Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 4

Client:

ADDITIONAL PROCESS UNITS

OIL AND NATURAL GAS CORPORATION LIMITED

L&T, E&C DIVISION

Contractor : Larsen & Toubro Limited,


E&C DIVISION, Mumbai

Doc. No. : 5015-LT-00-EL-04-CA-0003 Rev. : 00

CAPACITOR SIZING CALCULATION OWNER UNIT L&T JOB NO. : OIL AND NATURAL GAS CORPORATION LIMITED, URAN : ADDITIONAL PROCESS UNITS : 5015

DOC. CATEGORY: DOCUMENT STATUS

I 1

REVIEW CODE
REVIEWED, NO COMMENTS.WORK TO PROCEED. REVIEWED AS COMMENTED. WORK SHALL PROCEED WITH FABRICATION / MANUFACTURING TAKING CARE AND INCORPORATING OWNER /PMC COMMENTS. MAJOR NON CONFORMANCE AND DEVIATIONS TO CONTRACT SPECIFICATIONS. RESUBMIT FOR REVIEW AFTER INCORPORATING COMMENTS. RETAINED FORINFORMATION / RECORDS.

1st

2nd

3rd 2

FINAL FOR CODE 1

AS BUILT

COMMENTS (IF ANY): 3 I

ONGC/PMC

DATE

REVIEWED BY

00
REV.

24.11.10
DATE

Issued for Review


DESCRIPTION

SA
PREPARED BY

RH
CHECKED BY HOD PEM APPROVED BY

LARSEN & TOUBRO LIMITED E&C DIVISION

DOCUMENT NO.

PROJECT CUSTOMER

: Additional Process Units : ONGC, URAN

CAPACITOR SIZING CALCULATION

5015-LT-00-EL-04-CA-0003 REVISION PAGE : : 00 2 OF 4

CONTENTS

SECTION

PAGE

1. 2. 3. 4.

Scope...........................................................................................................................3 Reference Documents................................................................................................. 3 Capacitor sizing calculation.........................................................................................3 Conclusion....................................................................................................................4

LARSEN & TOUBRO LIMITED E&C DIVISION

DOCUMENT NO.

PROJECT CUSTOMER 1. SCOPE

: Additional Process Units : ONGC, URAN

CAPACITOR SIZING CALCULATION

5015-LT-00-EL-04-CA-0003 REVISION PAGE : : 00 3 OF 4

The scope of this document covers capacitor sizing calculation to be installed in APU Substation for Uran APU project.

2. REFERENCE DOCUMENTS

Engineering Design Basis Electrical Design Philosophy for Electrical Facilities Job Specification Electrical Overall Electrical Load Analysis Overall key single line Diagram

: V002-00-50-50-DB-001, Rev 1 : 6-51-0099 Rev 04 : V002-00-50-50-SP-02-0 : 5015-LT-00-EL-03-CA-0001 Rev 0 : 5015-LT-00-EL-00-SL-0002 Rev 0

3. CAPACITOR SIZING CALCULATION The kW and kVA loading on the HV switchboards HT-201 under normal running load as per overall electrical load analysis are as follows

KW 21244.6

NORMAL RUNNING LOAD/ MAXIMUM DEMAND LOAD KVAR KVA P.F. 11378.7 24100 0.881

The present power factor of 6.6kV bus is calculated as cos 1 = (kW/kVA) = 21244.6/24100=0.881 The required Power Factor as per ITB is 0.9. Hence cos 2 = 0.9 Total MW considering 15% future load growth = 21.2446* 1.15 = 24.43 MW

Capacitive MVAR = MW * (tan (cos-1(cos 1))-tan (cos-1(cos 2))) = 24.43 * (tan (cos-1(0.881))-tan (cos-1(0.9))) = 24.43 * (0.537-0.484) = 1.295 MVAr

LARSEN & TOUBRO LIMITED E&C DIVISION

DOCUMENT NO.

PROJECT CUSTOMER

: Additional Process Units : ONGC, URAN

CAPACITOR SIZING CALCULATION

5015-LT-00-EL-04-CA-0003 REVISION PAGE : : 00 4 OF 4

4.

CONCLUSION The total capacitor bank rating shall be 1.295 MVAR. The capacitor bank on each bus section of HT -201 shall be selected as 650 KVAr.