MVTP
Buswire Supervision for High Impedance Schemes
The MVTP is a monitoring device, used to ensure the integrity of busbar, and restricted earth fault schemes. The MVTP relay is available in two types: > Type MVTP 11 - single phase relay. > Type MVTP 31 - three phase relay. These provide continuous supervision of the buswires in high impedance type busbar protection schemes, detecting open-circuited buswires as well as open-circuited main current transformers.
Type MVTP
In earth-fault only protection schemes, the single-phase relay is employed. MVTP relays have a setting range of 2-14V, adjusted by means of a plug bridge on the relay front panel. Relays are continuously rated at 600V rms and no external components are required. The ac voltage input is continuously monitored and when it exceeds the level pre-set by means of the plug setting, the output relay is actuated after a three second delay. The hand reset contacts of the output relay are normally connected across the buswires of the busbar protection thus short-circuiting the busbar protection relay and rendering the protection of the zone concerned inoperative. On the same output relay are hand reset contacts for alarm purposes. Operation of the relay is indicated by a hand resettable mechanical flag.
Customer Benefits Integral buswire shorting facility Low ac burden No external resistors required Ensures the availability of MCAG and MFAC schemes
T&D
P1
S1 See note 3 S2
P1 S1
a b c n
P2
Vx
23
VA
24 25 RL1-2
2 4
v Case earth
87 A
87 B
Alarm contacts
87 C
VB
26 27
>Vs
Output circuits
RL1 6
RL1-3 RL1-4
1 3 5 7 9 11 13 15 17 19 21 23 25 27
2 4 6 8 10 12 14 16 18 20 22 24 26 28
VC
28 13 14 22 RL1-5
7 6 8
See note 3
+ve ve
RL1-6
9 11
CT shorting links make before (b) & (c) disconnect. Short terminals break before (c) Long terminals
2 Earthing connections as shown are typical only 3 CT connections are typical only.
Figure 1
Application diagram: static modular buswire voltage supervision relay, type MVTP 31.
TECHNICAL DATA
> Burdens
Measuring circuit - typical burdens Applied voltage Vac Burden VA 2 8 14 600
> Settings
Setting range (VS) 2-14V rms adjusted by means of a plug bridge in 7 equal steps.
0.01x10-3
0.7x10-3 2.2x10-3
4.0
Auxiliary supply - typical burdens at the upper rated voltage Vx rated voltage (V dc) 30/34 48/54 110/125 220/250 Output relay not energised mA 24 24 24 24 W 0.82 1.3 3.0 6.0 Output relay energised mA 90 90 35 35 W 3.06 4.86 4.37 8.75
2>3
Self monitoring for high impedance unit protection, for peace of mind
* Use a 30/34V relay with a separate MSTZ 02 dc/dc converter. All relays are rated continuously at the maximum voltage in the operative range.
> Cases
Types MVTP 11 and MVTP 31 are supplied in size 4 and size 6 cases respectively, as shown in Figures 2 and 3.
Frequency 50 and 60 Hz Operative range 47-61 Hz Operating time Fixed at 3 seconds Contact disengaging time <150ms Drop off/pick up ratio >85% after 3 second delay >98% before 3 second delay
CONTACTS
Buswire shorting contacts are normally open type. The two alarm contacts may be specified in any combination of make or break (2M, 1M 1B, or 2B)
1250VA with maxima of 5 amps and 300V 100 watts (resistive) 50 watts (inductive) and maxima of 5 amps and 300V
DC
The hand-reset contacts will carry 150A rms for 0.5 seconds.
97
52
4 holes 4.4
23.5
since 1984
>> Over 21000 MFAC schemes installed
168 159
since 1983
>> MVTP buswire supervision shipped
103
Reset
All dimensions in mm
Flush mounting
11
Figure 2
149
4 holes
4.4
103.6 24
168
159
177
155
Flush mounting
11
All dimensions in mm
Figure 3
AREVA T&D Worldwide Contact Centre: http://www.areva-td.com/contactcentre/ Tel.: +44 (0) 1785 250 070
www.areva-td.com
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advise on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.
AUTOMATION-L3-MVTP-BR-01.05-0796-GB - - AREVA - 2004. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA. MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP