3EE Surge Arresters
3EE Surge Arresters
www.siemens.com/energy
Siemens HG 21 2007
R-HG21-100.tif
Contents
Contents
Page
Description
General
5
6
Construction and mode of operation of 3EE arresters 7 Construction and mode of operation of 3EF limiters 10 Dielectric strength Standards 12 12
Equipment Selection
Ordering data and configuration example Selection of 3EE arresters Accessories for arresters Selection of 3EF limiters
13
14 15 21 22
Technical Data
Electrical data, dimensions and weights Arresters Electrical data, dimensions and weights Limiters
23
24 27
Annex
Inquiry form Configuration instructions Configuration aid
29
30 31 Foldout page
Siemens AG 2007
Siemens HG 21 2007
Siemens HG 21 2007
R-HG11-173.tif
Description
Contents
Contents
Page
Description
General Construction and mode of operation of 3EE arresters: Application Construction Mode of operation Installation Monitoring Selection criteria Construction and mode of operation of
R-HG11-174.tif
5
6
7 7 8 8 9 9
3EF limiters: Application Construction and mode of operation Installation Selection criteria Dielectric strength Standards 10 10 10 11 12 12
Siemens HG 21 2007
Description
General
R-HG21-101.eps
Surge arresters protect operational equipment, such as motors, generators and transformers both against external overvoltages from lightning strikes in overhead lines and internal overvoltages caused by switching operations or earth faults. As the voltage rises, the conductivity increases overproportionally, so that the load can be discharged to earth.
Surge limiters limit impermissibly high switching overvoltages that could be dangerous for the windings of high-voltage motors. Such overvoltages can appear when switching devices are used whose contact gap recovers extremely fast after current zero. Surge limiters are provided for use in cable systems and are usually installed in indoor switchgear.
Siemens HG 21 2007
R-HG21-102.eps
Description
Construction and mode of operation of 3EE arresters
Sectional view of a 3EE arrester 1 Insulator 2 Flange with gas diverting nozzle 3 Seal 4 Pressure relief diaphragm 5 Compression spring 6 Metal-oxide resistor (non-linear)
HG21-2200 eps
Siemens HG 21 2007
Description
Construction and mode of operation of 3EE arresters
Mode of operation
Residual voltage
HG21-2201_en eps
Discharge current
Metal-oxide resistors are strongly non-linear, i.e. they have a strongly curved current-voltage characteristic, so that below a certain voltage only a small leakage current flows. The arresters are designed in such a way that only the small leakage current flows at the continuous operating voltage applied in normal operation. When lightning or switching overvoltages occur, the resistors become very conductive. This makes an impulse current flow to earth, reducing the overvoltage to the value of the voltage drop at the arrester (residual voltage). Thereby, the impulse currents can be up to 1 kA in the case of switching overvoltages and from 1 kA to 20 kA in case of lightning overvoltages.
HG21-2202_en eps
If the switching overvoltages can reach impermissibly high values, the arresters must be designed to limit the overvoltages to permissible values, both between phases (L-L) and to earth (L-E). The target is to manage with three arresters in phase-to-earth connection. If this is not possible, a 6-arrester connection must be provided. Installation Normally, arresters are mounted in vertical position and with the high-voltage terminal at the top. If the construction requires this, the devices can also be installed in suspended or horizontal position. When ordering, these special installation conditions as well as the 6-arrester connection must be specified in clear text as a special version.
6-arrester connection
6-arrester connection with mounted tell-tale spark gaps 1 Not included in the scope of supply 2 Copper bars for delta connection
Siemens HG 21 2007
Description
Construction and mode of operation of 3EE arresters
Monitoring The arresters do not require any monitoring or maintenance. The frequency of operation of the surge arresters as well as the magnitude of the discharge currents and the type of possible overvoltages can be determined by installation of a tell-tale spark gap 3EX6040 in the earthing cable. Selection criteria The opposite table offers an overview of typical arresters for the typical system voltages defined in the IEC standards. For differing system voltages or intermediate values, the selection condition applicable to the respective type of power system must be complied with. The short-circuit current capability to be selected for the arrester must be greater than or equal to the maximum short-circuit current occurring in the power system. The following selection conditions apply to the different power systems: System with solidly earthed neutral Uc 1.05 x ULE = 1.05 x Um x e (for e = 1.0) 3
1
Maximum voltage for equipment System with System with solidly earthed impedanceneutral earthed neutral System with isolated neutral System with resonantearthed neutral
Um kV 3.6 7.2 12 17.5 24 36 40.5 3EE2 056 3EE2 056 3EE2 120 3EE2 150 3EE2 190 3EE2 270 3EE2 340 3EE2 056 3EE2 075 3EE2 120 3EE2 190 3EE2 230 3EE2 340 3EE2 450 3EE2 056 3EE2 090 3EE2 150 3EE2 230 3EE2 300 3EE2 450
3EE2 056 3EE2 090 3EE2 150 3EE2 230 3EE2 300 3EE2 450
Um x e = Um (for e = 1.73) 3
Continuous operating voltage Phase-to-earth voltage in case of a fault Maximum system voltage Earth-fault factor
The energy absorption capacity of 8kJ/kV is generally enough. Arresters with 10 kJ/kV are available when a higher energy absorption capacity is needed. The actual energy absorption capacity required can be determined by means of a network calculation.
Siemens HG 21 2007
HG21-2213 eps
Description
Construction and mode of operation of 3EF limiters
1
3EF1 surge limiter
10
Siemens HG 21 2007
R-HG21-104.tif
Description
Construction and mode of operation of 3EF limiters
Selection criteria Which surge limiter must be selected largely depends on the factors energy absorption capacity and overload performance. The limiters of the type series 3EF3 can absorb up to 5 times the energy of those of the 3EF1 series. The magnitude of the necessary energy absorption capacity must be determined in a network calculation. In case of overload, which cannot be excluded in the case of intermittent earth-faults, the housing of 3EF1 limiters can be torn open and the arc can escape. Limiters type 3EF3 have integrated rupture diaphragms which tear open in order to protect the housing from pressure damages. The gases escaping as the pressure is relieved are deflected to the outside due to the shape of the aluminium cap, and this ignites an arc between the counter electrode and the cap. The arc resulting from an overload burns until the circuit is interrupted by the upstream overcurrent protection devices. Surge limiters which failed due to overload must be replaced. The opposite table offers an overview of typical limiters for motor protection for typical rated motor voltages. For differing rated motor voltages or intermediate values, the following selection condition applicable to the respective type of power system must be complied with in order to select a suitable limiter: Ur Um
Um Maximum system voltage Ur Rated voltage Maximum voltage for equipment System with System with solidly earthed impedanceneutral earthed neutral System with isolated neutral System with resonantearthed neutral
1
Um kV 3.6 4.8 7.2 12 15 3EF1 036-0A 3EF3 036-0 3EF1 048-0A 3EF3 048-0 3EF1 072-0A 3EF3 072-0 3EF1 120-1 3EF1 150-0A 3EF1 036-0A 3EF3 036-0 3EF1 048-0A 3EF3 048-0 3EF1 072-0A 3EF3 072-0 3EF1 120-1 3EF1 150-0A 3EF1 036-0A 3EF3 036-0 3EF1 048-0A 3EF3 048-0 3EF1 072-0A 3EF3 072-0 3EF1 120-1 3EF1 150-0A 3EF1 036-0A 3EF3 036-0 3EF1 048-0A 3EF3 048-0 3EF1 072-0A 3EF3 072-0 3EF1 120-1 3EF1 150-0A
HG21-2213 eps
Siemens HG 21 2007
11
Description
Dielectric strength and standards
Dielectric strength
HG11-2517c_en eps
1.40
1.30
The dielectric strength of air insulation decreases with increasing altitude due to low air density. According to IEC 60694, the rated lightning impulse withstand voltage values specified in the chapter Technical Data apply to a site altitude of 1000 m above sea level. For an altitude above 1000 m, the insulation level must be corrected according to the opposite diagram. The characteristic shown applies to the rated short-duration power-frequency withstand voltage and the rated lightning impulse withstand voltage. To select the devices, the following applies: U U0 x Ka
U Rated withstand voltage under standard reference atmosphere U0 Rated withstand voltage requested for the place of installation Ka Altitude correction factor according to the opposite diagram
1.20
1.10
1.00 1000
1500
2000
2500
Example For a requested rated lightning impulse withstand voltage of 75 kV at an altitude of 2500 m, an insulation level of 90 kV under standard reference atmosphere is required as a minimum: 90 kV 75 kV x 1.2 Standards 3EE surge arresters conform to the following specifications and recommendations: IEC 60099-4 3EF1 and 3EF3 surge limiters are special devices which are not described by any of the standards applicable today. However, they are designed, manufactured and tested to a large extent in accordance with IEC 60099-4.
12
Siemens HG 21 2007
Equipment Selection
Contents
Contents
Page
Equipment Selection
Ordering data and configuration example Selection of 3EE arresters: Arresters for motors Arresters for generators Arresters for furnace transformers Accessories for arresters Selection of 3EF limiters: Voltage level 3.6 kV Voltage level 4.8 kV
R-HG21-101.eps
13
14
15 18 20 21
22 22 22 22 22
R-HG21-102.eps
Siemens HG 21 2007
13
Equipment Selection
Ordering data and configuration example
Order number structure The surge arresters and surge limiters are described by an order number consisting of 8 to 11 digits. The positions 12 to 16 which are normally used for the 16-digit order number are not required.
Special versions () There are special arrester versions available. In this case, -Z is added to the order number and a descriptive code for the special version follows (6-arrester connection, or suspended respectively horizontal installation).
2
1st position 2nd position 3rd position Primary part Superior group Switching devices Main group Overvoltage protection devices Subgroup Machine and special arresters/limiters Basic equipment Arrester ratings Limiter ratings Components for special versions () Initiated with -Z Type of special version in clear text
n: numerical
6 7 8 9 10 11
Configuration example In order to simplify the selection of the correct order number for the requested arrester or limiter, you will find a configuration example on each page of the chapter Equipment Selection. On the foldout page we offer a configuring aid. Here you can fill in the order number you have determined for your arrester or limiter.
C A 0
14
Siemens HG 21 2007
Equipment Selection
Selection of 3EE arresters
Position: Order No.: Rated voltage Ur kV 5.6 Short-circuit current capability (0.2 s) kA 50 63 100 200 50 63 100 200 50 63 100 200 50 63 100 200 300 kJ / kV 8 8 8 8 8 8 8 8 8 8 8 8 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 Energy absorption capacity
10 11
2 n n n n n n n
7.5
7.2
9.6
12
12
15
15
19
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
5 5 5 5 7 7 7 7 9 9 9 9 2 2 2 2 2 2 2 2 2 2 5 5 5 5 5 5 5 5 5 5 9 9 9 9 9 9 9 9 9 9
6 6 6 6 5 5 5 5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A
A B C D A B C D A B C D A A B B C C D D E E A A B B C C D D E E A A B B C C D D E E
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1
Configuration example 3EE2 surge arrester Maximum continuous operating voltage Uc = 7.2 kV Rated voltage Ur = 9 kV Short-circuit current capability 100 kA / 0.2 s Energy absorption capacity 8 kJ/kV Version for motors Example for Order No.: Special version:
0 3 E E 2 0
9 9
0 0
1 1
A C A C
0 0
Siemens HG 21 2007
15
Equipment Selection
Selection of 3EE arresters
Position: Order No.: Rated voltage Ur kV 23 Short-circuit current capability (0.2 s) kA 50 63 100 200 300 kJ / kV 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 Energy absorption capacity
10 11
2 n n n n n n n
22
27
24
30
27
34
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
3 3 3 3 3 3 3 3 3 3 7 7 7 7 7 7 7 7 7 7 0 0 0 0 0 0 0 0 0 0 4 4 4 4 4 4 4 4 4 4
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A
A A B B C C D D E E A A B B C C D D E E A A B B C C D D E E A A B B C C D D E E
0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1
Configuration example 3EE2 surge arrester Maximum continuous operating voltage Uc = 22 kV Rated voltage Ur = 27 kV Short-circuit current capability 50 kA / 0.2 s Energy absorption capacity 10 kJ/kV Version for motors Example for Order No.: Special version:
2 3 E E 2 2
7 7
0 0
2 A A 0 2 A A 0
16
Siemens HG 21 2007
Equipment Selection
Selection of 3EE arresters
Position: Order No.: Rated voltage Ur kV 38 Short-circuit current capability (0.2 s) kA 50 63 100 200 300 kJ / kV 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 Energy absorption capacity
10 11
2 n n n n n n n
36
45
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
E E E E E E E E E E E E E E E E E E E E
E E E E E E E E E E E E E E E E E E E E
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
3 3 3 3 3 3 3 3 3 2 4 4 4 4 4 4 4 4 4 4
8 8 8 8 8 8 8 8 8 8 5 5 5 5 5 5 5 5 5 5
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
A A A A A A A A A A A A A A A A A A A A
A A B B C C D D E E A A B B C C D D E E
0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1
Configuration example 3EE2 surge arrester Maximum continuous operating voltage Uc = 36 kV Rated voltage Ur = 45 kV Short-circuit current capability 100 kA / 0.2 s Energy absorption capacity 8 kJ/kV Version for motors Example for Order No.: Special version:
4 3 E E 2 4
5 5
0 0
1 1
A C A C
0 0
Siemens HG 21 2007
17
Equipment Selection
Selection of 3EE arresters
Position: Order No.: Rated voltage Ur kV 5.6 Short-circuit current capability (0.2 s) kA 50 63 100 200 50 63 100 200 50 63 100 200 50 63 100 200 300 kJ / kV 8 8 8 8 8 8 8 8 8 8 8 8 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 Energy absorption capacity
10 11
2 n n n n n n n
7.5
7.2
9.6
12
12
15
15
19
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
5 5 5 5 7 7 7 7 9 9 9 9 2 2 2 2 2 2 2 2 2 2 5 5 5 5 5 5 5 5 5 5 9 9 9 9 9 9 9 9 9 9
6 6 6 6 5 5 5 5 5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B
A B C D A B C D A B C D A A B B C C D D E E A A B B C C D D E E A A B B C C D D E E
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1
Configuration example 3EE2 surge arrester Maximum continuous operating voltage Uc = 15 kV Rated voltage Ur = 19 kV Short-circuit current capability 300 kA / 0.2 s Energy absorption capacity 10 kJ/kV Version for generators Example for Order No.: Special version:
1 3 E E 2 1
9 9
0 0
2 2
B B
E E
1 1
18
Siemens HG 21 2007
Equipment Selection
Selection of 3EE arresters
Position: Order No.: Rated voltage Ur kV 23 Short-circuit current capability (0.2 s) kA 50 63 100 200 300 kJ / kV 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 Energy absorption capacity
10 11
2 n n n n n n n
22
27
24
30
27
34
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
3 3 3 3 3 3 3 3 3 3 7 7 7 7 7 7 7 7 7 7 0 0 0 0 0 0 0 0 0 0 4 4 4 4 4 4 4 4 4 4
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B
A A B B C C D D E E A A B B C C D D E E A A B B C C D D E E A A B B C C D D E E
0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1
Configuration example 3EE2 surge arrester Maximum continuous operating voltage Uc = 27 kV Rated voltage Ur = 34 kV Short-circuit current capability 63 kA / 0.2 s Energy absorption capacity 10 kJ/kV Version for generators Example for Order No.: Special version:
3 3 E E 2 3
4 4
0 0
2 2
B B
B B
0 0
Siemens HG 21 2007
19
Equipment Selection
Selection of 3EE arresters
Position: Order No.: Rated voltage Ur kV 38 Short-circuit current capability (0.2 s) kA 50 63 100 200 300 kJ / kV 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 8 10 Energy absorption capacity
10 11
2 n n n n n n n
36
45
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
E E E E E E E E E E E E E E E E E E E E
E E E E E E E E E E E E E E E E E E E E
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4
8 8 8 8 8 8 8 8 8 8 5 5 5 5 5 5 5 5 5 5
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
B B B B B B B B B B B B B B B B B B B B
A A B B C C D D E E A A B B C C D D E E
0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1
Configuration example 3EE2 surge arrester Maximum continuous operating voltage Uc = 42 kV Rated voltage Ur = 52 kV Short-circuit current capability 50 kA / 0.2 s Energy absorption capacity 10 kJ/kV Version for furnace transformers Special version: 6-arrester connection Example for Order No.: Special version:
C A 0 Z Z
C A 0
6-arrester connection
20
Siemens HG 21 2007
Equipment Selection
Selection of 3EE arresters
Accessories for arresters The order numbers are applicable to surge arresters and surge limiters of current manufacture. When components or spare parts are being ordered for existing arresters and limiters, always quote the type designation and the year of manufacture of the arrester or limiter to be sure to get the correct delivery. Note: Spare parts must only be replaced by instructed personnel.
Designation
Remarks
Order No.
Suitable for arrester type 3EE according to dimension drawing 1 or 2 (see chapter Technical data, page 26) Suitable for arrester type 3EE according to dimension drawing 1 or 2 (see chapter Technical data, page 26) Suitable for arrester type 3EE according to dimension drawing 3 (see chapter Technical data, page 26)
30 mm, complete with set of screws complete with set of screws complete with set of screws
Siemens HG 21 2007
21
Equipment Selection
Selection of 3EF limiters
3.6 kV
50/60 Hz Rated voltage Ur kV 3.6 3.6 Continuous operating voltage Uc kV 2.9 3.2 kJ / kV 0.8 4
F n n n n n n
3 3
E E
F F
1 3
0 0
3 3
6 6
0 A 0
4.8 kV
50/60 Hz Ur kV Uc kV 3.6 4.1 kJ / kV 0.8 4 3 3 E E F F 1 3 0 0 4 4 8 8 0 A 0
4.8 4.8
7.2 kV
50/60 Hz Ur kV 7.2 7.2 7.2 Uc kV 5.4 6.1 4.9 kJ / kV 0.8 4 4 3 3 3 E E E F F F 1 3 3 0 0 0 7 7 7 2 2 2 0 A 0 1
12 kV
50/60 Hz Ur kV 12 12 12 Uc kV 9 10.2 8.2 kJ / kV 0.8 4 4 3 3 3 E E E F F F 1 3 3 1 1 1 2 2 2 0 0 0 0 A 0 1
15 kV
50/60 Hz Ur kV 15 Uc kV 11 kJ / kV 0.8 3 E F 1 1 5 0 0 A
Configuration example 3EF surge limiter Rated voltage Ur = 12 kV Continuous operating voltage Uc = 10.2 kV Energy absorption capacity 4 kJ/kV Example for Order No.: Special version:
3 3 E F 3
1 1
2 2
0 0
0 0
22
Siemens HG 21 2007
Technical Data
Contents
Contents
Page
Technical Data
Electrical data, dimensions and weights: Arresters Limiters
23
24 27
R-HG21-105.eps
R-HG21-106.eps
Siemens HG 21 2007
23
Technical Data
Electrical data, dimensions and weights: 3EE arresters
1 kA waveshape 30/60 s
5 kA waveshape 8/20 s
10 kA waveshape 8/20 s
20 kA waveshape 8/20 s
Creepage distance
Arcing distance
Rated voltage
Order No.
Ur kV 3EE2 056-ooA0 3EE2 056-ooB0 3EE2 056-ooC0 3EE2 056-ooD0 3EE2 075-ooA0 3EE2 075-ooB0 3EE2 075-ooC0 3EE2 075-ooD0 3EE2 090-ooA0 3EE2 090-ooB0 3EE2 090-ooC0 3EE2 090-ooD0 3EE2 120-ooA0 5.6 5.6 5.6 5.6 7.5 7.5 7.5 7.5 9 9 9 9 12 12 12 12 12 15 15 15 15 15 19 19 19 19 19 22 23 23 23 23 23 27 27 27 27 27
Uc kV 4.5 4.5 4.5 4.5 6 6 6 6 7.2 7.2 7.2 7.2 9.6 9.6 9.6 9.6 9.6 12 12 12 12 12 15 15 15 15 15 17.5 18 18 18 18 18 22 22 22 22 22
(0.2 s) kA 50 63 100 200 50 63 100 200 50 63 100 200 50 63 100 200 300 50 63 100 200 300 50 63 100 200 300 50 50 63 100 200 300 50 63 100 200 300 kJ/kV 8 8 8 8 8 8 8 8 8 8 8 8 8/10 8/10 8/10 8/10 8/10 8/10 8/10 8/10 8/10 8/10 8/10 8/10 8/10 8/10 8/10 10 8/10 8/10 8/10 8/10 8/10 8/10 8/10 8/10 8/10 8/10 kV cr 11.5 11.5 11.5 11.5 15.5 15.5 15.5 15.5 18.5 18.5 18.5 18.5 25 25 25 25 25 31.5 31.5 31.5 31.5 31.5 39.5 39.5 39.5 39.5 39.5 43 48 48 48 48 48 56 56 56 56 56 kV cr 12 12 12 12 16 16 16 16 19.5 19.5 19.5 19.5 26 26 26 26 26 33 33 33 33 33 41 41 41 41 41 45 49 49 49 49 49 58 58 58 58 58 kV cr 13 13 13 13 18 18 18 18 22 22 22 22 29 29 29 29 29 37 37 37 37 37 49 49 49 49 49 50 55 55 55 55 55 65 65 65 65 65 kV cr 14 14 14 14 19 19 19 19 23 23 23 23 31 31 31 31 31 39 39 39 39 39 49 49 49 49 49 53 59 59 59 59 59 69 69 69 69 69 kV cr 16 16 16 16 21 21 21 21 26 26 26 26 35 35 35 35 35 44 44 44 44 44 55 55 55 55 55 59 66 66 66 66 66 77 77 77 77 77
Up kV 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 220 150 150 150 150 220 150 150 150 150 220 150 150 150 150 150 220 150 150 150 150 220 kV 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 105 80 80 80 80 105 80 80 80 80 105 80 80 80 80 80 105 80 80 80 80 105 kV 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 90 65 65 65 65 90 65 65 65 65 90 65 65 65 65 65 90 65 65 65 65 90 mm 255 255 255 255 255 255 255 255 255 255 255 255 255 255 255 255 360 255 255 255 255 360 255 255 255 255 360 255 255 255 255 255 360 255 255 255 255 360 mm 605 605 605 605 605 605 605 605 605 605 605 605 605 605 605 605 640 605 605 605 605 640 605 605 605 605 640 605 605 605 605 605 640 605 605 605 605 640 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 3 1 1 1 1 3 1 1 1 1 1 3 1 1 1 1 3 kg 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 75 30 30 30 30 75 30 30 30 30 75 30 30 30 30 30 75 30 30 30 30 85
3EE2 120-ooB0 3EE2 120-ooC0 3EE2 120-ooD0 3EE2 120-ooE1 3EE2 150-ooA0 3EE2 150-ooB0 3EE2 150-ooC0 3EE2 150-ooD0 3EE2 150-ooE1 3EE2 190-ooA0 3EE2 190-ooB0 3EE2 190-ooC0 3EE2 190-ooD0 3EE2 190-ooE1 3EE2 220-ooA0 3EE2 230-ooA0 3EE2 230-ooB0 3EE2 230-ooC0 3EE2 230-ooD0 3EE2 230-ooE1 3EE2 270-ooA0 3EE2 270-ooB0 3EE2 270-ooC0 3EE2 270-ooD0 3EE2 270-ooE1
24
Siemens HG 21 2007
Weights
Technical Data
Electrical data, dimensions and weights: 3EE arresters
1 kA waveshape 30/60 s
5 kA waveshape 8/20 s
10 kA waveshape 8/20 s
20 kA waveshape 8/20 s
Creepage distance
Arcing distance
Rated voltage
Order No.
Ur kV 3EE2 300-ooA0 3EE2 300-2CA0 3EE2 300-ooB0 3EE2 300-ooC0 3EE2 300-ooD0 3EE2 300-ooE1 3EE2 320-ooA0 3EE2 340-ooA0 3EE2 340-ooB0 3EE2 340-ooC0 3EE2 340-ooD0 3EE2 340-ooE1 3EE2 360-ooA0 3EE2 380-ooA0 3EE2 380-ooB0 3EE2 380-ooC0 3EE2 380-ooD0 3EE2 380-ooE1 3EE2 450-ooA0 3EE2 450-2CA0 3EE2 450-ooB0 3EE2 450-ooC0 3EE2 450-ooD0 3EE2 450-ooE1 3EE2 520-2CA0 30 30 30 30 30 30 32 34 34 34 34 34 36 38 38 38 38 38 45 45 45 45 45 45 52
Uc kV 24 24 24 24 24 24 24 27 27 27 27 27 29 30 30 30 30 30 36 36 36 36 36 36 42
(0.2 s) kA 50 50 63 100 200 300 50 50 63 100 200 300 50 50 63 100 200 300 50 50 50 50 50 50 50 kJ/kV 8/10 10 8/10 8/10 8/10 8/10 10 8/10 8/10 8/10 8/10 8/10 10 8/10 8/10 8/10 8/10 8/10 8/10 10 8/10 8/10 8/10 8/10 10 kV cr 62 59 62 62 62 62 63 70 70 70 70 70 71 78 78 78 78 78 92 88 92 92 92 92 100 kV cr 64 61 64 64 64 64 65 73 73 73 73 73 74 81 81 81 81 81 96 91 96 96 96 96 105 kV cr 72 66 72 72 72 72 73 82 82 82 82 82 82 91 91 91 91 91 108 102 108 108 108 108 118 kV cr 77 72 77 77 77 77 77 87 87 87 87 87 87 97 97 97 97 97 115 108 115 115 115 115 125 kV cr 86 80 86 86 86 86 86 97 97 97 97 97 97 109 109 109 109 109 129 120 129 129 129 129 139
Up kV 240 150 240 240 204 220 150 240 240 240 240 240 240 240 240 240 240 220 240 240 240 240 240 220 240 kV 130 80 130 130 130 105 80 130 130 130 130 105 130 130 130 130 130 105 130 130 130 130 130 105 130 kV 110 65 110 110 110 90 65 110 110 110 110 90 110 110 110 110 110 90 110 110 110 110 110 90 110 mm 435 255 435 435 435 360 255 435 435 435 435 360 435 435 435 435 435 360 435 435 435 435 435 360 435 mm 1095 605 1095 1095 1095 640 605 1095 1095 1095 1095 640 1095 1095 1095 1095 1095 640 1095 1095 1095 1095 1095 640 1095 2 1 2 2 2 3 1 2 2 2 2 3 2 2 2 2 2 3 2 2 2 2 2 3 2 kg 40 30 40 40 40 85 30 40 40 40 40 85 40 40 40 40 40 85 40 40 40 40 40 85 40
Weights
Siemens HG 21 2007
25
Technical Data
Electrical data, dimensions and weights: 3EE arresters
M16 ( 19)
M12 (2x)
31)
191 230
500
A
30
B
191 230 200 260 319
HG21-2205 eps
147
Dimension drawing 1
Top view
Section A B
31)
13
M16 ( 19)
M12 (2x)
680
191 230
A
30
B
191 230 200 260 319
HG21-2206 eps
147
Dimension drawing 2
Top view
Section A B
200 260
60
200 260
60
25
3
114 13
100 50
14
50
18
M 20 ( 23)
M12 x 30 (2x)
270
675
B
270 310 390 463
HG21-2207 eps
215 30
Dimension drawing 3
Top view
Section A B
100 25 50
14 13
80
191 230
114 50
310 390
60
191 230
Bolt terminal Top view 3EX6 006 for housing sizes 1 and 2
Top view
26
Siemens HG 21 2007
HG21-2209 eps
191 230
HG21-2208 eps
191 230
Technical Data
Electrical data, dimensions and weights: 3EF limiters
Ur kV 3EF1 036-0A 3EF1 048-0A 3EF1 072-0A 3EF1 120-0A 3EF1 150-0A 3EF3 036-0 3EF3 048-0 3EF3 072-0 3EF3 072-1 3EF3 120-0 3EF3 120-1 3.6 4.8 7.2 12 15 3.6 4.8 7.2 7.2 12 12
Ua kV 8 10 15 25 31 8 10 15 12 25 20
Ures kV 8 10 15 25 31 8 10 15 12 25 20 kJ/kV 0.8 0.8 0.8 0.8 0.8 4 4 4 4 4 4 kg 0.73 0.73 0.73 1.2 1.2 3 3.5 4 4 5 5 4 4 4 5 5 6 6 6 6 6 6
Rated voltage
Order No.
Weights
3
Dimension drawings for 3EF surge limiters
M8 90 M10
16
30
91
HG21-2210 eps
16
120
Dimension drawing 4
67
M8
16
255
63
70
110
169
63
HG21-2211 eps
16
Dimension drawing 5
Dimension drawing 6
30
HG21-2212a eps
28
Siemens HG 21 2007
27
28
Siemens HG 21 2007
R-HG21-107.tif
Annex
Contents
Contents
Page
Annex
Inquiry form Configuration instructions Configuration aid
29
30 31 Foldout page
R-HG11-180.eps
Siemens HG 21 2007
29
Annex
Inquiry form
Inquiry concerning
Please
o o o o
4.5 kV 12 kV 22 kV 29 kV
o o o o
6 kV 15 kV 24 kV 30 kV
o o o o
7.2 kV 17.5 kV 26 kV 36 kV
Earthing type
o Resonantearthed neutral
Your address
Company Dept. Name Street Postal code/city Phone Fax E-mail
o 63 kA/0.2 s
o 10 kJ/kV o Generator
Other values o _ _ _ kV o 3.6 kV o 6.1 kV o 11 kV o 4.1 kV o 8.2 kV o _ _ _ kV o _ _ _ kJ/kV o Power station or extensive cable system
Siemens AG
Other requirements
Dept. Name Street Postal code/city Fax
_ _ _ Please fill in
30
Siemens HG 21 2007
10 11
E n n n n n n n n n
Rated voltage (Ur) Short-circuit current capability Energy absorption capacity Application These ratings define the positions 5 to 11 of the order number.
Rated voltage Maximum continuous operating voltage Energy absorption capacity These equipment features define the positions 4 to 9 of the order number.
31
page 22
to
If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm.
Siemens AG Power Transmission and Distribution Medium Voltage Division Nonnendammallee 104 13623 Berlin Germany www.siemens.com/energy
For questions concerning Power Transmission and Distribution: You can contact our Customer Support Center 24 hours a day, 365 days a year. Tel.: +49 180/524 70 00 Fax: +49 180/524 24 71 (Charges depending on provider) E-Mail: support.energy@siemens.com www.siemens.com/energy-support
Subject to change without notice Order No. E50001-K1521-A101-A1-7600 Printed in Germany Dispo 31601 KG 11.07 4.0 32 En 102813 6101/6492
Responsible for Technical contents: Siemens AG, Dept. PTD M C PPM Berlin General editing: Siemens AG, Dept. PTD CC M Erlangen
R-HG21-100.tif
The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases. The required features should therefore be specified in each individual case at the time of closing the contract.