2.3 MCB
2.3 MCB
2.3 MCB
nxuong-BMTBD-TBD-V1
The Technology
Power contact : overcurrent breaking Arc chute : toggle : switch-on / off upon user s request overcurrent breaking
magnetic coil :
short-circuit tripping
Clip :
securing
nxuong-BMTBD-TBD-V1
nxuong-BMTBD-TBD-V1
Overload protection
A bimetal strip is used to protect the cable against overloads : avoid current exceeding cable heating withstand
symbol:
nxuong-BMTBD-TBD-V1
In = rated current
nxuong-BMTBD-TBD-V1
symbol
magnetic coil
nxuong-BMTBD-TBD-V1
Short-circuit tripping
Magnetic tripping curve acc. to IEC / EN 60 898 standard
time (sec)
In = rated current
0.1 sec
3 5 10
5 10 20
Current ( I/In)
nxuong-BMTBD-TBD-V1
nxuong-BMTBD-TBD-V1
Example Example : : for a usual 630 kVA transformer (delivering 800 Amps) for a usual 630 kVA transformer (delivering 800 Amps) : : Isc = 22 kA rms at transformer terminals; --Isc = 22 kA rms at transformer terminals; -Isc = 9 kA at the end of 120 sq.mm / /50 m cable - Isc = 9 kA at the end of 120 sq.mm 50 m cable Isc = 5 kA at the end of add. 35 sq.mm 30 m cable --Isc = 5 kA at the end of add. 35 sq.mm / /30 m cable
nxuong-BMTBD-TBD-V1
10
nxuong-BMTBD-TBD-V1
11
nxuong-BMTBD-TBD-V1
12
nxuong-BMTBD-TBD-V1
13
nxuong-BMTBD-TBD-V1
14
c thng s MCB
1 3
2 4
nxuong-BMTBD-TBD-V1
15