073
Insulated parts
A B 0 0 : datum.
Metal parts
0 0
Energised parts
00 60 (1) Without escutcheon. (2) With escutcheon. Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 50 mm is required to remove the arc chutes. An overhead clearance of 20 mm is required to remove the terminal block.
C-0
Connections
Horizontal rear connection
DB074 DB076 DB077 DB078
Detail
Detail
View A detail.
Front connection
DB083 DB084 DB088
Detail
Top connection
DB086
Bottom connection
View A detail.
Note: recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.
C-
Dimensions
DB089 DB090
Mounting detail
Safety clearances
DB093 DB094 DB095
Door cutout
Insulated parts
A B 0 0 : datum.
Metal parts
0 0
Energised parts
0 60 (1) Without escutcheon. (2) With escutcheon. Note: X and Y are the symmetry planes for a 3-pole device.
C-
Connections
Horizontal rear connection
DB096 DB097 DB098 DB078
Detail
Detail
View A detail.
Front connection
DB0303 DB0304 DB0308
Detail
Top connection
DB0306
Bottom connection
View A detail. Note: recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.
C-3
Dimensions
DB067 DB068
Mounting detail
Safety clearances
DB07 DB07 DB073
Door cutout
Insulated parts
A B 0 0 : datum.
Metal parts
0 0
Energised parts
00 60 (1) Without escutcheon. (2) With escutcheon. Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 110 mm is required to remove the arc chutes. An overhead clearance of 20 mm is required to remove the terminal block.
C-4
Connections
Horizontal rear connection
DB0309 DB076
Detail
DB030 DB03
Detail
DB087 DB034
Note: recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.
DB035
C-5
Dimensions
DB089 DB090
Mounting detail
Safety clearances
DB093 DB094 DB095
Door cutout
Insulated parts
A B : datum. 0 0
Metal parts
0 0
Energised parts
0 60 (1) Without escutcheon. (2) With escutcheon. Note: X and Y are the symmetry planes for a 3-pole device. The safety clearances take into account the space required to remove the arc chutes.
C-6
Connections
Horizontal rear connection
DB036 DB097
Detail
DB037 DB03 DB034 DB035
View A detail.
Detail
DB0307
Note: recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.
C-7
Dimensions
DB067 DB030
Mounting detail
Safety clearances
DB07 DB033 DB03
Door cutout
Insulated parts
A B 0 0 : datum.
Metal parts
0 0
Energised parts
00 60 (1) Without escutcheon. (2) With escutcheon. Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 110 mm is required to remove the arc chutes. An overhead clearance of 20 mm is required to remove the terminal block.
C-8
Connections
Horizontal rear connection (NW40b - NW50)
DB033 DB034 DB035 DB078
Detail
Detail
View A detail.
Detail
Note: recommended connection screws: M10 s/s class A4 80. Tightening torque: 50 Nm with contact washer.
View A detail.
C-9
Dimensions
DB0334 DB0335
Mounting detail
Safety clearances
DB093 DB0338 DB0339
Door cutout
Insulated parts
A B 0 0
Metal parts
0 0
Energised parts
0 60
(1) Without escutcheon. (2) With escutcheon. Note: X and Y are the symmetry planes for a 3-pole device. : datum.
C-0
Connections
Horizontal rear connection (NW40b - NW50)
DB034 DB034 DB0343 DB078
Detail
Detail
DB08
View A detail.
Detail
DB034
View A detail. Note: recommended connection screws: M10 s/s class A4 80. Tightening torque: 50 Nm with contact washer.
C-
NT/NW accessories
Detail
View A detail.
Detail
Note: recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer. : datum.
View A detail.
C-
DB125695
DB101361
Escutcheon
Masterpact NT Fixed device Drawout device
DB101363
DB101365
: datum.
DB101366
DB101364
DB101362
DB101360
Drawout device
C-23
C-4
BatiBUS
C-5
C-6
Busbars
Window (mm) Weight (kg)
I y 1600 A
80 x 5 4
I y 3200
470 x 60 8
Busbars path
280 x 115 window Busbars spaced 70 mm centre-to-centre
DB0393 DB709
C-7
TOOLS
schneider-electric.com The electrical installation guide
According to IEC 60364 This guide, part of the Schneider Electric offer, is the essential tool to "guide" you any time in your business: p design office, consultant p contractor, panelbuilder p teacher, trainer. Comprehensive and concrete information on: p all the new technical solutions p all the components p of an installation from a global point of view p all the IEC standards modifications p all the fundamental electrotechnical knowledge p all the design stages, from medium to low voltage.
This international site allows you to access all the Schneider Electric products in just clicks via comprehensive range datasheets, with direct links to: p complete library: technical documents, catalogs, FAQs, brochures p selection guides from the e-catalog. p product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, the list of country contacts
Masterpact
Electrical diagrams
Masterpact NT and NW
Communications of the 4 V DC External power supply AD module Communications option 4 V DC external power supply Earth-fault and earth-leakage protection - Neutral protection Zone selective interlocking Additional characteristics Catalogue numbers and order form D-6 D-6 D-8 D-0 E-1 F-1
D-
Electrical diagrams
The diagram is shown with circuits de-energised, all devices open, connected and charged and relays in normal position. Power
DB040
Control unit
Remote operation
Control unit
Terminal block marking Com
E5 E6 E3 E4 E E
Remote operation
UC2 UC3
F+ VN F
UC1
SDE2 /
84 8 8 / /
Res
K
SDE1
84 8
MN
D
/ MX2
/ C
MX1
C C3
XF
A A3 A
PF
54 5 5
MCH
B B3 B
Z5 M M M3 Z3 Z4 Z Z T3 T4 T T
K
8
D
C
C
A
b b
P
b b
H
b b
Control unit Com : E-E6 communication UC1 : Z-Z5 zone selective interlocking Z = ZSI OUT SOURCE Z = ZSI OUT ; Z3 = ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault) M = Vigi module input (Micrologic 7) UC2 : T, T, T3, T4 = external neutral M, M3 = Vigi module input (Micrologic 7) UC3 : F+, F external 4 V DC power supply VN external voltage connector (must be connected to the neutral with a 3P circuit breaker) UC4 : External Voltage Connector (PTE option)
or
Remote operation SDE2 : fault-trip indication contact or Res : remote reset SDE1 : fault-trip indication contact (supplied as standard) MN : undervoltage release or MX2 : shunt release MX1 : shunt release (standard or communicating) XF : PF : closing release (standard or communicating) ready-to-close contact
b b b b
b b b b b
b b b b b
b b
b b
M6C : 6 programmable contacts to be connected to the external module M6C) ext. 4 V DC power supply required.
D-
Electrical diagrams
Indication contacts
DB0406 DB0407
Chassis contacts
Indication contacts
OF4
44 4 4
Chassis contacts
OF1
4
OF3
34 3 3
OF2
4
CD2
84 8 8
CD1
84 8 8
CE3
334 33 33
CE2
34 3 3
CE1
34 3 3
CT1
94 9 9
Chassis contacts
CD2 : disconnected CD1 position contacts CE3 : CE2 CE1 connected position contacts CT1 : test position contacts
DB7043
Key: drawout device only. XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard. interconnected connections (only one wire per connection point).
D-3
Electrical diagrams
The diagram is shown with circuits de-energised, all devices open, connected and charged and relays in normal position. Power
DB040
Control unit
Remote operation
Control unit
Terminal block marking Com
E5 E6 E3 E4 E E
Remote operation
UC2 UC3
F+ VN F
UC1
UC4
V3 V V
M2C / M6C
484 474 47 / / / Q3 Q Q
SDE2 /
84 8 8 / /
Res
K
SDE1
84 8
MN
D
/ MX2
/ C
MX1
C C3
XF
A A3 A
PF
54 5 5
MCH
B B3 B
Z5 M M M3 Z3 Z4 Z Z T3 T4 T T
K
8
D
C
C
A
b b
P
b b
H
b b
Control unit Com : E-E6 communication UC1 : Z-Z5 zone selective interlocking Z = ZSI OUT SOURCE Z = ZSI OUT ; Z3 = ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault) M = Vigi module input (Micrologic 7) UC2 : T, T, T3, T4 = external neutral M, M3 = Vigi module input (Micrologic 7) UC3 : F+, F external 4 V DC power supply
Remote operation SDE2 : fault-trip indication contact or Res : remote reset SDE1 : fault-trip indication contact (supplied as standard) MN : undervoltage release or MX2 : shunt release MX1 : shunt release (standard or communicating) closing release (standard or communicating) ready-to-close contact
b b b b
b b b b b
b b b b b
XF : VN external voltage connector (must be connected to the neutral with a 3P circuit breaker) PF :
b b
b b
UC4 : External Voltage Connector (PTE option) M2C : programmable contacts (internal relay) ext. 4 V DC power supply required
or
M6C : 6 programmable contacts (to be connected to the external module M6C) ext. 4 V DC power supply required
D-4
Electrical diagrams
Indication contacts
DB0409
Chassis contacts
Indication contacts
OF4 44 4 4 OF3 34 3 3 OF2 4 OF1 4 44 4 4 34 3 3 4 4 44 4 4 34 3 3 4 4
Chassis contacts
CD3 834 83 83 CE6 48 46 45 38 36 35 8 6 5 8 6 5 48 46 45 38 36 35 8 6 5 8 6 5 364 36 36 CD2 84 8 8 CD1 84 8 8 CE4 344 34 34 CE3 334 33 33 CE2 34 3 3 CE1 34 3 3 CT3 934 93 93 CE9 394 39 39 CT2 94 9 9 CT1 94 9 9 CE7 374 37 37
or
or
or
or
or
or
or
or
or
CE5 354 35 35
or
CE8 384 38 38
Indication contacts
OF4 : OF3 OF2 OF1 ON/OFF indication contacts OF24 or EF24 OF23 or EF23 OF22 or EF22 OF21 or EF21 OF14 or EF14 OF13 or EF13 OF12 or EF12 OF11 or EF11 Combined connected-deconnected indication contacts
Chassis contacts
CD3 CD2 CD1 or CE6 CE5 CE4 disconnected CE3 position CE2 contacts CE1 connected position contacts connected position contacts CT3 CT2 CT1 or CE9 CE8 CE7 or CD6 CD5 CD4 test position contacts
Key: drawout device only. XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard. interconnected connections (only one wire per connection point).
D-5
Electrical diagrams
Masterpact NT and NW
MC, M6C programmable contacts option Yes Yes Protection function No No No (2) Display function No (1) Time-stamping function No No Circuit-breaker status indications No No and control via communications bus Identification, settings, operation No (1) No (2) and maintenance aids via communications bus (1) Except for Micrologic A control units (if current < 20 % In). (2) Except for Micrologic A control units. (3) Time setting is manual and can be carried out automatically by the supervisor via the communications bus.
DB790
Note: In case of using the 24 V DC external power supply (AD module), maximum cable length between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed 10 meters. The BAT battery module, mounted in series upstream of the AD module, ensures an uninterrupted supply of power if the AD module power supply fails. The voltage measurement inputs are standard equipment on the downstream connectors of the circuit breaker. External connections are possible using the PTE external voltage measurement input option. With this option, the internal voltage measurement inputs are disconnected and terminals VN, V1, V2, V3 are connected only to the control unit (Micrologic P and H only). The PTE option is required for voltages less than 220 V and greater than 690 V (in which case a voltage transformer is compulsory). For three-pole devices, the system is supplied with terminal VN connected only to the control unit (Micrologic P and H). When the PTE option is implemented, the voltage measurement input must be protected against short-circuits. Installed as close as possible to the busbars, this protection function is ensured by a P25M circuit breaker (1 A rating) with an auxiliary contact (cat. no. 21104 and 21117). This voltage measurement input is reserved exclusively for the control unit and must not ever be used to supply other circuits outside the switchboard.
D-6
Electrical diagrams
Masterpact NT and NW
Wiring diagrams
DB4653 DB4530
Power supply wiring for Micrologic trip unit and M6C module.
Connection
The maximum length for each conductor supplying power to the trip unit or M6C module is 0 m. Do not ground F2+, F1-, or power supply output: b the positive terminal (F+) on the trip unit must not be connected to earth ground b the negative terminal (F-) on the trip unit must not be connected to earth ground b the output terminals (- and +) of the 4 V DC power supply must not be grounded. Reduce electromagnetic interference: b the input and output wires of the 4 V DC power supply must be physically separated as much as possible b if the 4 V DC power supply wires cross power cables, they must cross perpendicularly. If this is not physically possible, the power supply conductors must be twisted together b Power supply conductors must be cut to length. Do not loop excess conductor. Use only one 24 V DC power supply for each Micrologic trip unit. Connect external 24 V DC power supply only per the following wiring diagrams.
D-7
Electrical diagrams
Masterpact NT and NW
DB047
(1) Drawout device equipped with Modbus chassis COM. (2) Drawout device equipped with Digipact chassis COM.
D-8
Electrical diagrams
Masterpact NT and NW
Communicating switchboard
This configuration provides remote display and control of Masterpact equipped with the Modbus module.
DB5568
D-9
Electrical diagrams
Masterpact NT and NW
Shield Drain
D-0
Electrical diagrams
Masterpact NT and NW
Connection of the rectangular-sensor secondary circuit Use the cable shipped with the rectangular sensor.
Neutral protection
b three pole circuit breaker: v neutral protection is impossible with Micrologic A v Masterpact equipped with Micrologic P or H v the current transformer for external neutral is necessary (the wiring diagram is identical to the one used for the residual earth-fault protection) b four pole circuit breaker: v Masterpact equipped with Micrologic A, P or H v the current transformer for external neutral is not necessary.
Note: the maximum permissible distance between two devices is 3000 m. A downstream circuit breaker can control up to ten upstream circuit breakers.
D-
TOOLS
schneider-electric.com The technical guide
This international site allows you to access all the Schneider Electric products in just clicks via comprehensive range datasheets, with direct links to: p complete library: technical documents, catalogs, FAQs, brochures p selection guides from the e-catalog. p product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, the list of country contacts
These technical guides help you comply with installation standards and rules i.e.: the electrical installation guide, the protection guide, the switchboard implementation guide, the technical booklets and the co-ordination tables all form genuine reference tools for the design of high performance electrical installations. For example, the LV protection co-ordination guide - discrimination and cascading - optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations.
Masterpact
Additional characteristics
Presentation Functions and characteristics Installation recommendations Dimensions and connection Electrical diagrams
Contents
E-
Additional characteristics
Tripping curves
Micrologic 2.0
DB05
E-
(1)
Ig = In x...
Ig < 400 A 400 A y Ig y 00 A Ig > 00 A
A
0.3 0. 500
B
0.3 0.3 640
C
0.4 0.4 70
D
0.5 0.5 800
E
0.6 0.6 880
F
0.7 0.7 960
G
0.8 0.8 040
H
0.9 0.9 0
I
00
E-3
Additional characteristics
Limitation curves
Current limiting
Voltage 380/415/440 V AC
Limited short-circuit current (k peak)
DB055
Voltage 660/690 V AC
Limited short-circuit current (k peak)
DB056
E-4
Energy limiting
Voltage 380/415/440 V AC
Limited energy
DB053
Voltage 660/690 V AC
Limited energy
DB054
E-5
TOOLS
schneider-electric.com CAD software and tools
This international site allows you to access all the Schneider Electric products in just clicks via comprehensive range datasheets, with direct links to: p complete library: technical documents, catalogs, FAQs, brochures p selection guides from the e-catalog. p product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, the list of country contacts
The CAD software and tools enhance productivity and safety. They help you create your installations by simplifying product choice through easy browsing in the Schneider Electric offers. Last but not least, they optimise use of our products while also complying with standards and proper procedures.
Masterpact
Presentation Functions and characteristics Installation recommendations Dimensions and connection Electrical diagrams Additional characteristics
3 A-1 B-1 C-1 D-1 E-1 F-2 F-2 F-3 F-4 F-4 F-5 F-6 F-7 F-8 F-9 F-10 F-11 F-12
Masterpact NT
Connection Remote operation
Micrologic control unit, communication option Chassis locking and accessories Clusters Circuit breaker locking and accessories Mechanical interlocking for source changeover Indication contacts Instructions
F-13 F-14 F-14 F-15 F-16 F-17 F-18 F-19 F-20 F-21 F-22
Portable data acquisition Communication bus accessories and Modbus Masterpact NT and NW order form
F-23 F-24
F-1
Catalogue numbers
To replace a Masterpact M with a Masterpact NW, order a retrofit device (without connections) and select a set of connectors corresponding to the replaced device. The Masterpact NW is installed in exactly the same place as the old Masterpact M device, without any modifications required on the switchboard.
Masterpact M16
Type N1/NI/H1/H2/HI/HF Top 3x Bottom 3x
48954 48965
4x 4x
48954 48965
Masterpact M32
Type H1/H2/HI/HF Top Bottom 1x 1x
48957 48958
4x 4x
48957 48958
48962 48961
1x 1x
48960 48960
To replace a Masterpact M with a Masterpact NW, order a retrofit device (without connections) and select a set of connectors corresponding to the replaced device. The Masterpact NW is installed in exactly the same place as the old Masterpact M device, without any modifications required on the switchboard.
Masterpact M16
Type N1/NI/H1/H2/HI/HF/L1 Top 3x Bottom 3x
48969 48969
4x 4x
48969 48969
Masterpact M32
Type H1/H2/HI/HF/M20/L1 Top 1x Bottom 1x
48970 48970
4x 4x
48970 48970
48974 48974
1x 1x
48978 48978
Masterpact M16
Type N1/NI/H1/H2/HI/HF/L1 Top 3x Bottom 3x
48954 48965
4x 4x
48954 48965
48957 48958
4x 4x
48957 48958
48976 48977
48977 48976
Masterpact NT
Connection
Connection
3P 4P
250/630-1600 A
47069
47070
Installation manual
E46430 E46429
Vert. mounting.
47102
250/630-1600 A
33588
33589
Installation manual
E46430 E46429
Vert. mounting.
Connection accessories
47102 3P 4P 33643
33642 47102 33644 47102 33622 47102 33648 33768 47102 47335 47102
33645
For fixed and drawout front and rear-connected circuit breakers Installation manual
33623
47336
F-4
Long-time rating plug (limits setting range for higher accuracy) / 1 part
0.4 at 1 x Ir 0.4 at 0.8 x Ir 0.8 at 1 x Ir off 33542 33543 33544 33545
Battery + cover
Battery (1 part) Cover (1 part) For Micrologic A For Micrologic P and H 33593 33592 47067
E95540
menu
Communication option
Chassis
E95541
Modbus COM 6 wires terminal drawout (1 part) 6 wires terminal fixed (1 part)
Installation manual
33088
External sensors
E46671
400/1600 A
33576
Source ground return (SGR) earth-fault protection / 1 part External sensor (SGR) MDGF summing module Rectangular sensor for earth-leakage protection + Vigi cable / 1 part 280 mm x 115 mm
33579 48891
E46672
E46672
33573
1 battery
24 V DC
L4 L3
t Inpu 24VDC Output 24VDC G2
0A AD 22
G1
F-5
Masterpact NT
Remote operation
Remote operation
Gear motor
E95168
DC
48 V 100/130 V 200/240 V 277/415 V 440/480 V + resistor 24/30 V 48/60 V 100/125 V 200/250 V For fixed circuit breaker For drawout circuit breaker
33186 33176 33177 33179 33179 33193 33185 33186 33187 33188 47074 33098
Fixed.
33658 33659 33660 33661 33662 33663 33664 33032 33033 33034 33035 33036 33037 33038 47074 33098
E95169
Fixed.
E95171
Drawout. Installation manual Undervoltage release (1 part) AC 50/60 Hz 24/30 V DC, 24 V AC DC 48/60 V DC, 48 V AC 100/130 V AC/DC 200/250 V AC/DC 380/480 V AC Terminal block (1 part) For fixed circuit breaker For drawout circuit breaker 47103
Undervoltage release MN
E95170
E95169
Fixed.
E95171
E46694
MN delay unit
MN delay unit (1 part) R (non-adjustable) AC 50/60 Hz DC 48/60 V AC/DC 100/130 V AC/DC 200/250 V AC/DC 380/480 V AC/DC 33684 33685 Rr (adjustable) 33680 33681 33682 33683 47103
Installation manual
F-6
Chassis locking
E46685
Installation manual
47104 33788
Installation manual
47104 33767
Chassis accessories
E46698
Installation manual
47104
Installation manual
47104
F-7
Masterpact NT
Clusters
Clusters
E95538
64906
Racking handle
47098
F-8
Installation manual
47103
By padlocks + BPFE support 47514 By Profalux keylocks + BPFE support Profalux 1 lock with 1 key + adaptation kit 2 locks 1 keys + adaptation kit 1 keylock Profalux (without adaptation kit): identical key not identified combination identical key identified 215470 combination identical key identified 215471 combination By Ronis keylocks + BPFE support Ronis 1 lock with 1 key + adaptation kit 2 locks 1 keys + adaptation kit 1 keylock Ronis (without adaptation kit): identical key not identified combination identical key identified EL24135 combination identical key identified EL24153 combination identical key identified EL24315 combination Adaptation kit adaptation kit Profalux (without keylock): adaptation kit Ronis adaptation kit Kirk adaptation kit Castell Installation manual 64918 64919 33173 33174 33175 64920 64921 33189 33190 33191 33192 47515 47516 47517 47518 47103
33895
Installation manual
Escutcheon
E95558
Cover
Installation manual
47103 47094
Installation manual
47103
47092
Installation manual
47103
Installation manual
47103
F-9
Masterpact NT
Complete assembly with 2 adaptation fixtures + rods 2 Masterpact NT fixed devices 2 Masterpact NT drawout devices Note: the installation manual is enclosed.
33912 33913
33920 33921
F-10
Indication contacts
Indication contacts
E46463
F-11
Masterpact NT
Instructions
Instructions
Chassis accessories Circuit breaker accessories Fixed and drawout circuit breaker Micrologic user manual 47104 47103 47102 33076 33077 33079 33080 33082 33083 33085 33086 47106 47107 33088
20/50 (French) 20/50 (English) 2A/7A (French) 2A/7A (English) 5P/7P (French) 5P/7P (English) 5H/7H (French) 5H/7H (English) NT user manual French English Modbus communication notice for manual
F-12
50963
50964
50960
E79015
CCP303: Masterpact or Compact pre-wired cable (4 RS 485 wires + 2 power wires) 3 m length 50961
E67961
50965
MPS100
33507
Converter
RS 485/RS 232 (ACE909) 12 V DC power supply included RS 485/RS 232 RS 485/Ethernet RS 485/Ethernet (SMS compatible) (1) See catalogue Telemecanique. (2) Consult PMC Department. (*) Consult us. 59648 TSX SCA72 174 CEV 300-10 EGX 100/400
(2) (1)
(2)
F-13
Masterpact NW
Connection
Connection
3P 4P
800-1600 A 2000/3200 A
Bottom Bottom
47932 47942
47933 47943
E95533
Installation manual Rear connection (vertical or horizontal mounting) / Replacement kit (3 or 4 parts) 800-2000 A Vertical Horizontal 2500/3200 A Vertical Horizontal Vertical mounting 4000 A Vertical Horizontal 4000b/5000 A Vertical Horizontal Horizontal mounting 6300 A Vertical Installation manual
47950 47964 47964 47966 47966 47968 47970 2x 47966 2x 47966 2x 47968 47950 47965 47965 47967 47967 47969 47971 2x 47967 2x 47967 2x 47969
E46446
E46445
Installation manual Rear connection (vertical or horizontal mounting) / Replacement kit (3 or 4 parts) 800-2000 A types N1/H1/H2 Vertical 800-1600 A types H3/L1 Horizontal 2500/3200 A types H1/H2 Vertical 2000/3200 A types H3/L1 Horizontal Vertical mounting 4000 A Vertical Horizontal 4000b/5000 A Vertical Horizontal Horizontal mounting 6300 A Vertical Installation manual
47950 47964 47964 47966 47966 47968 47970 2x 47966 2x 47966 2x 47968 47950 3P 47965 47965 47967 47967 47969 47971 2x 47967 2x 47967 2x 47969
E46446
E46445
Connection accessories
4P 48466 48467
F-14
Long-time rating plug (limits setting range for higher accuracy) / 1 part
0.4 at 1 x Ir 0.4 at 0.8 x Ir 0.8 at 1 x Ir off 33542 33543 33544 33545
Battery + cover
Battery (1 part) Cover (1 part) For Micrologic A For Micrologic P and H 33593 33592 47067
E95540
menu
Communication option
Chassis
E95541
Modbus COM 6 wires terminal drawout (1 part) 6 wires terminal fixed (1 part)
Installation manual
33088
External sensors
E46671
Source ground return (SGR) earth-fault protection / 1 part External sensor (SGR) MDGF summing module Rectangular sensor for earth-leakage protection + Vigi cable / 1 part (up to 3200 A) 280 mm x 115 mm 470 mm x 160 mm
33579 48891
E46672
33573 33574
E46672
1 battery
24 V DC
L4 L3
t Inpu 24VDC Output 24VDC G2
0A AD 22
G1
F-15
F-15
Masterpact NW
Remote operation
Remote operation
Gear motor
E95172
DC
E95169 E95171
48 V 100/130 V 200/240 V 250/277 V 380/415 V 440/480 V 24/30 V 48/60 V 100/125 V 200/250 V For fixed circuit breaker For drawout circuit breaker
47889 47893 47894 47895 47896 47897 47888 47889 47890 47891 47074 47849
Fixed.
33658 33659 33660 33661 33662 33663 33664 33032 33033 33034 33035 33036 33037 33038 47074 47849
E95169
Fixed.
E95171
Undervoltage release MN
Undervoltage release (1 part) AC 50/60 Hz 24/30 V DC, 24 V AC DC 48/60 V DC, 48 V AC 100/130 V AC/DC 200/250 V AC/DC 380/480 V AC Terminal block (1 part) For fixed circuit breaker For drawout circuit breaker
E95170
E95169
Fixed.
E95171
Drawout. Installation manual MN delay unit (1 part) R (non-adjustable) AC 50/60 Hz DC 48/60 V AC/DC 100/130 V AC/DC 200/250 V AC/DC 380/480 V AC/DC 33684 33685 Rr (adjustable) 33680 33681 33682 33683 47951 47951
MN delay unit
E46694
Installation manual
F-16
F-16
Chassis locking
E46451
Installation manual
Racking interlock
E46453
47952 64940
5 parts
Installation manual
47952 33767
Installation manual
47952
Chassis accessories
E46458
3P 4P 3P 4P
F-17
Masterpact NW
Clusters
Clusters
E95538
64906
32 32 48 56
Racking handle
E95561
Racking handle
47944
DC rear connection
Serial connection kit
DB105109
For NW10/20 DC
48642
DB105110
For NW40 DC
48643
F-18
Installation manual
47951
By padlocks 48539 1 lock with 1 key + adaptation kit 2 locks 1 keys + adaptation kit 2 locks 2 different keys + adaptation kit 1 keylock Profalux (without adaptation kit): identical key not identified combination identical key identified 215470 combination identical key identified 215471 combination By Ronis keylocks Ronis 1 lock with 1 key + adaptation kit 2 locks 1 keys + adaptation kit 2 locks 2 different keys + adaptation kit 1 keylock Ronis (without adaptation kit): identical key not identified combination identical key identified EL24135 combination identical key identified EL24153 combination identical key identified EL24315 combination Adaptation kit adaptation kit Profalux / Ronis (without keylock): adaptation kit Kirk adaptation kit Castell Installation manual By Profalux keylocks Profalux 64928 64929 64930 33173 33174 33175 64931 64932 64933 33189 33190 33191 33192 64925 64927 64926 47951
48535
Installation manual
Escutcheon
E95535
Cover
Installation manual
47951 47939
Installation manual
47951 47940
Installation manual
47951 3P 47935 47935 47936 47936 47937 47934 4P 47935 47935 47936 47936 47937 47934 47951
F-19
Masterpact NW
Complete assembly with 2 adaptation fixtures + rods 2 Masterpact NW fixed devices 2 Masterpact NW drawout devices Can be used with 1 NW fixed + 1 NW drawout. Note: the installation manual is enclosed.
48612 48612
F-20
Indication contacts
Indication contacts
E46689
Installation manual
47951 6 A - 240 V Low-level For fixed circuit breaker For drawout circuit breaker 47915 47916 47074 47849
Installation manual
1 changeover contact (5 A - 240 V) 1 low-level changeover contact Wiring For fixed circuit breaker For drawout circuit breaker Installation manual
Installation manual
47952 48560
Combined closed / connected contacts for use with 1 auxiliary contact / 1 part
1 contact (5 A - 240 V) or 1 low-level contact 48477 48478
E46690
Installation manual
1 pushbutton
Installation manual
F-21
Masterpact NW
Instructions
Instructions
Chassis accessories Circuit breaker accessories Fixed and drawout circuit breaker User manual 47952 47951 47950 47954 47955 64923 64924 33076 33077 33079 33080 33082 33083 33085 33086 33088
NW AC (French) NW AC (English) NW DC (French) NW DC (English) Micrologic user manual 20/50 (French) 20/50 (English) 2A/7A (French) 2A/7A (English) 5P/7P (French) 5P/7P (English) 5H/7H (French) 5H/7H (English) Modbus communication notice for manual
F-22
50963
50964
50960
E79015
CCP303: Masterpact or Compact pre-wired cable (4 RS 485 wires + 2 power wires) 3 m length 50961
E67961
50965
MPS100
33507
Converter
RS 485/RS 232 (ACE909) 12 V DC power supply included RS 485/RS 232 RS 485/Ethernet RS 485/Ethernet (SMS compatible) (1) See catalogue Telemecanique. (2) Consult PMC Department. (*) Consult us. 59648 TSX SCA72 174 CEV 300-10 EGX 100/400
(2) (1)
(2)
F-23
Order form
Masterpact NT and NW
To indicate your choice, check the applicable square boxes and enter the appropriate information in the rectangles
Indication contacts
OF - ON/OFF indication contacts Standard 4 OF 6 A-240 V AC (10 A-240 V AC and low-level for NW) Alternate 1 OF low-level for NT Max. 4 qty Additional 1 block of 4 OF for NW Max. 2 Max. 8 Max. 8 qty qty qty EF - combined connected/closed contacts 1 EF 6 A-240 V AC for NW 1 EF low-level for NW SDE - fault-trip indication contact Standard 1 SDE 6 A-240 V AC Additional 1 SDE 6 A-240 V AC Programmable contacts Carriage switches CE - connected position CD - disconnected position CT - test position 2 M2C contacts Low level Max. 3 for NW/NT Max. 3 for NW - 2 for NT Max. 3 for NW - 1 for NT
Quantity
NW
1 SDE low level 6 M6C contacts 6 A-240 V AC qty qty qty qty V V V Low level 6 A-240 V AC V V V
Special circuit breaker H2 anticorrosion, H10 (NW) NA, HA, HF, ES, HA10 (NW) 3 or 4 Square D
Schneider Electric
Option: neutral on right side (NW) Type of equipment Fixed Drawout with chassis Drawout without chassis (moving part only) Chassis alone Earthing switch kit for chassis
Remote operation
Remote ON/OFF MCH - gear motor XF - closing voltage release MX - opening voltage release PF - ready to close contact
BPFE - electrical closing pushbutton RES - electrical reset option RAR - automatic reset option MN - undervoltage release R - delay unit (non-adjustable) Rr - adjustable delay unit 2nd MX - shunt release
Standard 0.4 to 1 Ir Low setting 0.4 to 0.8 Ir High setting 0.8 to 1 Ir LR OFF
Locking
VBP - ON/OFF pushbutton locking (by transparent cover + padlocks) OFF position locking: VCPO - by padlocks VSPO - by keylocks Keyock kit (w/o keylock) 1 keylock 2 identical keylocks, 1 key 2 keylocks, different keys (NW) Chassis locking in disconnected position: VSPD - by keylocks Keyock kit (w/o keylock) 1 keylock 2 identical keylocks, 1 key 2 keylocks, different keys VPEC - door interlock VPOC - racking interlock IPA - cable-type door interlock VDC - mismatch protection VIVC - shutter position indication and locking for NW IBPO - racking interlock between crank and OFF pushbutton for NW DAE - automatic spring discharge before breaker removal for NW Profalux Profalux Profalux Profalux Profalux Kirk Profalux Profalux Profalux Ronis Ronis Ronis Ronis Ronis Castell Ronis Ronis Ronis
TCE - external sensor (CT) for neutral and residual earth-fault protection TCE - external sensor (CT) for over sized neutral (3P - Micrologic P / H) and residual earth-fault protection TCW - external sensor for SGR protection Rectangular sensor for earth-leakage protection PTE - external voltage connector NT (280 x 115 mm) NW (470 x 160 mm)
Communication
COM module Eco COM module JBus/ModBus JBus/ModBus Device Device Chassis Chassis (*)
(*) for drawout devices, please order 1 JBus/Modbus chassis COM module Top Top Top Bottom Bottom Bottom
Connection
Horizontal Vertical Front Vertical-connection adapters Cable-lug adapters Arc chute screen Interphase barriers Spreaders Disconnectable front connection adapter Lugs for 240v or 300v cables
Optional connected/disconnected/test position lock On right-hand side chassis On left-hand side chassis
NT - FC fixed, draw. NT - FC fixed, draw. NT - FC fixed NT, NW fixed, drawout NT fixed, drawout NW fixed NT fixed, drawout
Accessories
VO - safety shutters on chassis for NT and NW CDM - mechanical operation counter NT, NW CB - auxiliary terminal shield for chassis NT, NW CC - arc chute cover for fixed NT CDP - escutcheon NT, NW CP - transparent cover for escutcheon NT, NW OP - blanking plate for escutcheon NT, NW Brackets for mounting Test kits NW fixed Mini test kit On backplates Portable test kit X
Micrologic control unit functions: 2.0 : basic protection (long time + inst.) 5.0 : selective protection (long time + short time + inst.) 6.0 : selective + earth-fault protection (long time + short time + inst. + earth-fault) 7.0 : selective + earth-leakage protection (long time + short time + inst. + earth-leakage)
F-24
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Design: Schneider Electric Photos: Schneider Electric Printed: Imprimerie du Pont-de-Claix/JPF - made in France
09-2009