CJX7 AC Contactor
1. Application
CJX7-9~300 AC contactor(hereafter refer to as contactor)is mainly used in power system with AC 50/60Hz, therated working voltage up to 660V, under the application category of AC-3, when the rated working voltage 380V, the rated operating current to 300A electrical, for the longdistance range making and breaking the electric circuit, and combines the electorm agnetism starter with the suitable thermal overload relay or the electronic protector to protect against the possible overload electric circuit during operation(running).
CJX7-09,16
very convenient and rapid. The electric conduction part does not appear externally, the security performance is good. 3.2 The working principle of contactor: control power source power source of making(breaking) contactor pullin coil, magnetism system produces(vanishes)electromagnetism suction to drive the moving part making and(breaking) circuit through then, realize the goal of control.
B-67
CJX7
4. Common Work Condition and Installing Condition
a. The installation site elevation does not surpass 2000m; b. Ambient air temperature should not over +40C, also not over +35C with in 24h, the lower limit of ambient air temperature is -5C; c. The air relative humidity at installation site should not over 50% when the maximum temperature is +40C; the higher relative humidity are allowed under lower temperature, for example, 90% at 20C, It must take the mesures on the product occuring dew because of the change of temperature. d. The installation site pollution class is 3; e. The contactor can be mounted vertically or horizontally. If vertically mounts, the gradient
CJX7-45,50
between the mounted surface and the perpendicular plans is not bigger than= 1)
CJX7-63
5. Technical Parameter
5.1 The allowable application category of main circuit and the auxiliary circuit of the contactor and its code see Table 1 Table 1 application category of main circuit and the auxiliary circuit of the contactor and its code
Circuit Application category code CJX7-1 CJX7-2 Main circuit CJX7-3 CJX7-4 CJX7-75 Auxiliary circuit CJX7-15 CJX7-13 Example of the typical usage Noninductive or the micro ineuductive load, resistance furnace The starting and breaking of wire winding type asynchronous motor The starting and breaking during operation of cage asynchronous motor The starting, plug breaking or reverse revolution, spot moving of cage asynchronous motor Control AC electromagnet load(>72VA) Control DC magnet load
5.2 Contactor rated insulation voltage(Ui), reted working voltage(Ue), conventional free air heat current(Ith), rated operating current(Ie) and rated work rate see Table 2.
B-68
CJX7
Table 2 main circuits basic parameters Frame code Rated insulation Convensional AC-3 rated operating current Ie A free air heat 220V 380V 660V 9 12 17 26 32 37 50 65 75 96 110 145 185 210 260 300 9 12 17 26 32 37 50 65 75 96 110 145 185 210 260 300 7 9 10 17 21 25 35 43 46 65 82 120 170 210 260 280 AC-3 control the max. power kW of generator 220V 2.2 3 4 6.5 9 11 15 18.5 22 25 30 40 50 60 78 88 380V 4 5.5 7.5 11 15 8.5 22 30 37 45 55 75 90 110 140 160 660V 5.5 6.5 9 15 18.5 22 30 37 40 55 75 100 120 150 190 220 Type voltage Ui V current Ith A 26 16 26 40 28 30 45 65 65 100 75 1000 125 125 110 185 145 160 250 275 350 300 400 450
CJX7-9 CJX7-12 CJX7-16 CJX7-26 CJX7-30 CJX7-40 CJX7-50 CJX7-63 CJX7-95,110 CJX7-75 CJX7-95 CJX7-110 CJX7-145 CJX7-185 CJX7-210 CJX7-260 CJX7-300
6. Installation
6.1 Correct install wiring Note that the terminal symbole: Main circuit 1L1,3L2,5L3 is incoming therminal; 2T1,4T2,6T3 outgoing terminal. The incoming terminal of NO auxiliary contact is: 13,23,33,43 the outgoing terminal of NO auxiliary contact is: 14,24,34,44 The outgoing terminal of OFF auxiliary contat is :11,21,31, 41 the outgoing terminal of OFF auxiliary contact is: 12,22,32,42 and A2 The coil terminal is: A1
6.2 Contactors Overall and installation dimensions see Figure 2, Figure 4, Figure 5 and table 9.
CJX7-100
B-69
CJX7
A 44 54 54 70 90
B 74 90 90 110
C 74 93.5
C 102 120.5
a 35 45 45 60 78
b1 60 80 80 100 136
b2 50 70 70 90 126
Mounting mode Screw installation or TH75 mounting rail installation installation or TH35 or TH75 mounting rail
6.2 6.2
148.5 123.5
Note: Refer to drawing 6 for dimension Note: Refer to drawing 7 for dimension
B-70