Professional Documents
Culture Documents
Capacitor Sizing Calculation (5015 LT 00 EL 03 CA 0003) Rev 00
Capacitor Sizing Calculation (5015 LT 00 EL 03 CA 0003) Rev 00
CAPACITOR SIZING CALCULATION OWNER UNIT L&T JOB NO. : OIL AND NATURAL GAS CORPORATION LIMITED, URAN : ADDITIONAL PROCESS UNITS : 5015
I 1
REVIEW CODE
REVIEWED, NO COMMENTS.WORK TO PROCEED. REVIEWED AS COMMENTED. WORK SHALL PROCEED WITH FABRICATION / MANUFACTURING TAKING CARE AND INCORPORATING OWNER /PMC COMMENTS. MAJOR NON CONFORMANCE AND DEVIATIONS TO CONTRACT SPECIFICATIONS. RESUBMIT FOR REVIEW AFTER INCORPORATING COMMENTS. RETAINED FORINFORMATION / RECORDS.
1st
2nd
3rd 2
AS BUILT
ONGC/PMC
DATE
REVIEWED BY
00
REV.
24.11.10
DATE
SA
PREPARED BY
RH
CHECKED BY HOD PEM APPROVED BY
DOCUMENT NO.
PROJECT CUSTOMER
CONTENTS
SECTION
PAGE
1. 2. 3. 4.
DOCUMENT NO.
The scope of this document covers capacitor sizing calculation to be installed in APU Substation for Uran APU project.
2. REFERENCE DOCUMENTS
Engineering Design Basis Electrical Design Philosophy for Electrical Facilities Job Specification Electrical Overall Electrical Load Analysis Overall key single line Diagram
3. CAPACITOR SIZING CALCULATION The kW and kVA loading on the HV switchboards HT-201 under normal running load as per overall electrical load analysis are as follows
KW 21244.6
NORMAL RUNNING LOAD/ MAXIMUM DEMAND LOAD KVAR KVA P.F. 11378.7 24100 0.881
The present power factor of 6.6kV bus is calculated as cos 1 = (kW/kVA) = 21244.6/24100=0.881 The required Power Factor as per ITB is 0.9. Hence cos 2 = 0.9 Total MW considering 15% future load growth = 21.2446* 1.15 = 24.43 MW
Capacitive MVAR = MW * (tan (cos-1(cos 1))-tan (cos-1(cos 2))) = 24.43 * (tan (cos-1(0.881))-tan (cos-1(0.9))) = 24.43 * (0.537-0.484) = 1.295 MVAr
DOCUMENT NO.
PROJECT CUSTOMER
4.
CONCLUSION The total capacitor bank rating shall be 1.295 MVAR. The capacitor bank on each bus section of HT -201 shall be selected as 650 KVAr.