Compact size Flat design Built-in overheat protection 3-side DIN rail mountable
|
Technical Data
Heating element Overheat protection Heater body Connection Important! Heater must be operated together with a fan. Operating without a fan creates the danger of overheating. Connection housing Mounting Mounting position Operating / Storage temperature
100W/ 150W Heater
Mounting hole for DIN clip
high performance cartridge built-in temperature limiter die-cast aluminum, glass bead finish 3-pole terminal AWG 14 max. (2.5mm), torque 0.8Nm max.. plastic, UL 94V-0, black clip for 35mm DIN rail, EN 60 715 horizontal -49 to +158F (-45 to +70C) I (grounded) / IP20 service life 50,000h at 77F (25C) see table below 2-pole terminal AWG 14 max. (2.5mm), terminals L2/N2 UL File No. E187294 (all), VDE (230VAC only)
Protection class / Protection type Axial fan, ball bearing Air flow, free blowing Axial fan connection Approvals
Air flow
Label
Axial fan
Thermostat
4.13 (104.8 mm) 4.68 (119 mm)
Air flow
Label
1
Axial fan
L N
Min. airflow (free blowing) 20 cfm (35m/h) 20 cfm (35m/h) 63 cfm (108m/h) 63 cfm (108m/h) 63 cfm (108m/h)
Dimensions (as mounted) 1.85 x 3.15 x 4.41 (47 x 80 x 112mm) 1.85 x 3.15 x 4.41 (47 x 80 x 112mm) 1.85 x 4.68 x 5.94 (47 x 119 x 151mm) 1.85 x 4.68 x 5.94 (47 x 119 x 151mm) 1.85 x 4.68 x 5.94 (47 x 119 x 151mm)
Weight (approx.) 1.3 lbs. (600g) 2.0 lbs. (900g) 2.0 lbs. (900g) 2.0 lbs. (900g)
HVL031/2-09/US
Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/ buyer in its final application.
STEGO, Inc. 1395 South Marietta Parkway Building 800 Marietta, GA 30067 Tel: (770) 984-0858 Fax: (770) 984-0615 Toll free: 1-888-783-4611 (US & Canada only) www.stegousa.com
Heating
The compact HVL 031 high-performance fan heater prevents formation of condensation and provides an evenly distributed interior air temperature in enclosures. For large OEM use, this fan heater can also be provided without the fan, in which case the OEM/customer must provide a fan which meets the minimum airflow requirements.