Room Air ZQ08-10 CP08!10!12 SVC Parts Manual 5-06
Room Air ZQ08-10 CP08!10!12 SVC Parts Manual 5-06
Room Air ZQ08-10 CP08!10!12 SVC Parts Manual 5-06
ZQ08C10
ZQ10C10
CP08C 10
CP10C 10
CP12C 10
CONTENTS
1. PREFACE
1.1 SAFETY PRECAUTIONS................................2 1.2 INSULATION RESISTANCE TEST .................2 1.3 SPECIFICATIONS...........................................3 1.4 FEATURES......................................................4 1.5 CONTROL LOCATIONS .................................4
3. TROUBLESHOOTING GUIDE
3.1 PIPING SYSTEM...........................................13 3.2 TROUBLESHOOTING GUIDE .....................14
2. DISASSEMBLY INSTRUCTIONS
2.1 MECHANICAL PARTS ....................................6 2.1.1 FRONT GRILLE .....................................6 2.1.2 CABINET ................................................6 2.1.3 CONTROL BOX .....................................6 2.2 AIR HANDLING PARTS ..................................7 2.2.1 AIR GUIDE AND TURBO FAN ...............7 2.2.2 FAN ........................................................7 2.2.3 SHROUD ................................................8 2.3 ELECTRICAL PARTS......................................8 2.3.1 OVERLOAD PROTECTOR ....................8 2.3.2 COMPRESSOR......................................8 2.3.3 CAPACITOR...........................................9 2.3.4 POWER CORD ......................................9 2.3.5 MOTOR ................................................10 2.4 REFRIGERATION CYCLE ............................10 2.4.1 CONDENSER.......................................10 2.4.2 EVAPORATOR.....................................10 2.4.3 CAPILLARY TUBE ...............................11
1. PREFACE
This SERVICE MANUAL provides various service information, including the mechanical and electrical parts etc. This room air conditioner was manufactured and assembled under a strict quality control system. The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.
1.3 SPECIFICATIONS
1.3.1 F OR ZQ08C 10,ZQ10C 10,C P 08C 10,C P 10C 10,C P 12C 10
MODE L S IT E MS P OWE R S UP P LY C OOLING C AP AC IT Y INP UT R UNNING C UR R E NT E .E .R OP E R AT ING C ONDIT ION (B tu/h) (W) (A) (B T U/W.h) INDOOR ( C ) OUT DOOR ( C )
ZQ08C 10
ZQ10C 10
C P 08C10
1, 115V, 60HZ
C P 10C10
C P 12C10
23.9(WB )** 420g(14.8oz) 525g(18.5oz) 510g(18.0oz) 2 ROW 10STACKS 3 ROW 12STACKS 2 ROW 17STACKS 2 ROW 17STACKS(L)
R E F R IG E R ANT (R -22) C HAR G E E VAP OR AT OR C ONDE NS E R F AN, INDOOR F AN, OUT DOOR F AN S P E E DS , F AN/C OOLING F AN MOT OR OP E R AT ION C ONT R OL R OOM T E MP . C ONT R OL AIR DIR E C T ION C ONT R OL C ONS T R UC T ION P R OT E C T OR C OMP R E S S OR F AN MOT OR
P R OP E LLE R TYP E FAN WITH S LINGE R R ING 2/3 6 P OLE S R OTAR Y S WITC H THE R MOS TAT R E MOTE C ONTR OLLE R THE R MIS TOR 3/3
V E R T IC AL LOUV E R (R IG HT & LE F T ) HOR IZONT AL LOUV E R (UP & DOWN) S LIDE IN-OUT C HAS S IS OV E R LOAD P R OT E C T OR INT E R NAL T HE R MAL P R OT E C T OR (3 WIR E WIT H G R OUDING ) AT T AC HME NT P LUG (C OR D-C ONNE C T E D T Y P E ) DR AIN P IP E OR S P LAS HE D B Y F AN S LING E R (lbs/kg) (inch) (mm) 62/28 203/32 x 13 29/32 x 193/8 510 x 354 x 490
P OWE R C OR D DR AIN S Y S T E M NE T WE IG HT OUT S IDE DIME NS ION (W x H x D) * DB :Dry B ulb **WB :Wet B ulb
1.4 FEATURES
Designed for COOLING ONLY. Slide-out chassis for the simple installation and service. Low air-intake, top cooled-air discharge.
CONTROLS -ZQMODELS
OPERATION (Fig A) OFF MED FAN LOW FAN : Turns the air conditioner off.
5
: Medium fan speed without cooling. : Low fan speed without cooling.
MED FAN
HIGH COOL
4 3 2
6 7
8 1 9
LOW FAN
HIGH COOL : Cooling with the high fan speed. MED COOL : Cooling with the medium fan speed. LOW COOL : Cooling with the low fan speed.
Fig A
DIS P L AY
2 6
R E MOT E C ONT R OL
Power
1
Te mp
2
Fan S peed
4 3
T imer
Mode
Fig B
Fig C
Precaution: The Remote Control unit will not function properly if strong light shines on the sensor window of the air conditioner or if there are obstacles between the Remote Control unit and the air conditioner. Refer to Fig B&Fig C POWER BUTTON To turn the air conditioner ON and OFF. This button takes priority over any other buttons. TEMPERATURE SETTING BUTTON This button can control temperature of the room. The temperature can be adjusted within a range of 60 F to 86 F by 1F,Select the lower number for lower temperature of the room.
o o o
OPERATION MODE SELECTION BUTTON Push this button, it will shift operation between COOL, ENERGY SAVER, FAN and DRY modes. - Energy Saver: If Energy Save mode is selected, the fan stops when the compressor stops running Approximately every 3 minutes the fan will turn on and check the room air to determine if cooling is needed. FAN SPEED SELECTOR Push this button, to shift fan speeds, as follows. (Hi Low Med Hi Low ...) ON/OFF TIMER BUTTON ON - When the air conditioner is off, it can be set to automatically turn on. OFF - When the airconditioner is on, it can be set to automatically turn off.
2. DISASSEMBLY INSTRUCTIONS
Before servicing the unit,turn the unit OFF and disconnet the power cord.
2.1.2 CABINET
1. After removing the FRONT GRILLE, remove the 2 screws which fasten the cabinet at both sides. 2. Remove the 2 screws which fasten the cabinet at the back. 3. Pull the base pan forward. (See Figure 2) 4. Remove the cabinet. 5. Re-install the components by referring to the removal procedure, above. Figure 1
INDO OR
FAN
DES
DEF ROS T ENE RGY SAV ER AIR PUR YFIE AUT R RES O TAR T
IRED
FAN SPE ED
MO
DE TEM P POW ER
COO L
INDO OR
FAN
DEF ROS T
DES IRED
TIM E
FAN SPE ED
MO DE TEM P POW ER
Figure 4
Figure 5
2.2.2 FAN
1. Remove the cabinet. (Refer to section 2.1.2) 2. Remove the brace (Refer to section 2.2.1) 3. Remove the 5 screws which fasten the condenser. 4. Move the condenser to the left carefully. 5. Remove the clamp which secures the fan. 6. Remove the fan. (See Figure 7) 7. Re-install by referring to the removal procedure.
Figure 6
Figure 7 7
2.2.3 SHROUD
1. Remove the fan. (Refer to section 2.2.2) 2. Remove the shroud. (See Figure 8) 3. Re-install the components by referring to the removal procedure, above.
Figure 8
Figure 9
2.3.2 COMPRESSOR
1. Remove the cabinet. (Refer to section 2.1.2) 2. Discharge the refrigerant system using a FreonTM Recovery System. If there is no valve to attach the recovery system to, install one (such as a WATCO A-1) before venting the FreonTM. Remove the valve when finished 3. Remove the overload protector. (Refer to section 2.3.1) 4. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections. 5. Remove the 3 nuts and the 3 washers which fasten the compressor. 6. Remove the compressor. (See Figure 10) 7. Re-install the components by referring to the removal procedure, above.
Figure 10
2.3.3 CAPACITOR
1. Remove the control box. (Refer to section 2.1.3) 2. Open the top cover from the control box. (See Figure 11) 3. Pull out the capacitor from the control box. 4. Disconnect all the leads of capacitor terminals. 5. Re-install the components by referring to the removal procedure, above.
CO OL
FA N
DR Y
IN DO OR
FA N
DES IR ED
Figure 11
CO
IND OOR
FA
DEF ROS T ENE RGY SAV ER AIR PUR YFIE AUT R RES O TAR T
DES IRE D
TIM E
FAN SPE ED
MO DE TEM P PO WE R
Figure 12
2.3.5 MOTOR
1. Remove the cabinet. (Refer to section 2.1.2) 2. Remove the turbo fan. (Refer to section 2.2.1) 3. Remove the fan. (Refer to section 2.2.2) 4. Remove the 4 screws which fasten the motor to the air guide. (See Figure 13) 5. Remove the motor. 6. Re-install the components by referring to the removal procedure, above.(See Figure 13)
2.4.2 EVAPORATOR
1. Remove the control box.(Refer to section 2.1.3) 2. Remove the air guide upper. (Refer to section 2.2.1) 3. Remove the 2 screws which fasten the evaporator. 4. Move the evaporator sideways carefully. (Refer to section 2.2.1) 5. After discharging the refrigerant completely, unbraze the interconnecting tube at the evaporator connections. 6. Remove the evaporator. 7. Re-install the components by referring to notes. (See Figure 15)
Figure 14
Figure 15
10
NOTES Replacement of the refrigeration cycle. 1. When replacing the refrigeration cycle, be sure to Discharge the refrigerant system using a FreonTM recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Remove the valve when finished. 2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes. 3. Solder service valves into the pinch-off tube ports, leaving the valves open. 4. Evacuate as follows. 1) Connect the vacuum pump, as illustrated figure 16A. 2) Start the vacuum pump, slowly open manifold valves A and B with two full turns counterclockwise and leave the valves open. The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold and entire system. CAUTION If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump. 3) Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vacuum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump. 4) Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 16B. Open valve C. Discharge the line at the manifold connection. 5) The system is now ready for final charging. 5. Recharge as follows : 1) Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened. 2) Connect the charging cylinder as shown in figure 16B. With valve C open, discharge the hose at the manifold connection. 3) Open valve A and allow the proper charge to enter the system. Valve B is still closed. 4) If more charge is required, the high-side will not take it. Close valve A. 5) With the unit running, open valve B and add the balance of the charge. a. Do not add the liquid refrigerant to the Lowside. b. Watch the Low-side gauge; allow pressure to rise to 30 lbs. c. Turn off valve B and allow pressure to drop. d. Repeat steps b. and c. until the balance of the charge is in the system. 6) When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test for any leaks at the pinch-off connection.
11
Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment, Pinch-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valves.
B
CAPILLARY TUBE
COMPRESSOR
LOW
HI
A B
EXTERNAL VACUUM PUMP CHARGING CYLINDER
Figure 16B-Charging
12
3. TROUBLESHOOTING GUIDE
3.1 OUTSIDE DIMENSIONS
unit: mm(inch)
MODEL: ZQ08B10,CP08A10,ZQ10B10
490(19 3/8" ) 29(1 5 /32") 126.5(431/32")
510 20 3 32
COOL FAN DRY HEAT DEFROST
FAN
INDOOR DESIRED
354(13 /32")
29
18(23/32")
MODEL:CP10A10,CP12A10
600 23 5
FAN
INDOOR DESIRED
380(14 /32")
31
18(23/32")
13
TURBO FAN
EVAPORATOR COIL
Figure 17 is a brief description of the important components and their function in what is called the refrigeration system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.
EVAPORATOR COILS
COMPLETE LIQUID BOIL OFF POINT COOLED AIR SUCTION LINE COOL LOW PRESSURE VAPOR
CONDENSER COILS
VAPOR INLET HOT DISCHARGED AIR
MOTOR
COMPRESSOR
OIL
LIQUID OUTLET
(LIQUID REFRIGERANT) CAPILLARY TUBE
Figure 17 14
Fails to Start
Improper wiring. Drop of voltage. Improper thermostat setting. Bad capacitor. Defect of fan motor capacitor.
CAUSE
REMEDY Check voltage at outlet. Correct if none. Check voltage to rotary switch. If none, check power supply cord. Replace cord if circuit is open. Check switch continuity. Refer to wiring diagram for terminal identification. Replace switch if defective. Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal. Test capacitor. Replace if not within 10% of manufacturer's rating. Replace if shorted, open, or damaged. Fan blade hitting shroud or blower wheel hitting scroll. Realign assembly. Units using slinger ring for condenser fan must have 1 /4 to 5/16 inch clearance to the base. If it hits the base, shim up the bottom of the fan motor with mounting screw(s). Check fan motor bearings; if motor shaft will not rotate, replace the motor.
Power supply cord Rotary switch Wire disconnected or connection loose Capacitor (Discharge capacitor before testing.) Will not rotate
Revolves on overload.
Check voltage. If not within limits, call an electrician. Test capacitor. Check bearings. Does the fan blade rotate freely? If not, replace fan motor. Pay attention to any change from high speed to low speed. If the speed does not change, replace the motor.
If cracked, out of balance, or partially missing, replace it. If cracked, out of balance, or partially missing, replace it. Tighten it. If knocking sounds continue when running or loose, replace the motor. If the motor hums or noise appears to be internal while running, replace motor. Check voltage. If not within limits, call an electrician. Check the wire connections, if loose, repair or replace the terminal. If wires are off, refer to wiring diagram for identification, and replace. Check wire locations. If not per wiring diagram, correct. Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if circuit is open.
Voltage Wiring
Rotary
16
CAUSE Thermostat
REMEDY Check the position of knob. If not at the coldest setting, advance the knob to this setting and restart unit. Check continuity of the thermostat. Replace thermostat if circuit is open. Check the capacitor. Replace if not within 10% of manufacturers rating. Replace if shorted, open, or damaged. Check the compressor for open circuit or ground. If open or grounded, replace the compressor. Check the compressor overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool it, and retest.) Check the voltage. If not within limits, call an electrician. Check overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.) If not running, determine the cause. Replace if required. Remove the cabinet. inspect the interior surface of the condenser; if restricted, clean carefully with a vacuum cleaner (do not damage fins) or brush. Clean the interior base before reassembling. If condenser fins are closed over a large area on the coil surface, head pressures will increase, causing the compressor to overload. Comb the fins or replace the coil. Test capacitor. Check the terminals. If loose, repair or replace. Check the system for a restriction. If restricted, blow out system or replace component. Close if open. Determine if the unit is properly sized for the area to be cooled. Check the set screw or clamp. If loose or missing, correct. If the blower or fan is hitting air guide, rearrange the air handling parts. Remove the cabinet carefully and rearrange tubing not to contact cabinet, compressor, shroud, and barrier.
Voltage Overload
Excessive noise
Blower or fan
Copper tubing
17
4. SCHEMATIC DIAGRAM
MODEL: ZQ08C10,ZQ10C10
1
GN/YL (GN)
MOTOR
RY-LOW
RY-MED
RY-HI
BK BL RD YL OR
CN-MOTOR
CN-AC/DC
CN-AC/DC
5
DC PCB ASSEMBLY
CN-TH1
POWER INPUT BK(BR) WH(BL) (Plain) (Ribbed) ROTARY SWITCH 7 8 L 6 H RD BK BL RD BK BL OR(BR) YL YL CAPACITOR F C GN(GN/YL)
CAPACITOR
YL
9
1
4 M 2
MOTOR
F C OR(BR) BK H WH(BL) (Ribbed) BK(BR) (Plain) GN/YL (GN) R S BL OLP RD CN-PWR ZNR01J POWER TRANS
7
THERMISTOR
OR(BR)
3
BL
BK S BR(YL) RD BL
BK RD BL RD P.T.C H BK
COMP.
C
3 4
RY-COMP
OLP THERMOSTAT
3 4
COMP.
C
AC PCB ASSEMBLY
WIRING DIAGRAM
3854AR3563N
WIRING DIAGRAM
3854AR3563A
S: Service Parts N: Non Service Parts LOCATION NO. 1 2 3 4 5 6 7 8 9 DESCRIPTION MOTOR ASSY CAPACITOR COMPRESSOR OVERLOAD PROTECTOR DC PCB ASSEMBLY AC PCB ASSEMBLY THERMISTOR THERMOSTAT ROTARY SWITCH Q'TY PER SET 1 1 1 1 1 1 1 1 1 REMARKS S S S S S S S S S
18
5. EXPLODED VIEW
749740 731373
554031
554030
W48602 559011
349001
349480 130410
567502
237200 135312
264110
554160
147582-2 147581
269310
266003
352113
19
ZQ10C10
ZQ08C10
CP08C 10
ZQ10C10 67302924 67303711 67306014 67306109 67300311 67304601 67306260 67306261
CP10C 10
CP08C10
CP12C 10
DESCRIPTION Base Assy Single Cabinet Assy Single Grille Assy Front Grille Assy Inlet Cover Link Louver Vertical Louver Vertical REMARK R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
---
Escutcheon Thermistor Thermostat Power Cord Assy Switch Rotary Remote Controller PWB(PCB) Assy Display PWB(PCB) Assy Main Motor Assy Single Orifice Air Guide Assy Upper Air Guide Assy Lower Isolator Comp Fan Blade Fan Turbo O.L.P. Capacitor Clamp Spring stallation Kit w/Curtain Upper Guide Cabinet
20
LocNo 130410 130910 135312 135313 135500 145200 147582-1 147582-2 149980 152302 238310 263230 264110 267110 268714 268712 346811 349480 352390-1 352390-2 550140 559011 359012 567502 W0CZZ W48602 731373 749740
CP10C10 67302923
CP12C10 67302922
DESCRIPTION Base Assy Single Cabinet Assy Single Grille Assy Front Grille Assy Inlet Cover Link Louver Vertical Louver Vertical Shroud Filter (Mech) Escutcheon Thermistor Power Cord Assy Remote Controller PWB(PCB) Assy Display PWB(PCB) Assy Main Motor Assy Single Orifice Air Guide Assy Upper Air Guide Assy Lower Isolator Comp Fan Fan Turbo O.L.P. Capacitor Clamp Spring Installation Kit w/Curtains Upper Guide Cabinet
REMARK R R R R R R R R R R R R R R R R R R R R R R R R R R R
67303710 67306013 67306108 67300310 67304602 67306258 67306259 67303113 67304307 67500116 67307807 67300023 67300024 67307701 67307613 67307614 67303030 67303035 67303411 67302729 67302730 67301901 67302614 67302615 67301419 67301416 67300716 67300720 67302500 67306308 67304006
21
MEMO
22
MEMO