MP METER-PAK Meter Centers EZ METER-PAK Meter Centers

Class 4100

CONTENTS Description Page Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 General and Application Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 MP METER-PAK Meter Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 EZ METER-PAK Meter Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93

Schneider Electric Brands

MP METER-PAK Meter Centers Class 4141 EZ METER-PAK Meter Centers Class 4161, 4162
Product Description
MP METER-PAK meter centers and EZ METER-PAK (EZM) meter centers from Square D Company offer a wide range of solutions for multimetering applications: UL Listed NEMA Type 3R construction Meets EUSERC standards 9-inch meter center spacing allows for more sockets per device creating lighter more compact branch enclosures Meter socket jaws, constructed of tin-plated copper, are spring reinforced on MP and EZM devices Lever type bypass meter socket jaws (EZM only) are spring reinforced and equipped with jaw release Stainless steel cover hasps and latches meet tough coastal utility sealing requirements Barrel lock provisions on all ringless devices MP METER-PAK Meter Centers For 2- to 6-unit apartment buildings or light commercial applications.
MP METER-PAK branch meter/circuit breaker devices are available in 2- through 6-meter socket congurations.

Surface and semiush mounting Suitable only for use as service equipment Main bus ratings range from 200800 A 125 A and 200 A tenant circuit breaker versions Three meter socket congurations available:

Ring type Ringless type with 5th jaw Ringless type with 5th jaw and horn bypass 120/240 Vac, 1f3W or 120/208 Vac, 1f3W (derived from a 208Y/120 Vac, 3f4W network) EZ METER-PAK Meter Centers For maximum exibility on larger installations or where a main disconnect is required. VISI-TITE nuts provided for cross bus connectors Circuit breaker, fusible switch, and terminal box mains from 4001600 A maximum Suitable for use as service equipment 125 A, 200 A, and 400 A maximum branch unit frame sizes available Residential branches: Ring type, 125 A and 200 A maximum Ringless type with 5th jaw, 125 A and 200 A maximum Ringless type with 5th jaw and horn bypass, 125 A and 200 A maximum Commercial branches: Ringless type with 5th jaw and lever bypass, 200 A and 400 A maximum Ringless type, 7 jaw, 200 A maximum Ringless type, 7 jaw with lever bypass, 200 A and 400 A maximum 120/240 Vac, 1f3W or 120/208 Vac, 1f3W (derived from a 208Y/120 Vac, 3f4W network) 208Y/120 Vac, 3f4W or 240/120 Vac, 3f4W delta

EZ METER-PAK (EZM) meter centers are available in 1- through 6-meter/circuit breaker units where an EZM terminal box is used for the incoming service.

2
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141 EZ METER-PAK Meter Centers Class 4161, 4162
Product Description
Short Circuit Current Rating Selection Process 1. Review local utility requirements to ensure that metering equipment meets their standards. 2. Check with local utility to determine available fault current at the meter center. 3. Use the SCCR table (refer to pages 4 and 5): A. Select meter center conguration: Main Lugs only (6-Subdivision Rule), Remote Main, Main Circuit Breaker, or Main Fusible Switch. B. Read down to select SCCR equal to or greater than desired rating. C. Read across to select Main Device type. D. Read across to select Tenant Circuit Breaker type. 4. With information obtained from Step 3, turn to the appropriate selection pages to determine catalog numbers for Main Device and Tenant Circuit Breakers. 5. Refer to Square D Certied Ratings table below. Square D Certied Ratings Use this table to determine suitable load centers or panelboards installed downstream from any UL Listed EZM meter center applied on a system capable of delivering greater than 10,000 RMS symmetrical amperes. Requires a minimum of 20 feet (6.10 mm) of cable between meter center and downstream load center or panelboard. All ratings veried by actual Square D tests.
Meter Center 125 A and 200 A Branch Units QO Load Centers or NQOD Panelboards with Branch Circuit Breakers rated 10,000 AIR
QO, QOB: 1-Pole (1570 A) QOT: 1-Pole (1570 A) QO-GFI, QOB-GFI: 1-Pole (1530 A) QO-AFI, QOB-AFI: 1-Pole (1520 A) QO-QOB: 2-Pole (15125 A) QO, QOB: Downstream Three-Phase Load Center or Panelboard 1-Pole (1570 A) 2-Pole (15125 A) 3-Pole (15100 A) QO-GFI, QOB-GFI: 1-Pole (1530 A) QO-AFI, QOB-AFI: 1-Pole (1520 A)

HOM Load Centers with Branch Circuit Breakers rated 10,000 AIR
HOM: 1-Pole (1550 A) HOMT: 1-Pole (1520 A) HOM-GFI: 1-Pole (1520 A) HOM-AFI: 1-Pole (15-20 A) HOM: 2-Pole (1570 A) HOMT: 2-Pole (1530 A)

Downstream Single-Phase Load Center or Panelboard

3
5/99 1999 Square D All Rights Reserved

MP METER-PAK Meter Centers Class 4141 EZ METER-PAK Meter Centers Class 4161, 4162
UL Listed Meter Center Short Circuit Current Ratings (SCCR):
Short Circuit Current Rating RMS Symmetrical Amperesu MP METER-PAK Meter Centers 6-Subdivision Rule Applications Main Device Tenant Circuit Breakers u EZ METER-PAK Meter Centers 6-Subdivision Rule Applications Main Device
4001600 A Main Lugs Terminal Box (Tenant circuit breakers used as service disconnects - 6 max.)

Tenant Circuit Breakers u


QO (125 A max. 2-pole) Q2M (200 A max. 2-pole) QE-VH (200 A max. 2 or 3-pole) LAL (400 A max. 2 or 3-pole) QO-VH (125 A max. 2-pole) Q2M-VH (200 A max. 2-pole) QE-VH (200 A max. 2 or 3-pole) LAL (400 A max. 2 or 3-pole)k

10,000 AIR

Main Lugs Only with Main Bus Rated 200800 A (Tenant circuit QO (125 A max. 2-pole) breakers used as service disconnects - QOM2-MM (200 A max. 2-pole) 6 max.) Main Lugs Only with Main Bus Rated 200800 A (Tenant circuit QO-VH (125 A max. 2-pole) breakers used as service disconnects - QOM2-MVH (200 A max. 2-pole) 6 max.)

22,000 AIR

4001600 A Main Lugs Terminal Box (Tenant circuit breakers used as service disconnects - 6 max.)

42,000 AIR

Main Lugs Only with Main Bus Rated 200-600 A (Tenant circuit QOH (125 A max. 2-pole) breakers used as service disconnects 6 max.)

4001600 A Main Lugs Terminal Box (Tenant circuit breakers used as service disconnects - 6 max.)

QOH (125 A max. 2-pole) Q2MH (200 A max. 2-pole)

65,000 AIR

100,000 AIR

EZM Main Lugs Terminal Box EZM Branch Unit MP Branch Compartments

Service Disconnects (6 Maximum)

Service Disconnects (6 Maximum)

Transformer Transformer

Main Lugs Load Center (Typical) MP Main Lugs Compartment

Tenant Circuit Breakers

Main Lugs Load Center (Typical)

Refer to page 22 k u t AIR

Refer to page 66 for 1f or page 69 for 3f

LAL circuit breaker is limited to 18K AIR. Obtain calculated system information to determine if this will meet the requirements. When slider type manual circuit closers are installed, the meter center short circuit current rating is limited to 10,000 RMS symmetrical amperes. For 100 and 125 A requirements, use QO-VH circuit breakers with EZM125QOA conversion kit to achieve 42,000 AIR with a 1200 A main fusible switch. = Amperes Interrupting Rating

4
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141 EZ METER-PAK Meter Centers Class 4161, 4162

EZ METER-PAK Meter Centers Main Lugs Terminal Box Applications Protected by Remote Main Main Device
4001600 A Main Lugs Terminal Box Must be protected by an upstream disconnecting means rated 10,000 AIR minimum 4001600 A Main Lugs Terminal Box Must be protected by an upstream disconnecting means rated 22,000 AIR minimum 4001600 A Main Lugs Terminal Box Must be protected by a Square D circuit breaker rated 42,000 AIR minimum

Main Circuit Breaker Applications Main Device Tenant Circuit Breakers u

Main Fusible Switch Applications (with 300 V Class T Fuses Installed) Main Device Tenant Circuit Breakers u
QO (125 A max. 2-pole) Q2M (200 A max. 2-pole) QE-VH (200 A max. 2 or 3-pole) LAL (400 A max. 2 or 3-pole) QO-VH (125 A max. 2-pole) Q2M-VH (200 A max. 2-pole) QE-VH (200 A max. 2 or 3-pole) LAL (400 A max. 2 or 3-pole)k QO-VH (125 A max. 2-pole) Q2M-VH (200 A max. 2-pole) QE-VH (200 A max. 2 or 3-pole) QO-VH (125 A max. 2-pole) Q2M-VH (150 & 200 A only, 2-pole)t QE-VH (200 A max. 2-pole only) QO-VH (125 A max. 2-pole) Q2M-VH (200 A max. 2-pole) QE-VH (200 A max. 2 or 3-pole) Q2M-VH (150 & 200 A only, 2-pole) QE-VH (200 A max. 2 pole only)

Tenant Circuit Breakers u

QO (125 A max. 2-pole) Q2M (200 A max. 2-pole) 4001600 A Main Circuit Breaker QE-VH (200 A max. 2 or 3-pole) LAL (400 A max. 2 or 3-pole) QO-VH (125 A max. 2-pole) Q2M-VH (200 A max. 2-pole) 4001600 A Main Circuit Breaker QE-VH (200 A max. 2 or 3-pole) LAL (400 A max. 2 or 3-pole)k

QO (125 A max. 2-pole) Q2M (200 A max. 2-pole) 4001200 A Main QE-VH (200 A max. 2 or 3-pole) Fusible Switch LAL (400 A max. 2 or 3-pole) QO-VH (125 A max. 2-pole) Q2M-VH (200 A max. 2-pole) 4001200 A Main QE-VH (200 A max. 2 or 3-pole) Fusible Switch LAL (400 A max. 2 or 3-pole)k

400800 A Main Fusible Switch QO-VH (125 A max. 2-pole) QO-VH (125 A max. 2-pole) Q2M-VH (200 A max. 2-pole) 4001600 A Main Circuit Breaker Q2M-VH (200 A max. 2-pole) QE-VH (200 A max. 2 or 3-pole) QE-VH (200 A max. 2 or 3-pole) 1200 A Main Fusible Switch 400800 A Main Fusible Switch

4001600 A Main Lugs Terminal Box Must be protected by a Square D circuit breaker rated 65,000 AIR minimum

QO-VH (125 A max. 2-pole) QO-VH (125 A max. 2-pole) Q2M-VH (200 A max. 2-pole) 4001600 A Main Circuit Breaker Q2M-VH (200 A max. 2-pole) QE-VH (200 A max. 2 or 3-pole) QE-VH (200 A max. 2 or 3-pole) 1200 A Main Fusible Switch

4001600 A Main Lugs Terminal Box Must be protected by an upstream disconnection means with Class R (600 A max.), or 300 V, Class T (800 A max.) fuses.

QO-VH (125 A max. 2-pole) 10001200 A Main Circuit Q2M-VH (200 A max. 2-pole) Breaker with Catalog Number QE-VH (200 A max. 2 or 3-pole) Sufx "-CBU"

QO-VH (125 A max. 2-pole) 400800 A Main Q2M-VH (200 A max. 2-pole) Fusible Switch QE-VH (200 A max. 2 or 3-pole)

QO-VH (125 A max. 2-pole) Q2M-VH (200 A max. 2-pole) QE-VH (200 A max. 2 or 3-pole)

EZM Branch Unit EZM Main Lugs Terminal Box EZM Branch Unit

EZM Circuit Breaker Main or EZM Main Fusible Switch

Tenant Circuit Breakers Transformer

Main Lugs Load Center (Typical)

Transformer

Tenant Circuit Breakers

Main Lugs Load Center (Typical)

Refer to page 66 for 1f or page 69 for 3f

Refer to page 66 for 1f or page 69 for 3f

5
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Main Devices Terminal Box 400 A and 800 A Main Fusible Switch 400-800 A Residential Branch Devices 125 A 6-Position 5-Position 4-Position 3-Position Residential Branch Devices 200 A 4-Position 2-Position 3-Position Main Circuit Breaker 400-1000 A Terminal Box 1600 A Main Fusible Switch 1200 A 1f Main Circuit Breaker 1200 A and 1600 A Main EUSERC Devices Main Fusible Switch 1200 A 1f Main Circuit Breaker 1000 A and 1200 A

7.09
180

8.09
205

11.50 18.33 292


466

12.25
311

12.25
311

12.25
311

12.25
311

17.38
441

17.38
441

18.66
474

30.19
767

34.19
868

25.82
656

25.82
656

Top Meter Position Omitted on 2-Position Device

23.07
586

23.06
586

19.66 16.82
427 499

19.67
500

66.12
1679 87 (Typ.)

11.07
281

11.07
281

3.44

Top Edge of Mounting Channel

229 (Typ.)

9.00

56.51
1435

31.30
795

31.30
795

31.30
795

25.21
640

32.34
821

32.34 24.17
614 1382 821

34.30
871

40.30 16.21
412 1024 696

72.40
1839 925

63.40
1610 925

54.40
1382

63.40
1610

54.40 36.40
925

22.21
564

38.12
968

27.40

36.40

36.40

36.40
925

36.40
925

18.39
467

9.53
242

46.99
1194

Floor or Finished Grade Level

6
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Main EUSERC Devices Main Fusible Switch 600 A and 800 A, 3f Main Circuit Breaker 600 A and 800 A, 3f Main Fusible Switch 400 A, 1f and 3f Main Circuit Breaker 400 A, 1f and 3f Main Fusible Switch 600 A and 800 A, 1f Main Circuit Breaker 600 A and 800 A, 1f Commercial Branch Devices 200 A 7 Jaws Lever Bypass 5 Jaws Lever Bypass 7 Jaws No Bypass 4-Position 3-Position 1-Position 2-Position Commercial Branch Devices 400 A 7 Jaws Lever Bypass 2-Position 1-Position

9.44 11.50
240 292

9.44
240

26.19
665

20.46
520

19.44
494

19.44
494

19.44
494

23.21
590

23.21
590

27.56
700

19.66
499

19.66
499

Top Meter Position Omitted on 1-Position Device

31.80
808

13.56
344

13.56
344

7.78
198

27.44
697

14.00
356 (Typ.)

45.55
1157

25.50
648

56.51
1435

31.01
788

7.14
181

39.50
1003

17.01
432

39.50
1003

37.81
960

37.81
960

18.69 30.39
772

72.39 49.37
1254

49.37
1254

1839

30.39
772

58.39
1483

58.39
1483

44.39 67.66
1128 1719

40.22
1022

40.22
1022

475

Floor or Finished Grade Level

NOTE: Mounting channel height of 56.51 inches is for reference only. Consult local utility for minimum and maximum meter socket height requirements to properly position mounting channel above grade level.

Top Edge of Mounting Channel

7
5/99 1999 Square D All Rights Reserved

Take-off Sheets
MP and EZM
MP Take-off Sheet
Building Name Quantity of Building Type Mounting Location Utility Name Maximum SCCR Available Utility Power Feed 10K 120/240 Vac, 1f3W 22K 42K (125 A only) 120/208 Vac 1f3W Tenant Circuit Breaker Ampere Rating (40 125 A Max.) (40 125 A Max.) (40 125 A Max.) 200 A Maximum Tenant Circuit Breaker METER-PAK Equipment (100 200 A Max.) (100 200 A Max.) (100 200 A Max.) Semi-ush Mount Lug Landing Kits Required (EUSERC) Conductor Size and Quantity Yes Yes No No Outdoor Indoor

MP METER-PAK Branch Units (Cover Styles, MP = Ring Type, MPR, and MPH = Ringless Type) METER-PAK Type Number of Meter Sockets MP MPR MPH 125 A Maximum Tenant Circuit Breaker METER-PAK Equipment

EZM Take-off Sheet


Building Name Quantity of Building Type Mounting Location Utility Name Maximum SCCR Available Utility Power Feed 10K 120/240 Vac, 1f3W 22K 42K 120/208 Vac 1f3W 65K 100K 208/120 Vac 3f4W Tenant Circuit Breaker Ampere Rating (40 125 A Max.) (40 125 A Max.) (40 200 A Max.) (40 200 A Max.) (70 200 A Max.) (70 200 A Max.) (70 200 A Max.) (70 200 A Max.) (125 400 A Max.) No (Remote Main Upstream) Outdoor Indoor

EZ METER-PAK Branch Units (Cover Styles, EZM = Ring Type, EZMR, EZMH and EZML = Ringless Type) METER-PAK Type Number of Meter Sockets EZM EZMR EZMH EZML 125 A Residential 1f EZ METER-PAK Branch Units n/a n/a 200 A Residential 1f EZ METER-PAK Branch Units n/a n/a 200 A Commercial 1f EZ METER-PAK Branch Units n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a Yes

200 A Commercial 3f EZ METER-PAK Branch Units

400 A Commercial 3f EZ METER-PAK Branch Units (Circuit Breaker Supplied Factory Installed) EZ METER-PAK Main Devices Service Entrance Required Main Device Ampere Rating Main Device Feed Location Combination Overhead/ Underground Main with Factory Installed Lugs. Underground Only Main (Meets EUSERC Standards). Main Device Type Main Circuit Breaker (Circuit Breaker Supplied Factory Installed) Main Fusible Switch (Requires Use of 300 V Class T Fuses, Ordered Separately) Terminal Box Series Rated with Upstream Square D Circuit Breaker, Class R Fuses (600 A Max.), or Class T Fuses (800 A Max.). Terminal Box Fully Rated System EZ METER-PAK Special Application Devices Add-on Terminal Box for Back Feeding to CT Cabinet Quantity Quantity Corner Extension for Inside Corner (NEMA Type 1) Bus Extension (NEMA Type 1/3R) I-LINE II Busway Riser (NEMA Type 1) Requires Coordination to Determine Proper Phasing and Mounting Location of Main Device onto Busway. Ampere Rating (400 A, 800 A, or 1200 A) Ampere Rating (400 A, 800 A, or 1200 A) Yes Yes Yes No No No

8
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141


Contents
Application DataMP METER-PAK Meter Centers 125 A Maximum MP METER-PAK Meter Center Congurations . . . . 11 200 A Maximum MP METER-PAK Meter Center Congurations . . . . 11 Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Mains Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Branch Circuit Breaker Provisions . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Meter Sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Meter Socket Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Mounting Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Swingable Mounting Feet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Top Endwall Congurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 125 A Maximum MP METER-PAK Meter Center Top Endwalls . . . . 17 200 A Maximum MP METER-PAK Meter Center Top Endwalls . . . . 17 Semiush Flange Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Main Lugs Section Service Conductor Terminals Data . . . . . . . . . . . 19 Alternate Lug Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 NEMA/EUSERC Lug Landing Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Tenant Circuit Breaker Terminal Data . . . . . . . . . . . . . . . . . . . . . . . . 20 Load Neutral and Equipment Grounding Terminal Data . . . . . . . . . . 20 125 A Maximum MP METER-PAK Meter Centers . . . . . . . . . . . . . . 20 200 A Maximum MP METER-PAK Meter Centers . . . . . . . . . . . . . . 20 Hinged Rain Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Dimensions and Knockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

9
5/99 1999 Square D All Rights Reserved

MP METER-PAK Meter Centers Class 4141


Application Data

MP22125 (shown) MPR22125, MPH22125 (Sealing Rings not shown)

MP55125, MPR55125, MPH55125, MP66125, MPR66125, MPH66125 (shown) (Top Left Position Omitted on 5-Position Units)

MP33125, MPR33125, MPH33125 (shown) MP42200 (shown) MPR42200, MPH42200

MP44125 (shown) MPR44125, MPH44125

MP43200, MPR43200 MPH43200 (shown)

10
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141


Application Data
125 A MAXIMUM MP METER-PAK METER CENTER CONFIGURATIONS
Ring-type MP supplied with 4-jaw meter sockets without bypass (5th jaw and manual slider type bypass kits can be ordered separately and eld installed). Ringless-type MPR supplied with 5th jaw meter sockets without bypass (horn-type bypass kits can be ordered separately and eld installed). Ringless-type MPH supplied with 5th jaw meter sockets with horn-type bypass. Both ring- and ringless-type units have provisions for mounting 2-pole, plug-on type QO, QO-VH, or QOH circuit breakers.

200 A MAXIMUM MP METER-PAK METER CENTER CONFIGURATIONS


MP64200, MPR64200, MPH64200 (shown)

Ring-type MP supplied with 4-jaw meter sockets without bypass (5th jaw and manual slider type bypass kits can be ordered separately and eld installed). Ringless-type MPR supplied with 5th jaw meter sockets without bypass (horn-type bypass kits can be ordered separately and eld installed). Ringless-type MPH supplied with 5th jaw meter sockets with horn-type bypass. Both ring- and ringless-type units have provisions for mounting 2-pole, bolt-on type QOM2-MM or QOM2-MVH circuit breakers.

MP85200, MPR85200, MPH85200, MP86200 (shown), MPR86200, MPH86200 (Top Left Position Omitted on 5-Position Units)

11
5/99 1999 Square D All Rights Reserved

MP METER-PAK Meter Centers Class 4141


Application Data
TYPE
Enclosures are indoor/rainproof NEMA Type 3R meter center for use on ac systems. Available in 2-, 3-, 4-, 5-, or 6-position congurations. Suitable only for use as service entrance equipment (cannot be fed from an upstream service disconnect). Designed to be wall mounted only, not suitable for use as oor standing equipment. All unmetered conductor compartments are sealable by the utility company. Finish: ANSI gray, baked powder coat epoxy electro-deposited over cleaned phosphatized steel. UL Listed under File E-6294.
MPH55125

SERVICE
120/240 Vac, 1f3W 120/208 Vac, 1f3W (derived from a 208Y/120 Vac, 3f4W network).

MAINS RATINGS
125 A Maximum MP METER-PAK Meter Centers 200 A (2-position), 300 A (3-position), 400 A (4-position), 500 A (5-position), and 600 A (6-position) main bus ratings. 200 A Maximum MP METER-PAK Meter Centers
400 A Main Lugs

400 A (2- and 3-position), 600 A (4-position) and 800 A (5- and 6-position) main bus ratings.

BRANCH CIRCUIT BREAKER PROVISIONS


125 A Maximum MP METER-PAK Meter Centers Accepts 40125 A, 2-pole, plug-on type QO, QO-VH, or QOH circuit breakers. (Order circuit breakers separately.) UL Listed meter center short circuit current rating (RMS symmetrical amperes) equal to the lowest interrupting rating of installed tenant circuit breaker.
Ampere Rating
40

10,000 AIR 120/240 Vac


QO240 QO250 QO260 QO270 QO280 QO290 QO2100 QO2125

22,000 AIR 120/240 Vac


QO240VH QO250VH QO260VH QO270VH QO280VH QO290VH QO2100VH QO2125VH

42,000 AIR 120/240 Vac


QOH240 QOH250 QOH260 QOH270 QOH280 QOH290 QOH2100 QOH2125

QO Plug-On Mounting Base

QO2100 Plug-On Circuit Breaker Installed

50 60 70 80 90 100 125

NOTE: Square D Certied Ratings for use with 10,000 AIR Type QO or HOM load centers or NQOD panelboards installed downstream from any UL Listed METER-PAK meter center applied on a system capable of delivering greater than 10,000 RMS symmetrical amperes. Requires a minimum of 20 feet (6.1 meters) of cable between meter center and downstream load centers or panelboards. All ratings veried by actual Square D tests.
12
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141


Application Data
200 A Maximum MP METER-PAK Meter Centers Accepts 100200 A, 2-pole, bolt-on type QOM2-MM or QOM2-MVH circuit breakers. (Order circuit breakers separately.) UL Listed meter center short circuit current rating (RMS symmetrical amperes) equal to the lowest interrupting rating of tenant circuit breaker installed.
Ampere Rating
100

10,000 AIR 120/240 Vac


QOM2100MM QOM2125MM QOM2150MM QOM2175MM QOM2200MM

22,000 AIR 120/240 Vac


QOM2100MVH QOM2125MVH QOM2150MVH QOM2175MVH QOM2200MVH

QOM2-MM or QOM2-MVH Bolt-On Mounting Base

125 150 175 200

NOTE: Square D Certied Ratings for use with 10,000 AIR Type QO or HOM load centers or NQOD panelboards installed downstream from any UL Listed METER-PAK meter center applied on a system capable of delivering greater than 10,000 RMS symmetrical amperes. Requires a minimum of 20 feet (6.1 meters) of cable between meter center and downstream load centers or panelboards. All ratings veried by actual Square D tests.

METER SOCKETS
QOM2200MVH Bolt-On Circuit Breaker Installed

Standard Meter Socket Congurations Rated 200 A continuous duty. Front removable spring reinforced jaws equipped with line and load side blade guides. Thermoset polyester with berglass reinforced base assembly. 5th jaw supplied factory installed on ringless-type MPR and MPH in the 9 o'clock position, 5th jaw can be moved to the 3 or 6 oclock position as required. Ring-type MP supplied with 4-jaw meter socket without bypass. Ringless-type MPR supplied with 5-jaw meter socket without bypass. Ringless-type MPH supplied with 5-jaw meter socket with horn-type bypass.

Optional 5th Jaw Kit Installed on Ring-Type Device

Ringless-Type MPH Includes 5-Jaw Meter Socket and Horn Bypass

13
5/99 1999 Square D All Rights Reserved

MP METER-PAK Meter Centers Class 4141


Application Data
Optional Meter Socket Congurations 5th jaw kit (catalog number 5J) can be eld installed on ring-type MP at the 3, 6, or 9 oclock position and is required for 120/208 Vac, 1f3W, service (derived from a 208Y/120 Vac 3f4W network). One kit required per meter socket, order separately. Horn-type bypass kit, catalog number MMHB, can be eld installed on ringless-type MPR. One kit required per meter socket, order separately. Manual slider type bypass kit, catalog number MM125MB (for top position only on 125 A, 2-position ring-type MP) or MM200MB (for 125 A and 200 A ring-type MP). One kit required per meter socket, order separately for eld installation.

NOTE: Manual slider type bypass kits limit meter center equipment short circuit current rating to 10,000 RMS symmetrical amperes.
Ring-Type MP 4-Jaw Meter Socket without Bypass

METER SOCKET COVERS


Ring-Type MP Meter Socket Cover Individual meter socket cover provided for each meter socket. Cover cannot be removed with meter installed in meter socket. Seal ring is required to secure base of meter onto rim provided on meter socket cover. Aluminum snap-type seal ring (catalog number 29209-100-01) is standard on all ring-type MP meter socket covers.
Individual Ring-Type Meter Socket Cover

Manual Slider Type Bypass, Closed Position MM125MB, MM200MB (shown)

Optional Meter Socket Seal Rings for Type MP Stainless steel, snap-type seal ring (catalog number 29209-100-02), order separately for eld installation. Aluminum screw-type seal ring (catalog number 29008W), order separately for eld installation. Stainless steel, latch-type seal ring (catalog number 29008G), order separately for eld installation.

Manual Slider Type Bypass, Open Position MM125MB, MM200MB (shown)

Snap-Type Sealing Ring

Screw-Type Sealing Ring

Latch-Type Sealing Ring

14
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141


Application Data
Ringless-Type MPH and MPR Meter Socket Covers Individual meter socket cover provided for each meter socket. Base of meter is supported by brackets extending from meter socket base assembly. Meter socket cover is installed over meter to seal meter base to socket. Ringless meter socket covers are each supplied with a stainless steel latch and hasp to accommodate utility seals including lead wire seals, barrel locks, ribbon seals, padlocks, and snap-type seals. Ringless meter socket covers are also supplied with a 3/4-inch knockout to accommodate front-entry barrel locks. Barrel lock bracket located behind 3/4-inch knockout in each ringless meter socket cover. Barrel lock head protector kit (catalog number MMBLC) includes ferrule, lock nut, and seal cap to accommodate 1-inch long barrel lock (barrel lock not included).

Individual Ringless-Type Meter Socket Cover

Support Brackets for Base of Meter

Stainless Steel Latch and Hasp, Ringless Meter Socket Cover

Barrel Lock Installed Front Entry through Knockout in Ringless Meter Socket Cover (Reverse View)

Barrel Lock Head Protector Kit MMBLC Installed through Knockout in Ringless Meter Socket Cover

15
5/99 1999 Square D All Rights Reserved

MP METER-PAK Meter Centers Class 4141


Application Data
UTILITY PULL BOX COVER
Supplied with handles on 3- through 6-position 125 A maximum, and 2- through 6-position 200 A maximum METER-PAK meter center units. Supplied with swingable locking hasp to accommodate utility seals including lead wire seals, barrel locks, ribbon seals, padlocks, and snap-type seals.
Lifting Handles for Pull Box Cover

Swingable Locking Hasp

Hasp with Cover Installed

CUSTOMER / TENANT COMPARTMENT COVER


Removable without interfering with meter covers. Supplied with swingable locking hasp to accommodate a padlock (see swingable locking hasp above). Supplied with vertical rainproof tenant circuit breaker covers, one per meter socket.
Circuit Breaker Cover, Closed

TENANT CIRCUIT BREAKER COVERS


Constructed of impact resistant thermoplastic. Provisions for padlocking or sealing. Equipped with latch.

MOUNTING CHANNEL
Mounting channel supplied with 3- through 6-position 125 A maximum and all 200 A maximum units. Mounting ange is formed as a part of the top endwall to permit easy installation. Mount the channel to the wall at proper height. Hang unit on channel from mounting ange.

Tenant Compartment Circuit Breaker Cover

Circuit Breaker Cover, Open

SWINGABLE MOUNTING BRACKET


Permanently attached to save time. Easily moved for mounting hole drilling after marking. Accommodates slight mounting hole misalignment. Used for permanent mounting of device to wall.

Top Endwall Mounting Flange Mounting Channel

Mounting Channel

Swingable Mounting Bracket

16
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141


Application Data
TOP ENDWALL CONFIGURATIONS
125 A Maximum MP METER-PAK Meter Center Top Endwalls 2-position unit has utility compartment provisions for mounting one type A hub for use with 1- through 2.5-inch size conduit. Closing plate (Catalog Number ACP) supplied, order hub separately. 3- and 4-position units have utility compartment provisions for mounting one type A-L hub for use with 2- through 4-inch size conduit. Closing plate (Catalog Number ACPL) supplied, order hub separately. 5- and 6-position units have utility compartment provisions for mounting two type A-L hubs for use with 2- through 4-inch size conduits. Two ACPL closing plates supplied, order hubs separately. 200 A Maximum MP METER-PAK Meter Center Top Endwalls 2- through 6-position units have utility compartment provisions for mounting two type A-L hubs for use with 2- through 4-inch size conduit. Two ACPL closing plates supplied, order hubs separately.

Closing Plate ACP (supplied) 2-Position 125 A Top Endwall

Type A Hub Installed 2-Position 125 A Top Endwall

SEMIFLUSH FLANGE KITS


Closing Plate ACPL (supplied) 3- and 4-Position 125 A Top Endwall

Prior to installation, semiush ange kits can be ordered separately for eld modication. (Refer to instructions included in kits for complete directions.) To drill enclosure top endwall and box sides to secure mounting anges: 1. Drill 5/16-inch diameter clearance holes at center punched marks provided and secure anges with 1/4-20 mounting hardware provided. 2. Secure mounting anges of enclosure to stud wall on three sides (top, left, and right). 3. Cover mounting anges with building paper and caulk to seal between enclosure and building paper. Semiush Flange Kit

Type A-L Hub Installed 3- and 4-Position 125 A Top Endwall

Description
125 A Maximum 2-Position 125 A Maximum 3- and 4-Position 125 A Maximum 5- and 6-Position 200 A Maximum 2- and 3-Position 200 A Maximum 4-Position 200 A Maximum 5- and 6-Position

Catalog Number
MPSF12 MPSF14 MPSF16 MPSF23 MPSF24 MPSF26

Two Closing Plates ACPL (supplied) 5- and 6-Position 125 A Top Endwall and 2- through 6-Position 200 A Top Endwall

Semiush Flange Kit MPSF23

Two Type A-L Hubs Installed 5- and 6-Position 125 A Top Endwall and 2- through 6-Position 200 A Top Endwall

17
5/99 1999 Square D All Rights Reserved

MP METER-PAK Meter Centers Class 4141


Application Data
Knockouts
Symbol
A B C D E F G H I J

Conduit Size IN mm
0.50 0.75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

Hole Diameter IN mm
0.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.19 4.63 22 29 35 44 51 64 76 92 105 117

MP METER-PAK Meter Center Hub and Knockout Congurations


Maximum Tenant Circuit Breaker Ampere Rating and Number of Positions
125 A 2-Position 125 A 3-Position 125 A 4-Position 125 A 5-Position 125 A 6-Position 200 A 2-Position 200 A 3-Position 200 A 4-Position 200 A 5-Position 200 A 6-Position a

Top Endwall Pull Box Compartment Catalog Number Closing Plate(s) Supplied Factory Installed
(1) ACP

Bottom Endwall Pull Box Compartment Knockout and Hub Provisions


(1) Type A Hub or (1) B300 Hub or (1) D, F, G, and (1) A (2) Type A-L Hubs or (2) E, F, G, H and (1) A, B Note: One knockout is provided with I and J rings.

Hub Provisions

Tenant Circuit Breaker Compartment Knockouts


(2) C, D, F and (1) A

Box Back Tenant Circuit Breaker Compartment Knockouts


(2) C, D, Fa

MP22125 MPH22125 MPR22125 MP33125 MPH33125 MPR33125 MP44125 MPH44125 MPR44125 MP55125 MPH55125 MPR55125 MP66125 MPH66125 MPR66125 MP42200 MPH42200 MPR42200 MP43200 MPH43200 MPR43200 MP64200 MPH64200 MPR64200 MP85200 MPH85200 MPR85200 MP86200 MPH86200 MPR86200

(1) Type A

(1) ACPL

(1) Type AL

(4) C, D, F and (1) A, B

(4) C, D, F

(2) ACPL

(2) Type AL

(2) Type A-L Hubs or (2) G, H, I, J and (1) A

(3) C, D, F and (1) A, B Provided per compartment.

(3) C, D, F Provided per compartment.

(2) ACPL

(2) Type AL

(2) Type A-L Hubs or (2) G, H, I, J and (1) A

(4) C, D, F and (1) A, B

(3) C, D, F

(2) ACPL

(2) Type AL

(2) Type A-L Hubs or (2) G, H, I, J and (1) A

(4) C, D, F and (1) A, B

(4) C, D, F

(2) ACPL

(2) Type AL

(2) Type A-L Hubs or (2) G, H, I, J and (1) A, B, C

(3) C, D, F and (1) A, B Provided per compartment.

(3) C, D, F Provided per compartment.

Same knockout pattern on side of box.

18
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141


Application Data
MAIN LUGS SECTION SERVICE CONDUCTOR TERMINATION DATA
Neutral bus is bonded permanently to the enclosure. Suitable only for use as service equipment. 125 A Maximum MP METER-PAK Meter Center Service Conductor Termination Data
Number of Meter Socket Positions
2 3 4 5 6

Main Bus Rating (Amperes)


200 A 300 A 400 A 500 A 600 A

Factory Installed Main Lugs Capacity (Amperes)


200 A 300 A 400 A 400 A AL or 500 A CU 400 A AL or 500 A CU

Line Phase and Neutral Lug Wire Size Al/Cu AWG/kcmil


(1) #4-250 (1) 1/0-600 or (2) 1/0-250

200 A Maximum MP METER-PAK Meter Center Service Conductor Termination Data


2 400 A 400 A 600 A 800 A 800 A 400 A 400 A 400 A AL or 500 A CU 600 A AL or 750 A CU 600 A AL or 750 A CU

Main Lugs Compartment

3 4 5 6

(1) 1/0-600 or (2) 1/0-250 (2) 3/0-500

ALTERNATE LUG KITS


Available for use on 36-position 125 A and all 200 A METER-PAK meter centers units (order separately):
Catalog Number MMLK250
MMLK250c MMLK500 MMLK600q c q

Lug Type (Mechanical)


Double Barrel Double Barrel Double Barrel

Lug Wire Size Al/Cu AWG/kcmil


(1) 1/0-600 or (2) 1/0-250 (2) 3/0-500 (2) #2-600

Standard lug kit supplied factory installed on 36-position 125 A units, and 24-position 200 A units. Kit includes NEMA/EUSERC lug landing pads (MMSK2). Kit is rated 800 A maximum (600 A maximum in EUSERC areas).

MMLK500

NEMA/EUSERC LUG LANDING KIT


Catalog number MMSK2 (order separately). Available for use on 3- through 6-position 125 A and all 200 A METER-PAK meter center units. Kit includes three bus bar lug landing pads and mounting hardware to secure pads to main cross bus. Each lug landing pad supplied with two 1/2-13 studs on 1-3/4-inch centers and mounting hardware. Rated 600 A maximum when applied in EUSERC areas. Order one kit per METER-PAK meter center device, order lugs separately (refer to the following table for lugs). Lugs for use with NEMA/EUSERC Lug Landing Kit
Lug Manufacturer
ANDERSON VCEL-060-12-H2 TA-600-2Nf ILSCO AU-600-2N p f Mechanical (2) #2-600 Al/Cu 500 lb-in (57 Nm) Lugs are not available from Square D and must be ordered separately from ANDERSON or ILSCO. Available by ordering kit catalog number CMELK4 (kit includes 4 lugs). Mechanical

MMSK2

Catalog Numberp
VHCL-600-12-BN

Lug Type
Compression

Lug Wire Size AWG / kcmil


250-600 Cu

Crimping Tool or Torque


VC-6FT or VC-7FT

400-600 Al/Cu #2-600 Al/Cu 375 lb-in (42 Nm)

MMLK600

19
5/99 1999 Square D All Rights Reserved

MP METER-PAK Meter Centers Class 4141


Application Data
TENANT CIRCUIT BREAKER TERMINATION DATA
125 A Maximum MP METER-PAK Meter Center Tenant Circuit Breaker Termination Data
Tenant Circuit Breaker Type and Ampere Rating
QO, QO-VH, and QOH 2-pole, 4070 A QO, QO-VH, and QOH 2-pole, 80125 A

Lug Wire Size


#8#2 AWG Al/Cu #42/0 AWG Al/Cu

QO2100 Tenant Circuit Breaker

QOM2200MVH Tenant Circuit Breaker

200 A Maximum MP METER-PAK Meter Center Tenant Circuit Breaker Termination Data
Tenant Circuit Breaker Type and Ampere Rating
QOM2-MM and QOM2-MVH 2-pole, 100200 A c

Lug Wire Size


#4 AWG 300 kcmil Al/Cu

Wire Bending Space


#4 AWG 250 kcmil Al/Cuc

Bottom tenant circuit breaker position has wire bending space to accommodate 300 kcmil wire, for bottom feed only.

SERVICE GROUND/LOAD NEUTRAL AND EQUIPMENT GROUNDING TERMINATION DATA


Service ground/load neutral lugs, located in the tenant compartment, are bonded to the enclosure. Two service ground lugs provided per device. One load neutral lug and one equipment grounding lug are provided for each tenant circuit breaker position.
Service Grounds and Load Neutrals

Equipment Grounding Lugs

125 A Maximum MP METER-PAK Meter Centers Load neutral and service ground lugs will accept one #14-2/0 AWG Cu or one #12-2/0 AWG Al conductor. 200 A Maximum MP METER-PAK Meter Centers Load neutral and service ground lugs will accept one #6 AWG 300 kcmil Al/Cu conductor.

HINGED RAIN CHANNEL


Rain channel is hinged at bottom of tenant compartment allowing easy access to wiring gutter for pulling wires.

Hinged Rain Channel

20
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141


Catalog Number Logic
MP METER-PAK Meter Centers
MP H 4 4 125 MAXIMUM TENANT CIRCUIT BREAKER AMPERAGE
125, 200 A

NUMBER OF METER SOCKETS


Meter Sockets Available 2, 3, 4, 5, 6

BUS AMPACITY
2 = 200 A 3 = 300 A 4 = 400 A 5 = 500 A 6 = 600 A 8 = 800 A

SOCKET/BYPASS TYPE
Blank = Ring Type R = Ringless with 5th Jaw H = Ringless with Horn Bypass and 5th Jaw

DEVICE NAME
MP METER-PAK Meter Center

21
5/99 1999 Square D All Rights Reserved

MP METER-PAK Meter Centers Class 4141


Product Selection
STEP 1: SELECT RING OR RINGLESS TYPE MP METER-PAK METER CENTERS
Select MP METER-PAK meter center short circuit current rating RMS symmetrical amperes from table on page 4, then make selections from the following:
Metering Equipment Ampere Rating Number of Positions Ringless-Type, 5-Jaw Ring-Type, 4-Jaw Catalog Numbera
MP22125 MP33125 MP44125 MP55125 MP66125 MP42200 MP43200 MP64200 MP85200 MP86200

No Bypass Catalog Number


MPR22125 MPR33125 MPR44125 MPR55125 MPR66125 MPR42200 MPR43200 MPR64200 MPR85200 MPR86200

Horn Bypass Catalog Number


MPH22125 MPH33125 MPH44125 MPH55125 MPH66125 MPH42200 MPH43200 MPH64200 MPH85200 MPH86200

2 125 A (Use QO circuit breakers) 3 4 5 6 2 200 A (Use QOM2 circuit breakers) 3 4 5 6 a

Meets EUSERC standards with addition of lug landing kit, MMSK2. Kit not required for MP22125.

STEP 2: SELECT TENANT CIRCUIT BREAKERS

Device Type

Ampere Rating
40 50 60 70

10,000 AIR 120/240 Vac


QO240 QO250 QO260 QO270 QO280 QO290 QO2100 QO2125 QOM2100MM QOM2125MM QOM2150MM QOM2175MM QOM2200MM

22,000 AIR 120/240 Vac


QO240VH QO250VH QO260VH QO270VH QO280VH QO290VH QO2100VH QO2125VH QOM2100MVH QOM2125MVH QOM2150MVH QOM2175MVH QOM2200MVH

42,000 AIR 120/240 Vac


QOH240 QOH250 QOH260 QOH270 QOH280 QOH290 QOH2100 QOH2125 ... ... ... ... ...

125 A 80 90 100 125 100 125 200 A 150 175 200

22
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141


Product Selection
STEP 3: CHOOSE ACCESSORIES AND/OR REPLACEMENT PARTS
AccessoriesDescription
Fifth Jaw Kit (one per kit) Barrel Lock Head Protector Kit (use on MPR and MPH only) (Barrel Lock not included) Horn Bypass Kit (use on MPR and MPH only) Manual Slider Type Bypass: 125 A Ring Type 2 Position Top Meter (only) 125 A and 200 A Ring Type Sealing Rings: Snap Type Aluminum (standard) Screw Type Aluminum Snap Type Stainless Steel Stainless Steel Latch Type Meter Socket Closing PlateLEXAN Meter Socket Closing PlateMetal (Ringless-Type use only) Optional Lug Kits (3 Lugs per kit): 400 A: (1) 1/0-600 AWG/kcmil or (2) 1/0-250 per phase Al/Cu 600 A: (2) 3/0-500 AWG/kcmil per phase Al/Cu 800 A: (2) 2-600 AWG/kcmil per phase Al/Cu Semiush Kits: 125 A, 2-Position 125 A, 34-Position 125 A, 56-Position 200 A, 23-Position 200 A, 4-Position 200 A, 56-Position NEMA/EUSERC Lug Landing Kit: For 36-position 125 A and all 200 A devices. Each pad rated 600 A maximum and includes (2) 1/2-13 studs and mounting hardware. u p h MPSF12 MPSF14 MPSF16 MPSF23 MPSF24 MPSF26 MMSK2h MMLK250ph MMLK500h MMLK600h 29209-100-01 29008W 29209-100-02 29008G 29007 RSG-4 MM125MBu MM200MBu

Catalog Number
5J MMBLC MMHB

The meter center short circuit current rating is 10,000 RMS symmetrical amperes when manual slider type bypass is used. Not rated for continuous duty. Standard lug for 36-position 125 A and 24-position 200 A devices. Cannot be installed on 2-position 125 A devices.

Replacement Parts(Refer to page 93 for details)


Replacement Socket/Jaw/Bus/Circuit Breaker Base Assemblies (Order Horn Bypass Kits separately, as needed) 125 A Standard Socket, 5th Jaw 200 A Standard Socket, 5th Jaw Replacement Socket Covers Ring Cover, 125 A and 200 A Ringless Cover, 125 A and 200 A

Catalog Number

MM125KIT MP200KIT MMC MMRC

23
5/99 1999 Square D All Rights Reserved

MP METER-PAK Meter Centers Class 4141


Dimensions and Knockouts

Supplied with ACP Closing Plate (for Underground Service), Order Type A Hub Separately (for Overhead Service)

3.67
93

1.97
50

7.10
180

.19
5

1.38
35

12.28
312

2.56
65

9.37
238

Embossed Mounting Holes (4 Locations) .25 Dia. 6

2.56 From Top to


65 Center of Embossed Mounting Holes

37.50
953

24.31
617

9.00
229 Line Phase Lugs

24.31
617

18.50
470 C,D,F

C,D,F

11.25 6.97
177

8.62
219

286

6.97
177

2.32 3.77
96 60

4.70
119

Line Neutral Lug

1.75
44

3.77
96

12.13
308 45

1.79
C,D,F

1.75
44

A or B300 Hub Provision D,F,G A 2

.42 Dia.
11

4.70
119

.09 Dia. .09 x .33 Slot


2 8

3.08
78

8.14
207

.83
21

2.09
53

Ringless Cover Latch

MP22125 MPR22125 MPH22125

.10 Dia.
3

.10 x .40 Slot


3 10

.42 Dia.
11

Seal Bracket

Symbol
A B C D E F G H I J

Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

24
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141


Dimensions and Knockouts
Supplied with ACPL Closing Plate (for Underground Service), Order Type A-L Hub Separately (for Overhead Service)

6.10
155

2.76
70

24.34
312

4.68
119 Top Position Omitted on 3-Position Unit

12.00
305

185 (NTS)

7.28

Line Phase Lugs 87 (Typical)

.75
19

3.44

Cover Lifting Handles

48.12
1222

47.37
1203

C,D,F

229 (Typical)

9.00

23.62 2.84
600 72 11.19 284

2.29
58

5.58
142

13.50 1.75
44 343

5.25
133

6.53
166

6.85
174

10.05
255

24.12
613 A-L Hub Provision E,F,G,H,I,J A-L Hub Provision E,F,G,H

.42 Dia.
11

.09 Dia.
2

C,D,F

A,B

1.80
45

.09 x .33 Slot


2 8

4.75
121 A

Ringless Cover Latch


9.00
229

3.00
76

1.78
45

3.20
81

.10 Dia.
3

.10 x .40 Slot


3 10

MP33125 MPR33125 MPH33125

MP44125 MPR44125 MPH44125

.42 Dia.
11

Seal Bracket
.38 Dia. .95
10

1.73 24
44

Mounting Feet
Knockouts Conduit Size IN mm
.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

Symbol
A B C D E F G H I J

Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

25
5/99 1999 Square D All Rights Reserved

MP METER-PAK Meter Centers Class 4141


Dimensions and Knockouts
Supplied with ACPL Closing Plate (for Underground Service), Order Type A-L Hub Separately (for Overhead Service)

6.00
152

15.23
387

2.76
70

36.46
926

4.70
119

12.00
305

7.36
187

185 (NTS)

7.28

Top Position Omitted on 5-Position Unit

Line Phase Lugs

.75
19

N 87 (Typical)

42.37
1076

3.44

Cover Lifting Handles

41.62
1057 229 (Typical)

9.00

C,D,F

23.62
600

2.95
75

11.19
284

3.02 2.65
67 77

6.53
166

5.85
149

6.22
158

7.75
197

20.75
527

9.05
230

9.42
239

.42 Dia.
11

36.19
919 A-L Hub Provision G,H,I,J

.09 Dia.
2

A,B C,D,F

14.92
379

15.07
383

.09 x .33 Slot


2 8

3.00
76

Ringless Cover Latch

1.75
44

2.61
66

3.20
81

2.99 3.20
81 76

.10 Dia.
3

.10 x .40 Slot


3 10

18.02
458

.42 Dia.
11

Seal Bracket
.38 Dia. .95
10

MP55125 MPR55125 MPH55125

MP66125 MPR66125 MPH66125

1.73 24
44

Mounting Feet

Symbol
A B C D E F G H I J

Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

26
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141


Dimensions and Knockouts
Supplied with ACPL Closing Plate (for Underground Service), Order Type A-L Hub Separately (for Overhead Service)

9.70
246

3.70
94

2.58
66

29.44
748

7.25
184 Top Position Omitted on 2-Position Unit Line Phase Lugs

210 (NTS)

8.28

.75
19

43.41
1103 Line Neutral Lugs

42.66
229 (Typical)

9.00

31.50
800

1084

28.00
711

C,D,F

24.62
625

2.25
57

12.22
310

12.55 2.70
69 319

8.38
213

7.53
191

6.10
155

12.15
309

29.31
744 C,D,F A,B

.42 Dia.
11

1.94
49

10.41 264

A-L Hub Provision G,H,I,J

.09 Dia.
2

.09 x .33 Slot


2 8

Ringless Cover Latch


3.00 2.66
68 85 (Typ.)

3.04
77

3.33

76

9.20
234

.10 Dia.
3

15.48
393

.10 x .40 Slot


3 10

.42 Dia.
11

MP42200 MPR42200 MPH42200

MP43200 MPR43200 MPH43200


44

Seal Bracket
.38 Dia. .95
10

1.73 24

Mounting Feet
Knockouts Conduit Size IN mm
.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

Symbol
A B C D E F G H I J

Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

27
5/99 1999 Square D All Rights Reserved

MP METER-PAK Meter Centers Class 4141


Dimensions and Knockouts
Supplied with ACPL Closing Plate (for Underground Service), Order Type A-L Hub Separately (for Overhead Service)

9.70
246

3.70
94

2.58
66

29.44
748

9.82
249

7.36
187

210 (NTS)

8.25

.75
19

Line Phase Lugs

52.00
1321

51.25
1302 Line Neutral Lugs

229 (Typical) C,D,F 625

9.00

31.50
800

28.00
711

24.62 12.22
310

2.23
57

5.65
144

12.55 2.45
62 319

8.38
213

7.53
191

5.85
149

12.15
309

29.31
744 C,D,F A,B

.42 Dia.
11

10.37
263 A-L Hub Provision G,H,I,J

1.94
49

.09 Dia.
2

.09 x .33 Slot


2 8

Ringless Cover Latch


3.00 2.66
68 85 (Typ.)

3.04
77

3.33

76

9.20
234

.10 Dia.
3

15.48
393

.10 x .40 Slot


3 10

.42 Dia.
11

MP64200 MPR64200 MPH64200


44

Seal Bracket
.38 Dia. .95
10

1.73 24 Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

Symbol
A B C D E F G H I J

Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

Mounting Feet

28
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141


Dimensions and Knockouts
Supplied with ACPL Closing Plate (for Underground Service), Order Type A-L Hub Separately (for Overhead Service)

26.34
669

20.34
517

2.58
66

46.68
1186 305

9.82
249 Top Left Position Omitted on 5-Position Unit

7.36
187

12.00

9.82
249

210 (NTS)

8.28

Line Phase Lugs

.75
19

Line Neutral Lugs

43.41
1321

42.66
1084

229 (Typical) C,D,F 622

9.00

31.50
800

28.25
718

24.50 12.22
310

2.23
57

5.00 2.95
75 127

7.53
191

6.35
161

10.81
275

8.60
218

29.25
743

12.15
309

14.20
361

.42 Dia.
11

46.56
1183 C,D,F

.09 Dia.
A-L Hub Provision G,H,I,J 2

A,B,C

.09 x .33 Slot


2 8

1.93
49

3.04
77

Ringless Cover Latch

2.66
68

4.53 20.12
511

6.20
68

85 (Typ.)

3.33

115

.10 Dia.
3

.10 x .40 Slot


3 10

MP85200 MPR85200 MPH85200

MP86200 MPR86200 MPH86200

.42 Dia.
11

Seal Bracket
.38 Dia. .95
10

1.73 24
44

Mounting Feet
Knockouts Conduit Size IN mm
.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

Symbol
A B C D E F G H I J

Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

29
5/99 1999 Square D All Rights Reserved

MP METER-PAK Meter Centers Class 4141


Wiring Diagrams
125 A Devices
Fifth Jaw Factory Installed on Ringless Device Omitted on 3-Position Unit Omitted on 5-Position Unit

f f

f f

f f

f f

f N f Line
f f Fifth Jaw Factory Installed on Ringless Device

f f

f f

f Neutral, Service Ground and Equipment Grounding Terminals f f Line N

f f

MP22125 MPR22125 MPH22125

f f Fifth Jaw Factory Installed on Ringless Device

f f

f f

Equipment Grounding Terminals


f f

Neutral and Service Ground Equipment Grounding Terminals

Neutral and Service Ground

MP55125 MPR55125 MPH55125

MP66125 MPR66125 MPH66125

MP33125 MPR33125 MPH33125

MP44125 MPR44125 MPH44125

200 A Devices
Omitted on 2-Position Unit Omitted on 5-Position Unit

f f f f N Line f f Fifth Jaw Factory Installed on Ringless Device f f Equipment Grounding Terminals f f Fifth Jaw Factory Installed on Ringless Device f f Equipment Grounding Terminals f f f N Line Fifth Jaw Factory Installed on Ringless Device f f f f f f f f f

f f f f N Line f f

f f

Neutral and Service Ground

Equipment Grounding Terminals

MP42200 MPR42200 MPH42200

MP43200 MPR43200 MPH43200

Neutral and Service Ground

Neutral and Service Ground

MP85200 MPR85200 MPH85200

MP86200 MPR86200 MPH86200

MP64200 MPR64200 MPH64200

30
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Contents
Application DataEZ METER-PAK Meter Centers EZ METER-PAK (EZM) Meter Centers Typical Equipment Lineups. . 32 EZ METER-PAK Meter Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Main Device Ampere Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Branch Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Horizontal Cross Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Factory Phase Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 EZM Main Device Types and Congurations . . . . . . . . . . . . . . . . . . . 60 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Dimensions and Knockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

31
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
EZ METER-PAK (EZM) METER CENTERS TYPICAL EQUIPMENT LINEUPS

Typical Tenant Circuit Breakers

EZM114125 EZM1800TB

QO2100 2-Pole, Plug-On Type QO Circuit Breaker

Q2M2200VH 2-Pole, Bolt-On Type Q2M Circuit Breaker

EZM114200 EZM1800CB

LAL36400 3-Pole, Bolt-On Type LAL Circuit Breaker (Factory Installed)

QE3200VH 3-Pole, Bolt-On Type QE Circuit Breaker EZML312400 EZMR333200

EZM31600CB

NOTE: 1600 A main circuit breaker must be center mounted with branch units mounted on both sides.
32
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
EZ METER-PAK (EZM) METER CENTERS
Enclosures are indoor/rainproof NEMA Type 3R meter centers for use on ac systems. Finish: ANSI gray, baked powder-coat epoxy electrodeposited over cleaned phosphatized steel. 240 Vac maximum Suitable for use as service equipment. Enclosures meet NEC wire bending space requirements Designed to be wall mounted only (not suitable for oor mounting). All unmetered conductor compartments are sealable by the utility company.
EZM1800CB

EZ METER-PAK meter centers are UL Listed under File E-10582 and File E-131840. Utility Company Requirements Review local utility requirements to ensure that the metering equipment selected meets their standards. EZ METER-PAK meter centers, to be complete, must include: EZM main device, or terminal box EZM branch section(s), and Square D branch circuit breakers (tenant mains). Equipment Short Circuit Current Ratings Available up to 100,000 RMS symmetrical amperes. Refer to pages 4 and 5.

EZM3800FS

Systems Utility systems suitable for use as an incoming service to an EZM main device: System: 120/240 Vac, 1f3W Available incoming service to main device: 120/240 Vac, 1f3W System: 240/120 Vac, 3f4W delta Available incoming services to main device: 240/120 Vac, 3f4W delta 120/240 Vac, 1f3W (fed from transformers Af and Cf only). NOTE: Connection to High-Leg Bf not permitted for this service. System: 208Y/120 Vac, 3f4W Available incoming services to main device: 120/208 Vac, 1f3W 208Y/120 Vac, 3f4W

EZM1800TB

33
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Services The following are incoming services for an EZM main device and available outgoing feeder(s) to downstream panelboards from EZM branch section(s): 120/240 Vac, 1f3W to main device. Available outgoing feeder(s) to downstream panelboards 120/240 Vac, 1f3W 120/208 Vac, 1f3W to main device (derived from a 208Y/120 Vac, 3f4W network). Available outgoing feeder(s) to downstream panelboards 120/208 Vac, 1f3W. 240/120 Vac, 3f4W delta to main device. Available outgoing feeder(s) to downstream panelboards: 120/240 Vac, 1f3W (fed from transformers Af and Cf only). Special branch units are available for this system by adding sufx CA to catalog number, for example: EZM313125CA. NOTE: Connection to High-Leg Bf not permitted for this service. Standard 3f IN/1f OUT branch units are not suitable for use on this delta system. 240/120 Vac, 3f4W delta 208Y/120 Vac, 3f4W to main device. Available outgoing feeder(s) to downstream panelboards: 120/208 Vac, 1f3W (5th Jaw required) 208Y/120 Vac, 3f4W

EZM314125

EZM114200

EZML312400

EZML113200

34
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
MAIN DEVICE AMPERE RATINGS
Main Circuit Breaker Ratings 400 A, 600 A, 800 A, 1000 A, 1200 A and 1600 A combination overhead/ underground. 400 A, 600 A, 800 A, 1000 A, 1200 A underground only (meets EUSERC standards). Mounting Restrictions for Main Circuit Breaker Devices 1000 A and 1200 A mains must be center mounted when used with 125 A and 200 A residential branch units, with main bus rated 800 A. 1600 A mains must always be center mounted.
EZM31600CB

Main Fusible Switch Ratings 400 A, 600 A, 800 A and 1200 A combination overhead/underground. 400 A, 600 A, 800 A and 1200 A underground only (meets EUSERC standards). Mounting Restrictions for Main Fusible Switch Devices 1200 A mains must be center mounted when used with 125 A and 200 A residential branch units, with main bus rated 800 A. Terminal Box Ratings 400 A, 800 A, and 1600 A combination overhead/underground. Mounting Restrictions for Terminal Boxes 1600 A mains must always be center mounted.

EZM1800CBU

EZM3800FS

EZM1800TB

35
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
BRANCH UNITS
UL Listed meter center short circuit current ratings (RMS symmetrical amperes) are listed on pages 4 and 5. 125 A Maximum Residential Branch Units Available in two cross bus congurations, 1f IN/ 1f OUT (includes three horizontal cross bus bars), and 3f IN/1f OUT (includes four horizontal cross bus bars). Accepts 40125 A, 2-pole, plug-on type QO, QO-VH, or QOH circuit breakers (order circuit breakers separately). Ring-type EZM branch units supplied with 4-jaw (1f IN units), and with 5-jaw (3f IN units) are rated at 200 A continuous duty rated meter socket jaws on all 1f OUT meter sockets without bypass (manual slider type bypass kit MM200MB can be ordered separately and eld installed).
EZM115125

EZM316125

Ringless-type EZMR branch units supplied with 5-jaw, 200 A continuous duty meter socket jaws without bypass (horn type bypass kit MMHB can be ordered separately and eld installed). Ringless-type EZMH branch units supplied with 5-jaw, 200 A continuous duty meter socket jaws and horn type bypass. Supplied with 800 A horizontal main cross. Main must be center located when used with a 1000 A, 1200 A, or 1600 A main device. 200 A Maximum Residential Branch Units Available in two cross bus congurations, 1f IN/1f OUT (includes three horizontal cross bus bars), and 3f IN/1f OUT (includes four horizontal cross bus bars). Accepts 100200 A, 2-pole, bolt-on type Q2M, Q2M-VH, or Q2MH circuit breakers, or with the use of plug-on adapter catalog number EZM125QOA, these units will accept 40125 A, 2-pole plug-on type QO, QO-VH, or QOH circuit breakers (order circuit breakers and adapters separately). Ring-type EZM branch units supplied with 4-jaw (1f IN units), and with 5-jaw (3f IN units) are rated at 200 A continuous duty rated meter socket jaws on all 1f OUT meter sockets without bypass (manual slider type bypass kit MM200MB can be ordered separately and eld installed). Ringless-type EZMR branch units supplied with 5-jaw, 200 A continuous duty meter socket jaws without bypass (horn type bypass kit MMHB can be ordered separately and eld installed). Ringless-type EZMH branch units supplied with 5-jaw, 200 A continuous duty meter socket jaws and horn type bypass. Supplied with 800 A horizontal main cross bus. Main must be center located when used with a 1000 A, 1200 A, or 1600 A main device.

EZMH114125

EZM113125

EZM114200

36
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
200 A Maximum Commercial Branch Units Available in two cross bus congurations, 1f IN/1f OUT (includes three horizontal cross bus bars), 3f IN/1f OUT, and 3f IN/3f OUT (includes four horizontal cross bus bars). 1f OUT branch units accept 70200 A type QE-VH, 2-pole, plug-on circuit breakers (order circuit breakers separately). 3f OUT branch units accept 70200 A type QE-VH, 3-pole, plug-on circuit breakers (order circuit breakers separately). 1f OUT ringless-type EZML branch units are supplied with 5-jaw, 200 A continuous duty 1f meter sockets with lever type bypass. 3f OUT ringless-type EZML branch units are supplied with 7-jaw, 200 A continuous duty 3f meter sockets with lever bypass. 3f OUT ringless-type EZMR branch units are supplied with 7-jaw, 200 A continuous duty 3f meter sockets without bypass. Supplied with 1200 A horizontal main cross bus. Main must be center located when used with a 1600 A main device. 400 A Maximum Commercial Branch Units Available in one cross bus conguration for 3f IN/1f OUT, and 3f IN/3f OUT (includes four horizontal cross bus bars). 1f OUT branch units are supplied with factory installed 400 A, type LAL, 2-pole circuit breaker(s). Other circuit breaker ampere ratings are available, consult your local eld ofce for catalog numbers and availability. 3f OUT branch units are supplied with factory installed 400 A, type LAL, 3-pole circuit breaker(s). Other circuit breaker ampere ratings are available, consult your local eld ofce for catalog numbers and availability. Supplied with 1200 A horizontal main cross bus. Main must be center located when used with a 1600 A main device.

EZMR333200

EZML332200

EZML331400

37
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Bussed Extension Sections (NEMA Type 3R) Bussed extensions provide separation between enclosures where needed to avoid building obstructions. The bussed extension occupies an area 19.25" (489 mm) H x 11.75" (298 mm) W positioned vertically in line with the horizontal cross bus of main and branch unit enclosures. Provide additional space between the main device and the branch unit where needed to meet some local utility requirements. In this case the main device is deeper than the branch unit, and the dimension between the side of the main device and the centerline of the branch unit meter socket is too close to meet minimum clear space requirements.
EZM3EXT

Bussed extensions are also used with bussed corner sections to provide additional working space in inside corner areas. Use EZM1EXT with 1f cross bus equipment. Use EZM3EXT with 3f cross bus equipment. Supplied with 1200 A horizontal main cross bus. Provisions for padlocking or sealing by the utility. Bussed Corner Sections For Indoor (NEMA Type 1) Construction Only Enables mounting of metering enclosures on two adjacent walls. NEMA Type 1 construction for use indoors only. Designed for inside corner only. Use EZM1CORNER with 1f cross bus equipment. Use EZM3CORNER with 3f cross bus equipment. Supplied with 1200 A horizontal main cross bus. Provisions for padlocking or sealing by the utility. Mounting Channel EZM main and branch units are each supplied with a wall mounting channel. Mounting channel is packed externally to each device on top surface of front cover inside each carton for easy access. Covers do not need to be removed from device to access mounting channel. Swingable Mounting Brackets EZM sections are equipped with permanently attached swingable mounting brackets that are easily rotated out of the way after marking wall for drilling mounting holes. The swingable feature of the mounting brackets will accommodate slight mounting hole misalignment. Rotate mounting brackets to extended position before lifting device onto mounting channel for ease of installation. Swingable mounting brackets are provided at top and bottom of each unit to secure device to the wall.
21.79
553

EZM3CORNER

15.41
391

8.50
216

7.09
180

Bussed Extension

8.02
204

Bussed Extension

Main Device

Common Corner Application to Meet Utility Clearance Requirements

14.88
378

Common Wall Application to Meet Utility Clearance Requirements

38
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Determine Mounting Channel Height for Metering Equipment Lineup Contact your local utility to determine the following branch unit meter socket mounting height restrictions: Maximum dimension, centerline of top meter socket to oor or nished grade level. Minimum dimension, centerline of bottom meter socket to oor or nished grade level. Total branch unit meter socket height window (maximum dimension less minimum dimension).
125 A and 200 A Residential Branch Units (Typical) Main Circuit Breaker Device (Typical) 200 A Commercial Branch Units (Typical)

Chalk Line

56.51
1435

Chalk Line on Wall at Proper Height and Secure Mounting Channel to Wall. Mounting Channel is Secured to Wall and Device is Hung on Channel by Bracket Attached to Rear of Unit.

Maximum Meter Socket Height Requirement

229 (Typical) Mounting Channel

9.00

356 (Typical) Maximum Meter Socket Height Requirement Total Meter Socket Window Height

14.00

Total Meter Socket Window Height

511 (Typical)

20.10

663 (Typical)

26.10

Minimum Meter Socket Height Requirement

Minimum Meter Socket Height Requirement Minimum Height Requirement to Bottom of Main

Floor or Finished Grade Level

Mounting Channel

Mounting Channel Height Requirements Detail

Contact your local utility to determine minimum dimension from bottom of main device to oor or nished grade level. Refer to drawings of main devices and branch units starting on page 72 and determine proper height to install mounting channels. Ensure branch unit meter sockets are positioned within total branch unit meter socket height window, and main device bottom is positioned far enough above oor or nished grade level to comply with local requirements. Once the mounting channel height is determined, chalk a level line on wall at proper height. Align top edge of mounting channels with chalk line. Secure mounting channels for each unit to wall in the order that they will be installed. Some EZM branch sections (5-position, and 6-position branch units) might not t within utility's meter height window for outdoor applications, but could be acceptable for use in indoor installations.

Swingable Mounting Brackets

39
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Width

Main Devices
If Mounting Channel Height = 56.51" then mm
500 586 586 586 586 586 586 586 500 499 500 499 500 500 499 500 499 500 499 500 499 500 500 586 586 586 586 586 500 499 500 499 500 500 499 500 499 500 499 500 499 500

Catalog Number

Height

Width

Depth

IN
EZM11000CB Height 53.97

mm
1371 1779 1554 1779 1554 1779 1554 1554 1371 1753 1371 1753 1371 1371 1753 1371 1753 1371 1753 1371 1753 1371 1371 1779 1554 1779 1554 1554 1371 1753 1371 1753 1371 1371 1753 1371 1753 1371 1753 1371 1753 1371

IN
18.66 34.19 30.19 34.19 30.19 34.19 30.19 30.19 18.66 20.46 18.66 20.46 18.66 18.66 20.46 18.66 20.46 18.66 20.46 18.66 20.46 18.66 18.66 34.19 30.19 34.19 30.19 30.19 18.66 20.46 18.66 20.46 18.66 18.66 26.19 18.66 26.19 18.66 26.19 18.66 26.19 18.66

mm
474 868 767 868 767 868 767 767 474 520 474 520 474 474 520 474 520 474 520 474 520 474 474 868 767 868 767 767 474 520 474 520 474 474 665 474 665 474 665 474 665 474

IN
11.50 18.33 18.33 18.33 18.33 18.33 18.33 18.31 11.50 11.50 11.50 11.50 11.50 11.50 11.50 11.50 11.50 11.50 11.50 11.50 11.50 11.50 11.50 18.33 18.33 18.33 18.33 18.31 11.50 11.50 11.50 11.50 11.50 11.50 11.65 11.50 11.65 11.50 11.65 11.50 11.65 11.50

mm
292 466 466 466 466 466 466 465 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 466 466 466 466 465 292 292 292 292 292 292 296 292 296 292 296 292 296 292

IN
34.30 46.99 38.13 46.99 38.13 46.98 38.13 38.12 34.30 49.37 34.30 49.37 34.30 34.30 49.37 34.30 49.37 34.30 49.37 34.30 49.37 34.30 34.30 46.99 38.13 46.99 38.13 38.12 34.30 49.37 34.30 49.37 34.30 34.30 49.37 34.30 49.37 34.30 49.37 34.30 49.37 34.30

mm
871 1194 969 1194 969 1193 969 968 871 1254 871 1254 871 871 1254 871 1254 871 1254 871 1254 871 871 1194 969 1194 969 968 871 1254 871 1254 871 871 1254 871 1254 871 1254 871 1254 871

IN
19.67 23.06 23.06 23.06 23.06 23.07 23.06 23.07 19.67 19.66 19.67 19.66 19.67 19.67 19.66 19.67 19.66 19.67 19.66 19.67 19.66 19.67 19.67 23.06 23.06 23.06 23.06 23.07 19.67 19.66 19.67 19.66 19.67 19.67 19.66 19.67 19.66 19.67 19.66 19.67 19.66 19.67

IN
22.21 9.52 18.38 9.52 18.38 9.53 18.38 18.39 22.21 7.14 22.21 7.14 22.21 22.21 7.14 22.21 7.14 22.21 7.14 22.21 7.14 22.21 22.21 9.52 18.38 9.52 18.38 18.39 22.21 7.14 22.21 7.14 22.21 22.21 7.14 22.21 7.14 22.21 7.14 22.21 7.14 22.21

mm
564 242 467 242 467 242 467 467 564 181 564 181 564 564 181 564 181 564 181 564 181 564 564 242 467 242 467 467 564 181 564 181 564 564 181 564 181 564 181 564 181 564

EZM11000CBU 70.05 EZM11200CB B 61.19

EZM11200CBU 70.05

56.51
1435 Mounting Channel

EZM11200FS

61.19

EZM11200FSU 70.05 EZM11600CB EZM11600TB 61.19 61.19 53.97 69.03 53.97 69.03 53.97 53.97 69.03 53.97 69.03 53.97 69.03 53.97 69.03 53.97 53.97

M Floor or Finished Grade Level

EZM1400CB EZM1400CBU EZM1400FS

Main Device (Typical)


NOTE: Mounting channel height of 56.51 inches is for reference only. Consult local utility for minimum and maximum meter socket height requirements to properly position mounting channel above grade level.

EZM1400FSU EZM1400TB EZM1600CB EZM1600CBU EZM1600FS EZM1600FSU EZM1800CB EZM1800CBU EZM1800FS EZM1800FSU EZM1800TB EZM31000CB

EZM31000CBU 70.05 EZM31200CB 61.19

EZM31200CBU 70.05 EZM31600CB EZM31600TB EZM3400CB EZM3400CBU EZM3400FS EZM3400FSU EZM3400TB EZM3600CB EZM3600CBU EZM3600FS EZM3600FSU EZM3800CB EZM3800CBU EZM3800FS EZM3800FSU EZM3800TB 61.19 61.19 53.97 69.03 53.97 69.03 53.97 53.97 69.03 53.97 69.03 53.97 69.03 53.97 69.03 53.97

40
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
125 A and 200 A Residential Branch Units (Typical) Main Device (Typical) U T T U 200 A Commercial Branch Units (Typical)

R C B B L S Min. Mounting Channel M Floor or Finished Grade Level L C B

S Max.

S Max.

S Min. Mounting Channel

Determine Height for Mounting Channel


NOTE: S Max. , S Min. and M dimensions are based on local utility requirements and will determine proper height for mounting channel.

Single-Phase Branch Devices


If S Min. for Bottom meter = 30" then Catalog Number Height Width Depth A B C T U L R Top meter would be at IN
EZM112-200 EZM113-125 EZM113-200 EZM114-125 EZM114-200 EZM115-125 EZM116-125 EZMH112-200 EZMH113-125 EZMH113-200 EZMH114-125 EZMH114-200 EZMH115-125 EZMH116-125 EZML111-200 EZML112-200 EZML113-200 EZML114-200 EZMR112-200 EZMR113-125 EZMR113-200 EZMR114-125 EZMR114-200 EZMR115-125 EZMR116-125

Mounting Channel Height IN mm

mm

IN

mm
441 311 441 311 441 311 311 441 311 441 311 441 311 311 494 494 494 494 441 311 441 311 441 311 311

IN
8.09 7.09 8.09 7.09 8.09 7.09 7.09 8.09 7.09 8.09 7.09 8.09 7.09 7.09 9.44 9.44 9.44 9.44 8.09 7.09 8.09 7.09 8.09 7.09 7.09

mm
205 180 205 180 205 180 180 205 180 205 180 205 180 180 240 240 240 240 205 180 205 180 205 180 180

IN
9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 n/a 14.00 14.00 14.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00

mm
229 229 229 229 229 229 229 229 229 229 229 229 229 229 n/a 356 356 356 229 229 229 229 229 229 229

IN
32.34 31.30 32.34 31.30 32.34 31.30

mm

IN

mm
511 511 511 511 511 511 739 511 511 511 511 511 511 739 309 309 665 665 511 511 511 511 511 511 739

IN
11.07 11.07 11.07 16.82 19.66 25.82 25.82 11.07 11.07 11.07 16.82 19.66 25.82 25.82 13.56 13.56 13.56 27.56 11.07 11.07 11.07 16.82 19.66 25.82 25.82

mm
281 281 281 427 499 656 656 281 281 281 427 499 656 656 344 344 344 700 281 281 281 427 499 656 656

IN
22.18 13.18 13.18 9.93 12.77 9.93 9.93 22.18 13.18 13.18 9.93 12.77 9.93 9.93 25.73 11.73 11.73 11.73 22.18 13.18 13.18 9.93 12.77 9.93 9.93

mm
563 335 335 252 324 252 252 563 335 335 252 324 252 252 654 298 298 298 563 335 335 252 324 252 252

IN
12.23 11.19 12.23 11.19 12.23 11.19 11.19 12.23 11.19 12.23 11.19 12.23 11.19 11.19 13.33 13.33 13.33 13.33 12.23 11.19 12.23 11.19 12.23 11.19 11.19

mm
311 284 311 284 311 284 284 311 284 311 284 311 284 284 339 339 339 339 311 284 311 284 311 284 284

IN
9.00 18.00 18.00 27.00 27.00 36.00

mm
229 457 457 686 686 914

IN
39.00 48.00 48.00 57.00 57.00 66.00 75.00 39.00 48.00 48.00 57.00 57.00 66.00 75.00 30.00 44.00 58.00 72.00 39.00 48.00 48.00 57.00 57.00 66.00 75.00

mm
991 1219 1219 1448 1448 1676 1905 991 1219 1219 1448 1448 1676 1905 762 1118 1473 1829 991 1219 1219 1448 1448 1676 1905

43.41 1103 17.38 42.37 1076 12.25 43.41 1103 17.38 48.12 1222 12.25 52.00 1321 17.38 57.12 1451 12.25 66.12 1679 12.25 43.41 1103 17.38 42.37 1076 12.25 43.41 1103 17.38 48.12 1222 12.25 52.00 1321 17.38 57.12 1451 12.25 66.12 1679 12.25 39.06 39.06 992 19.44 992 19.44

821 20.11 795 20.11 821 20.11 795 20.11 821 20.11 795 20.11

50.11 1273 50.11 1273 50.11 1273 50.11 1273 50.11 1273 50.11 1273 59.11 1501 50.11 1273 50.11 1273 50.11 1273 50.11 1273 50.11 1273 50.11 1273 59.11 1501 42.17 1071 42.17 1071 56.17 1427 56.17 1427 50.11 1273 50.11 1273 50.11 1273 50.11 1273 50.11 1273 50.11 1273 59.11 1501

40.30 1024 29.11 32.34 31.30 32.34 31.30 32.34 31.30 821 20.11 795 20.11 821 20.11 795 20.11 821 20.11 795 20.11

45.00 1143 9.00 18.00 18.00 27.00 27.00 36.00 229 457 457 686 686 914

40.30 1024 29.11 25.50 25.50 648 12.17 648 12.17

45.00 1143 n/a 14.00 28.00 n/a 356 711

53.06 1348 19.44 67.06 1703 19.44 43.41 1103 17.38 42.37 1076 12.25 43.41 1103 17.38 48.12 1222 12.25 52.00 1321 17.38 57.12 1451 12.25 66.12 1679 12.25

39.50 1003 26.17 39.50 1003 26.17 32.34 31.30 32.34 31.30 32.34 31.30 821 20.11 795 20.11 821 20.11 795 20.11 821 20.11 795 20.11

42.00 1067 9.00 18.00 18.00 27.00 27.00 36.00 229 457 457 686 686 914

40.30 1024 29.11

45.00 1143

41
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
125 A and 200 A Residential Branch Units (Typical) Main Device (Typical) U T T U 200 A Commercial Branch Units (Typical)

R C B B L S Min. Mounting Channel M Floor or Finished Grade Level L C B

S Max.

S Max.

S Min. Mounting Channel

Determine Height for Mounting Channel


NOTE: S Max. , S Min. and M dimensions are based on local utility requirements and will determine proper height for mounting channel.

Three-Phase Branch Devices


If "S Min." for Bottom meter = 30" then R Mounting Top meter Channel would be at Height IN mm IN mm IN mm
9.00 18.00 18.00 27.00 27.00 36.00 9.00 18.00 18.00 27.00 27.00 36.00 n/a 14.00 27.44 28.00 n/a n/a 14.00 27.44 28.00 9.00 18.00 18.00 27.00 27.00 36.00 14.00 28.00 229 457 457 686 686 914 229 457 457 686 686 914 n/a 356 697 711 n/a n/a 356 697 711 229 457 457 686 686 914 356 711 39.00 48.00 48.00 57.00 57.00 66.00 75.00 39.00 48.00 48.00 57.00 57.00 66.00 75.00 30.00 44.00 57.44 58.00 72.00 30.00 30.00 44.00 57.44 58.00 72.00 39.00 48.00 48.00 57.00 57.00 66.00 75.00 44.00 58.00 72.00 991 1219 1219 1448 1448 1676 1905 991 1219 1219 1448 1448 1676 1905 762 1118 1459 1473 1829 762 762 1118 1459 1473 1829 991 1219 1219 1448 1448 1676 1905 1118 1473 1829 50.11 1273 50.11 1273 50.11 1273 50.11 1273 50.11 1273 50.11 1273 59.11 1501 50.11 1273 50.11 1273 50.11 1273 50.11 1273 50.11 1273 50.11 1273 59.11 1501 46.28 1176 42.17 1071 46.28 1176 56.17 1427 56.17 1427 42.17 1071 46.28 1176 42.17 1071 46.28 1176 56.17 1427 56.17 1427 50.11 1273 50.11 1273 50.11 1273 50.11 1273 50.11 1273 50.11 1273 59.11 1501 42.17 1071 56.17 1427 56.17 1427

Catalog Number

Height

Width

Depth

IN
EZM312-200 EZM313-125 EZM313-200 EZM314-125 EZM314-200 EZM315-125 EZM316-125 EZMH312-200 EZMH313-125 EZMH313-200 EZMH314-125 EZMH314-200 EZMH315-125 EZMH316-125 EZML311-400 EZML312-200 EZML312-400 EZML313-200 EZML314-200 EZML331-200 EZML331-400 EZML332-200 EZML332-400 EZML333-200 EZML334-200 EZMR312-200 EZMR313-125 EZMR313-200 EZMR314-125 EZMR314-200 EZMR315-125 EZMR316-125 EZMR332-200 EZMR333-200 EZMR334-200

mm

IN

mm
441 311 441 311 441 311 311 441 311 441 311 441 311 311 590 494 590 494 494 494 590 494 590 494 494 441 311 441 311 441 311 311 494 494 494

IN
8.09 7.09 8.09 7.09 8.09 7.09 7.09 8.09 7.09 8.09 7.09 8.09 7.09 7.09 9.44 9.44 9.44 9.44 9.44 9.44 9.44 9.44 9.44 9.44 9.44 8.09 7.09 8.09 7.09 8.09 7.09 7.09 9.44 9.44 9.44

mm
205 180 205 180 205 180 180 205 180 205 180 205 180 180 240 240 240 240 240 240 240 240 240 240 240 205 180 205 180 205 180 180 240 240 240

IN
9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 n/a 14.00 27.44 14.00 14.00 n/a n/a 14.00 27.44 14.00 14.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00 14.00 14.00 14.00

mm
229 229 229 229 229 229 229 229 229 229 229 229 229 229 n/a 356 697 356 356 n/a n/a 356 697 356 356 229 229 229 229 229 229 229 356 356 356

IN
32.34 31.30 32.34 31.30 32.34 31.30 32.34 31.30 32.34 31.30 32.34 31.30 37.81 25.50 37.81

mm

IN

mm
511 511 511 511 511 511 739 511 511 511 511 511 511 739 414 309 414 665 665 309 414 309 414 665 665 511 511 511 511 511 511 739 309 665 665

IN
11.07 11.07 11.07 16.82 19.66 25.82 25.82 11.07 11.07 11.07 16.82 19.66 25.82 25.82 7.74 13.56 31.80 13.56 27.56 13.56 7.74 13.56 31.80 13.56 27.56 11.07 11.07 11.07 16.82 19.66 25.82 25.82 13.56 13.56 27.56

mm
281 281 281 427 499 656 656 281 281 281 427 499 656 656 197 344 808 344 700 344 197 344 808 344 700 281 281 281 427 499 656 656 344 344 700

IN
22.18 13.18 13.18 9.93 12.77 9.93 9.93 22.18 13.18 13.18 9.93 12.77 9.93 9.93 24.02 11.73 20.64 11.73 11.73 25.73 24.02 11.73 20.64 11.73 11.73 22.18 13.18 13.18 9.93 12.77 9.93 9.93 11.73 11.73 11.73

mm
563 335 335 252 324 252 252 563 335 335 252 324 252 252 610 298 524 298 298 654 610 298 524 298 298 563 335 335 252 324 252 252 298 298 298

IN
12.23 11.19 12.23 11.19 12.23 11.19 11.19 12.23 11.19 12.23 11.19 12.23 11.19 11.19 21.53 13.33 21.53 13.33 13.33 13.33 21.53 13.33 21.53 13.33 13.33 12.23 11.19 12.23 11.19 12.23 11.19 11.19 13.33 13.33 13.33

mm
311 284 311 284 311 284 284 311 284 311 284 311 284 284 547 339 547 339 339 339 547 339 547 339 339 311 284 311 284 311 284 284 339 339 339

43.41 1103 17.38 42.37 1076 12.25 43.41 1103 17.38 48.12 1222 12.25 52.00 1321 17.38 57.12 1451 12.25 66.12 1679 12.25 43.41 1103 17.38 42.37 1076 12.25 43.41 1103 17.38 48.12 1222 12.25 52.00 1321 17.38 57.12 1451 12.25 66.12 1679 12.25 45.55 1157 23.21 39.06 992 19.44 69.61 1768 23.21 53.06 1348 19.44 67.06 1703 19.44 39.06 39.06 992 19.44 992 19.44 45.55 1157 23.21 69.61 1768 23.21 53.06 1348 19.44 67.06 1703 19.44 43.41 1103 17.38 42.37 1076 12.25 43.41 1103 17.38 48.12 1222 12.25 52.00 1321 17.38 57.12 1451 12.25 66.12 1679 12.25 39.06 992 19.44 53.06 1348 19.44 67.06 1703 19.44

821 20.11 795 20.11 821 20.11 795 20.11 821 20.11 795 20.11 821 20.11 795 20.11 821 20.11 795 20.11 821 20.11 795 20.11 960 16.28 648 12.17 960 16.28

40.30 1024 29.11

45.00 1143

40.30 1024 29.11

45.00 1143

39.50 1003 26.17 39.50 1003 26.17 25.50 37.81 25.50 37.81 648 12.17 960 16.28 648 12.17 960 16.28

42.00 1067

39.50 1003 26.17 39.50 1003 26.17 32.34 31.30 32.34 31.30 32.34 31.30 25.50 821 20.11 795 20.11 821 20.11 795 20.11 821 20.11 795 20.11 648 12.17

42.00 1067

40.30 1024 29.11 39.50 1003 26.17 39.50 1003 26.17

45.00 1143

42.00 1067

42
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Closing PlatesMain Devices EZM main devices are supplied with two closing plates, one on each side of the enclosure to cover and seal openings for horizontal cross bus. Right-side closing plate secured to box side by three 1/4-20 captive screws and three 1/4-inch hex nuts. Two sealing wing nuts for this side are provided in a bag assembly packed with each main device. Holes in wing nuts and lanced ears in closing plates are provided to seal closing plate to box sides. Install one wing nut on screw extending through closing plate at bottom center and another wing nut on screw extending through closing plate at the top front to seal. Left-side closing plate secured to box side by three 1/4-20 carriage head screws and three 1/4-inch hex nuts. Two sealing wing nuts for this side are provided in a bag assembly packed with each main device. Holes in wing nuts and lanced ears in closing plates are provided to seal closing plate to box sides. Install one wing nut on screw extending through closing plate at bottom center and another wing nut on screw extending through closing plate at the top rear to seal. Where sealing is not required, install screws from outside to inside of unit and secure with hex nuts.
Closing Plates Provided with Main Device for Use at Each End of Metering Line Up

Closing PlatesBranch Units EZM branch units are shipped without closing plates, but are designed to receive one from a main device. To install, remove closing plate from side of main device before connecting branch unit to main device. After last branch unit is installed in lineup, follow closing plate installation instructions for main devices. Closing PlatesMain Devices and Branch Units When adding onto an existing EZM (Type M01) metering equipment line up, repeat this procedure by moving closing plate to end of line up.

Left-Side Closing Plate Installs with Hex Nuts (As Viewed from Inside)

Right-Side Closing Plate Installs with Captive Screws

43
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
HORIZONTAL CROSS BUS
800 A aluminum horizontal cross bus is standard in the following devices: 400 A, 600 A, 800 A, and 1000 A main circuit breaker devices 400 A, 600 A, and 800 A main fusible switches 400 A and 800 A main lugs terminal boxes 125 A and 200 A residential branch units Right end of each horizontal cross bus bar is supplied with 1/2-13 captive bolt and VISI-TITE nut. Left end of each horizontal cross bus bar has a slotted end. 800 A horizontal cross bussed units will connect with 1200 A horizontal cross bussed units. 1f main and branch units have 3 horizontal cross bus bars (f, f and neutral).
Right End of 3f Horizontal Cross Bus, Shown with VISI-TITE Nuts Left End of 3f Horizontal Cross Bus, Shown with Slotted End Bus Bars

3f main and branch units have 4 horizontal cross bus bars (Af, Bf, Cf and neutral). 1f main or branch units will not interconnect with 3f main or branch units. 1200 A copper horizontal cross bus is standard in the following devices: 1200 A main circuit breaker devices (must be center mounted when used with 125 A and 200 A residential branch units). 1600 A circuit breaker devices (must always be center mounted) 1600 A main lugs terminal box (must always be center mounted) 200 A commercial branch units 400 A commercial branch units Right end of each horizontal cross bus bar is supplied with 1/2-13 captive bolt and VISI-TITE nut. Left end of each horizontal cross bus bar has a slotted end. 1200 A horizontal cross bussed units will connect with 800 A horizontal cross bussed units. 1f main and branch units have 3 horizontal cross bus bars (f, f and neutral). 3f main and branch units have 4 horizontal cross bus bars (Af, Bf, Cf and neutral). 1f main or branch units will not interconnect with 3f main or branch units.

44
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Equipment Grounding Procedure 1. Install mounting channels to wall at proper height (refer to Mounting Channel on page 39). 2. Remove closing plates from sides of EZM main device next to where EZM branch sections is to be installed. 3. Position units on mounting channel next to each other, but do not secure swingable mounting brackets to wall at this time. 4. Remove outer covers from EZM main device and exterior trims from EZM branch sections, (refer to Exterior Trim on page 47). 5. Remove individual meter socket trim from over horizontal cross bus area of EZM branch sections, (refer to Individual Meter Socket Trim on page 47). 6. Bond enclosures together by sliding three captive screws from the RIGHT side of unit through holes in box side (closing plate holes), and through LEFT side of adjacent enclosure. Install three 1/4-20 hex nuts with star washer provided onto 1/4-20 captive screws and torque to 50 lb-in (5.6 Nm). Bonding for equipment ground path is complete, and enclosure gaskets are compressed to seal connection between units. 7. Replace closing plates at each end of metering equipment lineup (refer to Closing Plates on page 43). At this point the enclosures are connected together and a bonded equipment ground path is established. Next installation step involves connection of the horizontal cross bus assemblies.
Tighten Until Outer Head Twists Off and RED Indicating Disc Falls Away

Captive Equipment Bonding Screws are Located on Right Side of Each EZM Main and Branch Device

Install Hex Nuts with Star Washers onto Captive Screws

VISI-TITE Nut Horizontal Cross Bus Connectors The VISI-TITE nut horizontal cross bus connector is a high-strength (grade 5) 1/2-13 UNC, double-headed torque indicating nut. Installed as an integral part of the horizontal cross bus structure in every EZM main and branch device, this unique nut makes it possible to ensure proper torque at each connection without the need for a torque wrench. The torque indicating VISI-TITE nut assembly also makes it possible to reduce equipment installation time over other designs requiring the use of a torque wrench. When making EZM metering equipment cross bus connections there is no need for a torque wrench. Use a long handle socket wrench to tighten the outer VISI-TITE nut head until it twists off and releases the RED plastic warning disc.

Shown with RED Indicating Disc in Place

Shown with Outer Head and RED Indicating Disc Falling Away

If the RED disc remains visible during inspection, the horizontal cross bus assembly has not yet been tightened. Once the outer VISI-TITE nut head is twisted off, an inner hex-head nut remains for use with a torque wrench on maintenance checks or relocation of equipment (torque 50 lb-ft (600 lb-in) [68 Nm]). All phase and neutral connections to the horizontal cross bus structure are now completed. Final step is to secure the swingable mounting brackets to wall at top and bottom of each EZM main and branch unit enclosure.

Shown After Installation of Cross Bus Structure is Completed

45
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Sealing Rings for Ring-Type Meter Sockets Standard Snap-Type Aluminum Sealing Ring29209-100-01, standard sealing ring for all ring-type EZM branch sections. Replacement sealing rings may be ordered separately. Snap-Type Stainless Steel Sealing Ring29209-100-02, non-standard sealing ring. Order separately and install when required by the local utility. Latch-Type Stainless Steel Sealing Ring29008G, non-standard sealing ring. Order separately and install when required by the local utility. Screw-Type Aluminum Sealing Ring29008W, non-standard sealing ring. Order separately and install when required by the local utility.
Latch-Type Sealing Ring

Snap-Type Sealing Ring

Screw-Type Sealing Ring

Circuit Breaker Doors 125 A, 200 A, and 400 A EZM branch sections are supplied with factoryinstalled circuit breaker doors constructed of durable impact-resistant material. The following replacement kits are available: BCV replacement door for vertically operated circuit breaker handles: 125 A ring and ringless residential branch sections 200 A ring and ringless residential branch sections 200 A ringless commercial branch sections Supplied with built-in latch with padlock provisions.

BCV Circuit Breaker Door Shown with Door Closed

BCM replacement door for vertically operated circuit breaker handles: 400 A ringless commercial branch sections 400800 A standard and EUSERC fusible switch main devices 4001000 A standard circuit breaker main devices 4001200 A EUSERC circuit breaker main devices Supplied with built-in latch with padlock provisions.

BCM Circuit Breaker Cover Shown with Door Opened

46
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Branch Unit Outer Covers for Tenant Circuit Breaker and Individual Meter Socket Compartments 125 A and 200 A Ring-Type Residential Branch Unit Outer Covers for Tenant Circuit Breaker Compartments and Individual Meter Socket Trims Outer tenant circuit breaker covers can be removed without disturbing sealed utility meters mounted to the individual meter socket trim. All unmetered conductor compartments remain sealed and isolated when outer tenant circuit breaker covers are removed. Outer tenant circuit breaker covers are supplied with individual tenant circuit breaker doors that are padlockable. An individual meter socket trim is supplied for each meter socket position. Each ring-type meter socket trim has a rim formed into the cover to support the base of the utility meter.
EZM113125 (Ring-Type) Outer Tenant Circuit Breaker Cover and Individual Meter Socket Trims EZM113200 (Ring-Type) Outer Tenant Circuit Breaker Cover and Individual Meter Socket Trims

Aluminum snap-type sealing rings are standard and are used to attach the base of the utility meter to the rim. A slot is provided in the tab of the sealing ring for the local utility to install their seal to lock meter in place. 125 A, 200 A, and 400 A Ringless-Type Branch Unit Outer Covers for Tenant Circuit Breaker Compartments and Individual Meter Socket Trims Outer tenant circuit breaker covers can be removed without disturbing sealed utility meters secured under individual meter socket trims. All unmetered conductor compartments remain sealed and isolated when outer tenant circuit breaker covers are removed. Outer tenant circuit breaker covers are supplied with individual tenant circuit breaker doors that are padlockable. Individual ringless-type meter socket trims are supplied with stainless steel hasps that extend through cover and stainless steel latches for sealing trims to branch unit while utility meter or closing plate is mounted in meter socket. Ringless meter socket trims have provisions to accept utility seals including plastic padlocks, lead and wire seals, padlocks, and barrel locks to prevent unauthorized access to meter socket compartment.

EZML113-200 (Ringless-Type) Outer Tenant Circuit Breaker Cover and Individual Meter Socket Trims

EZML332-200 (Ringless-Type) Outer Tenant Circuit Breaker Cover and Individual Meter Socket Trims

47
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Individual Meter Socket Closing Plates LEXAN Meter Socket Closing Plate for Residential Branch Units Order separately (catalog number 29007). For use with 125 A and 200 A residential branch units. Molded of LEXAN #141-112 polycarbonate resin. LEXAN offers high impact and tensile strength characteristics, and contains an ultra-violet inhibitor to ensure years of clear visibility.
LEXAN Closing Plate

Closing plates have four LEXAN blades as a part of the molding used to engage meter socket jaws. Metal Meter Socket Closing Plate for Ringless-Type Branch Units Order separately (catalog number RSG4). For use with ringless-type branch units. Metal closing plate attaches to individual meter socket trim from the backside with four hold-down screws. Closing plate can not be removed from individual meter socket trim with meter socket trim installed on branch unit.

Ringless-Type Metal Closing Plate

48
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Branch Unit Load Neutral Terminals 125 A branch unit load neutral terminals accept one 14-2/0 AWG copper or one 12-2/0 AWG aluminum conductor per meter socket position. 200 A branch unit load neutral terminals accept one 6-300 kcmil aluminum or copper conductor per meter socket position. 400 A branch unit load neutral terminals will accept one 1-600 kcmil or two 1-250 kcmil aluminum or copper conductor per meter socket position. Branch Unit Load Equipment Grounding Terminals Branch units are supplied with load equipment grounding terminals for feeders to downstream panelboards.
125 A Branch Unit Load Neutral Terminals

Grounding terminals on 125 A and 200 A branch devices have provisions to accept one 14-2/0 AWG copper, or one 12-2/0 aluminum conductor per meter socket position. Grounding terminals on 400 A branch devices have provisions to accept one 6-300 kcmil copper or aluminum conductor per meter socket position. Grounding terminals are factory-installed at the bottom of the wiring gutter compartment, but may be relocated to the top of the wiring gutter compartment when exiting out the top of the device.

200 A Branch Unit Load Neutral Terminals

400 A Branch Unit Load Neutral Terminals

Branch Unit Load Equipment Grounding Terminals

49
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Branch Unit Tenant Circuit Breaker Types and Meter Socket Congurations EZM branch units are supplied with meter sockets and provisions for mounting tenant circuit breakers to feed downstream type QO or HOM load centers, or type NQOD panelboards. The following table includes standard and optional branch unit features, along with tenant circuit breaker types, and meter socket congurations. 125 A and 200 A Ring-Type EZM Residential Branch Units (1f OUT)
Meter Socket Ring-Type (Quantity) 4-Jaw Meter Socket 1f IN Catalog Number
125 A Ring-Type Residential without Bypass 3-Position 4-Position 5-Position 6-Position EZM113125 EZM114125 EZM115125 EZM116125 EZM313125 EZM314125 EZM315125 EZM316125 QO, QO-VH or QOH QO, QO-VH or QOH QO, QO-VH or QOH QO, QO-VH or QOH

5-Jaw Meter Socket 3f IN Catalog Number

Circuit Breaker Type (2-pole only)

200 A Ring-Type Residential without Bypass 2-Position 3-Position 4-Position EZM112200 EZM113200 EZM114200 EZM312200 EZM313200 EZM314200 Q2M, Q2M-VH or Q2MH Q2M, Q2M-VH or Q2MH Q2M, Q2M-VH or Q2MH

Ring-Type Residential Meter Socket Compartment Standard Features 1f IN, 1f OUT branch sections include three horizontal cross bus bars and 4-jaw meter sockets. 3f IN, 1f OUT branch sections include four horizontal cross bus bars and 5-jaw meter sockets.
EZM115125 EZM113200

120/208 Vac, 1f3W (derived from a 208Y/120 Vac, 3f4W network). Standard 3f IN/1f OUT branch units are suitable for use on this system. 120/240 Vac, delta, 1f3W (fed from transformers Af and Cf only). Connection to high-leg Bf not permitted for use on this system. Standard 3f IN/1f OUT branch units are not suitable for use on this system. Special branch units are available for this system by adding sufx: CA to catalog number, for example: EZM313125CA. Meter socket jaws are front removable and spring reinforced. Meter blade guides supplied as standard on both line and load side meter socket jaws. 200 A continuous duty rated meter socket jaws supplied without bypass.

125 A and 200 A Ring-Type Meter Socket, 4-Jaw without Bypass

125 A and 200 A Ring-Type Individual Meter Socket Trim Shown without Sealing Ring

Aluminum snap-type sealing ring supplied with each meter socket as standard.

50
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
125 A Tenant Circuit Breaker Compartment 125 A maximum branch units will accept 40125 A, 2-pole, plug-on type QO, QO-VH or QOH circuit breakers (order circuit breakers separately). Refer to pages 4 and 5 for meter center available short circuit current ratings with the above tenant circuit breakers installed. 200 A Tenant Circuit Breaker Compartment 200 A maximum branch units listed in this section will accept 100200 A, 2-pole, bolt-on type Q2M, Q2M-VH, or Q2MH circuit breakers.
125 A QO Tenant Circuit Breaker Base (2-Pole) QO2100 Tenant Circuit Breaker Installed

Or with the use of plug-on adapter catalog number EZM125QOA, these units will accept 40125 A, 2-Pole plug-on type QO, QO-VH, or QOH circuit breakers. (Order circuit breakers and adapters separately). Refer to pages 4 and 5 for meter center available short circuit current ratings with the above tenant circuit breakers installed. Optional Ring-Type Residential Meter Socket Features 5-jaw kit, catalog number 5J (one kit required per meter socket) is available for eld installation and can be mounted on the meter socket base assembly at 3, 6, or 9 oclock positions. Used to convert a 4-jaw 125 A or 200 A ring-type branch unit meter socket to a 5-jaw meter socket.

200 A Q2M Tenant Circuit Breaker Base (2-Pole)

Q2M2200VH Tenant Circuit Breaker Installed

5-jaw meter sockets are required for a 120/208 Vac, 1f 3W service derived from a 208Y/120 Vac, 3f4W system. Manual slider type bypass kit, catalog number MM200MB, is available for eld installation. Kit includes manual slider type bypass, and replacement individual meter socket trim (trim is notched to allow handle of slider bypass to pass through rim with meter installed). Slider type bypass is intended for temporary use only (not continuous duty rated). Available short circuit current rating of metering equipment is limited to 10,000 RMS symmetrical amperes with slider type bypass kits installed. Plug-on adapter kit, catalog number EZM125QOA, available for use in 200 A branch units that use bolt-on type Q2M, 2-pole tenant circuit breakers. Kit will accept 40125 A, 2-pole plug-on type QO, QO-VH, or QOH circuit breakers. (Order circuit breakers and adapters separately).

5-Jaw Kit (5J) Installed at the 9 Oclock Position

EZM125QOA, 2-Pole, Plug-On Adapter Kit for Use in Q2M Bolt-On Tenant Circuit Breaker Compartments Manual Slider Type Bypass Shown in Closed Position with Handle Extending Through Notch in Rim of Meter Socket Trim Manual Slider Type Bypass Shown in Open Position with Handle Secured by Meter Socket Sealing Ring

51
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
125 A and 200 A Ringless-Type EZMR and EZMH Residential Branch Units (1f OUT)
Meter Socket Ringless-Type (Qty.) 5-Jaw Meter Socket 1f IN Catalog Number
125 A Ringless without Bypass 3-Position 4-Position 5-Position 6-Position 200 A Ringless without Bypass 2-Position 3-Position 4-Position 125 A Ringless with Horn Bypass 3-Position 4-Position 5-Position 6-Position 200 A Ringless with Horn Bypass 2-Position 3-Position 4-Position EZMH112200 EZMH113200 EZMH114200 EZMH312200 EZMH313200 EZMH314200 Q2M, Q2M-VH or Q2MH Q2M, Q2M-VH or Q2MH Q2M, Q2M-VH or Q2MH EZMH113125 EZMH114125 EZMH115125 EZMH116125 EZMH313125 EZMH314125 EZMH315125 EZMH316125 QO, QO-VH or QOH QO, QO-VH or QOH QO, QO-VH or QOH QO, QO-VH or QOH EZMR112200 EZMR113200 EZMR114200 EZMR312200 EZMR313200 EZMR314200 Q2M, Q2M-VH or Q2MH Q2M, Q2M-VH or Q2MH Q2M, Q2M-VH or Q2MH EZMR113125 EZMR114125 EZMR115125 EZMR116125 EZMR313125 EZMR314125 EZMR315125 EZMR316125 QO, QO-VH or QOH QO, QO-VH or QOH QO, QO-VH or QOH QO, QO-VH or QOH

5-Jaw Meter Socket 3f IN Catalog Number

Circuit Breaker Type (2-pole only)

Ringless Residential Meter Socket Compartment Standard Features


EZMH114125

1f IN, 1f OUT branch sections (include 3 horizontal cross bus bars). 5-jaw meter sockets supplied as standard. 3f IN, 1f OUT branch sections (include 4 horizontal cross bus bars). 5-jaw meter sockets supplied as standard. 120/208 Vac, 1f3W (Derived from a 208Y/120 Vac, 3f4W Service). Standard 3f IN/1f OUT branch units are suitable for use on this system. 120/240 Vac, 1f3W (fed from transformers Af and Cf only). Connection to high-leg Bf not permitted for use on this system. Standard 3f IN/1f OUT branch units are not suitable for use on this delta system. Special branch units are available for this system by adding sufx: CA to catalog number (Examples: EZMR313125CA, EZMH314125CA, EZMR313200CA and EZMH312200CA).

125 A and 200 A Ringless 125 A and 200 A Ringless-Type Meter Socket with Horn Individual Meter Socket Trim Type Bypass Shown with Stainless Steel Hasp and Latch for Use with Utility Seals

52
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Meter socket jaws are front removable and spring reinforced. Meter blade guides supplied as standard on both line and load side meter socket jaws. 200 A continuous duty rated meter socket jaws supplied with 5th jaw. Individual ringless-type meter socket trims are supplied with stainless steel hasps that extend through cover, and stainless steel latches for sealing trims to branch unit. The utility meter or closing plate is mounted in meter socket. Ringless meter socket trims have provisions to accept utility seals including plastic padlocks, lead and wire seals, and barrel locks to prevent unauthorized access to meter socket compartment. 125 A Tenant Circuit Breaker Compartment 125 A maximum residential branch units will accept 40125 A, 2-pole, plug-on type QO, QO-VH, or QOH circuit breakers (order circuit breakers separately). Refer to pages 4 and 5 for meter center available short circuit current ratings with the above tenant. 200 A Tenant Circuit Breaker Compartment 200 A maximum branch units listed in this section will accept 100200 A, 2-pole, bolt-on type Q2M, Q2M-VH, or Q2MH circuit breakers. Or with the use of plug-on adapter catalog number EZM125QOA, these units will accept 40125 A, 2-pole plug-on type QO, QO-VH, or QOH circuit breakers. (Order circuit breakers and adapters separately.) Refer to pages 4 and 5 for meter center available short circuit current ratings with the above tenant circuit breakers installed. Optional Ringless Residential Meter Socket Features Barrel lock head protector kit, catalog number MMBLC (one kit covers six meter sockets) is available for eld installation. Knockout in individual meter socket trim is provided for barrel lock head protector kit. Secure head protector kit to trim with lock nut supplied. Barrel lock not supplied. Horn bypass kit, catalog number MMHB (one kit required per meter socket) is available for eld installation on type EZMR branch units. To install horn bypass kit, remove one of four 1/4-inch hex nuts from meter socket jaw assemblies and position horn bypass bus bar connector on top of meter jaw. Secure with hex nut (torque 75 lb-in [8.5 Nm]). Repeat this process for remaining three jaw positions. Horn bypass bus bars are of different shapes, and must be installed as shown (refer to instructions packed with each kit). Horn bypass factory installed on EZMH device.

125 A QO Tenant Circuit Breaker Base (2-Pole)

QO2100 Tenant Circuit Breaker Installed

200 A Q2M Tenant Circuit Breaker Base (2-Pole)

Q2M2200VH Tenant Circuit Breaker Installed

Ringless-Type Individual Meter Socket Trim Shown with Barrel Lock Head Protector (Catalog Number MMBLC)

Ringless-Type Individual Meter Socket Trim Shown with Barrel Lock Installed Through Cover and Lock Bracket (Reverse View)

Residential Horn Type Bypass Kit Available for Use on EZMR Ringless Branch Units, and Standard on EZMH Ringless Branch Units

53
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
200 A and 400 A Ringless-Type EZML Commercial Branch Units (1f OUT)
Meter Socket Ringless-Type (Qty.) 5-Jaw Meter Socket 1f IN Catalog Number
200 A Ringless with Lever Type Bypass and Jaw Release 1-Position 2-Position 3-Position 4-Position EZML111200 EZML112200 EZML113200 EZML114200 Not Available EZML312200 EZML313200 EZML314200 QE-VH QE-VH QE-VH QE-VH

5-Jaw Meter Socket 3f IN Catalog Number

Circuit Breaker Type (2-pole only)

400 A Ringless with Lever Type Bypass and Jaw Release 1-Position 2-Position Not Available Not Available EZML311-400 EZML312-400 LAL26400 (factory installed) LAL26400 (factory installed)

Ringless Commercial Meter Socket Compartment Standard Features 1f IN, 1f OUT branch units (include 3 horizontal cross bus bars). 5-jaw meter sockets supplied as standard. Not available in 400 A branch unit. 3f IN, 1f OUT branch units (include 4 horizontal cross bus bars). 5-jaw meter sockets supplied as standard.
EZML113200 EZML312400

120/208 Vac, 1f3W (derived from a 208Y/120 Vac, 3f4W service). Standard 3f IN/1f OUT branch units are suitable for use on this system. 120/240 Vac, 1f3W (fed from transformers Af and Cf only). Connection to high-leg Bf not permitted for use on this system. Standard 3f IN/1f OUT branch units are not suitable for use on this Delta system. Special branch units are available for this system by adding sufx: CA to catalog number (Examples: EZML313125CA and EZML312400CA). 320 A continuous duty rated meter sockets supplied with lever bypass Lever bypass meter sockets are supplied with jaw release. Lexan shield supplied as an integral part of meter socket assembly and used as a guide to assist mounting of utility meter. Individual ringless-type meter socket trims are supplied with stainless steel hasp that extend through cover and stainless steel latches for sealing trims to branch unit while utility meter or closing plate is mounted in meter socket. Ringless meter socket trims have provisions to accept utility seals including plastic padlocks, lead and wire seals, padlocks, and barrel locks to prevent unauthorized access to meter socket compartment.

200 A Ringless-Type Meter Socket, 5-Jaw with Lever Type Bypass Shown with Lexan Shield over Line and Load Meter Jaws

400 A Ringless-Type Meter Socket, 5-Jaw with Lever Type Bypass Shown with Lexan Shield over Line and Load Meter Jaws

54
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
200 A Tenant Circuit Breaker Compartment 200 A maximum commercial branch units accept 70200 A, 2-pole, plug-on type QE-VH circuit breakers (order circuit breakers separately). Refer to pages 4 and 5 for meter center available short circuit current ratings. 400 A Tenant Circuit Breaker Compartment LAL 26400 circuit beakers are factory installed into 400 A maximum commercial branch units. Refer to pages 4 and 5 for meter center available short circuit current ratings.
200 A QE Commercial Tenant Circuit Breaker Base (2-Pole) QE2200VH Tenant Circuit Breaker Installed

Other ampere ratings of LAL circuit breakers are available by special order; consult your local Square D sales ofce for details. Optional Ringless Residential Meter Socket Features Barrel lock head protector kit, catalog number MMBLC (one kit covers six meter sockets) is available for eld installation. Knockout in individual meter socket trim is provided for barrel lock head protector kit. Secure head protector kit to trim with lock nut supplied. Barrel lock not supplied.

LAL26400 Tenant Circuit Breaker Supplied Factory Installed

Ringless-Type Individual Meter Socket Trim Shown with Barrel Lock Head Protector

Ringless-Type Individual Meter Socket Trim Shown with Barrel Lock Installed Through Cover and Lock Bracket (Reverse View)

55
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
200 A and 400 A Ringless-Type Commercial Branch Units (3f OUT)
Meter Socket Ringless-Type (Quantity)
200 A Ringless without bypass 2-Position 3-Position 4-Position EZMR332200 EZMR333200 EZMR334200 QE-VH QE-VH QE-VH

7-Jaw Meter Socket` 3f IN

Circuit Breaker Type (3-pole only)

200 A Ringless with Lever Type Bypass and Jaw Release 1-Position 2-Position 3-Position 4-Position EZML331200 EZML332200 EZML333200 EZML334200 QE-VH QE-VH QE-VH QE-VH

400 A Ringless with Lever Type Bypass and Jaw Release

EZML332200

EZML331400

1-Position 2-Position

EZML331400 EZML332400

LAL36400 (factory installed) LAL36400 (factory installed)

Ringless Commercial Meter Socket Compartment Standard Features 3f IN, 3f OUT branch units (include 4 horizontal cross bus bars). 7-jaw meter sockets supplied as standard. 320 A continuous duty rated meter sockets are supplied with lever-type bypass. Lever-type bypass meter socket is supplied with jaw release. LEXAN shield supplied as an integral part of meter socket assembly and used as a guide to assist mounting of utility meter.
200 A Ringless-Type Meter Socket, 7-Jaw without Bypass Shown with Line and Load Side Blade Guides 200 A Ringless-Type Individual Meter Socket Trim Shown with Stainless Steel Hasp and Latch for Use with Utility Seals

Individual ringless-type meter socket trims are supplied with stainless steel hasps that extend through cover and stainless steel latches for sealing trims to branch unit while utility meter or closing plate is mounted in meter socket. Ringless meter socket trims have provisions to accept utility seals including plastic padlocks, lead and wire seals, and barrel locks to prevent unauthorized access to meter socket compartment.

400 A Ringless-Type Meter Socket, 7-Jaw with Lever Type Bypass Shown with Lexan Shield over Line and Load Meter Jaws

400 A Ringless-Type Individual Meter Socket Trim

56
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
200 A Tenant Circuit Breaker Compartment 200 A maximum commercial branch units will accept 70200 A, 3-pole, plug-on type QE-VH circuit breakers. (Order circuit breakers separately). Refer to pages 4 and 5 for meter center available short circuit current ratings. 400 A Tenant Circuit Breaker Compartment LAL36400 circuit breakers are factory installed into 400 A maximum commercial branch units. Refer to pages 4 and 5 for meter center available short circuit current ratings. Other ampere ratings of LAL circuit breakers are available by special order; consult your local Square D sales ofce for details. Optional Ringless Commercial Meter Socket Features Barrel lock head protector kit, catalog number MMBLC (one kit covers six meter sockets) is available for eld installation. Knockout in individual meter socket trim is provided for barrel lock head protector kit. Secure head protector kit to trim with lock nut supplied. Barrel lock not supplied.
LAL36400 Tenant Circuit Breaker Supplied Factory Installed

200 A QE Commercial Tenant Circuit Breaker Base (3-Pole)

QE3200VH Tenant Circuit Breaker Installed

Ringless-Type Individual Meter Socket Trim Shown with Barrel Lock Head Protector

Ringless-Type Individual Meter Socket Trim Shown with Barrel Lock Installed Through Cover and Lock Bracket (Reverse View)

57
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
FACTORY PHASE BALANCING
Branch unit meter sockets are phase balanced at the factory according to the following table.
Meter Socket (Quantity) Catalog Number Af Bf (Quantity) Af Cf (Quantity) Bf - Cf (Quantity)

125 A Branch Units (used on 120/208 Vac, 1f3W service derived from a 208Y/120 Vac, 3f4W system) 3-Position 4-Position 5-Position 6-Position 3-Position 4-Position 5-Position 6-Position 3-Position 4-Position 5-Position 6-Position EZM313125 EZM314125 EZM315125 EZM316125 EZMR313125 EZMR314125 EZMR315125 EZMR316125 EZMH313125 EZMH314125 EZMH315125 EZMH316125 1 1 2 2 1 1 2 2 1 1 2 2 1 2 1 2 1 2 1 2 1 2 1 2 1 1 2 2 1 1 2 2 1 1 2 2

200 A Branch Units (used on 120/208 Vac, 1f3W service derived from a 208Y/120 Vac, 3f4W system) 2-Position 3-Position 4-Position 2-Position EZM312200 EZM313200 EZM314200 EZMR312200 EZMR313200 EZMR314200 EZMH312200 EZMH313200 EZMH314200 EZML312200 EZML313200 EZML314200 1 1 1 1 1 1 1 1 1 1 1 1 0 1 2 0 1 2 0 1 2 0 1 2 1 1 1 1 1 1 1 1 1 1 1 1

EZM314125

3-Position 4-Position 2-Position 3-Position 4-Position 2-Position 3-Position 4-Position

400 A Branch Units (used on 120/208 Vac, 1f3W service derived from a 208Y/120 Vac, 3f4W system) 1-Position 2-Position EZML311400 EZML312400 0 1 1 0 0 1

NOTE: Refer to page 59 for phase balancing branch units in the eld.

58
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
A B C

Phase Balancing Flexibility The major benet of factory phase balancing is that most jobs will not require eld phase balancing. To see if meter socket phase balancing in the eld is required (refer to wiring diagram for complete instructions): 1. Determine the load in amperes on each phase of the transformer using handle rating of tenant circuit breakers installed at each number of meter sockets. Use Phase Balancing Chart to determine total number of connections each meter socket makes on each phase of transformer. 2. If phase balancing is required, determine which meter sockets should be changed to properly phase balance metering equipment lineup.

STARTING POSITION Meter Socket Phasing: Af and Cf

3. Once meter socket(s) is selected to be phase balanced, remove individual meter socket trim from each meter socket to be phase balanced. The vertical bus bars running top to bottom in the branch unit behind each meter socket are phased: Af, Bf, Cf, left to right. 4. By moving only the line side meter socket Z shaped connectors per meter socket to be changed, phase balancing can easily be accomplished on site:
Starting Position
Af and Bf Af and Cf Bf and Cf can be changed to can be changed to can be changed to

Possible Ending Position (by moving only one Z connector)


Af and Cf Af and Bf or Bf and Cf Af and Cf

Step 1: Remove hex nut from Af line side connection to vertical bus.

To change an Af and Cf meter socket to a Bf and Cf meter socket:

Step 2: Loosen hex nut from Af line side meter socket jaw and slide Z connector down to free connector from stud.

Step 4: Slide Z connector up to engage stud on Bf vertical bus.

Step 6: Replace hex nut (removed in step one) onto stud of Bf vertical bus and torque to 75 lb-in (8 Nm). Phase balancing of meter socket is complete: Bf and Cf.

Step 5: Torque hex nut of meter socket jaw to 75 lb-in (8 Nm).

Step 3: Rotate Z connector to right and align with stud on Bf vertical bus.

59
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
EZM MAIN DEVICE TYPES AND CONFIGURATIONS
EZM main devices are available as main circuit breakers, main fusible switches, or main lugs terminal boxes; for use in single Phase or three Phase applications. An EZM main device is required upstream from EZM branch units even in the case of the NEC six subdivision rule. EZM main devices ending in -CB, -FS or -TB are congured for overhead (Top feed) or underground (bottom feed) service, and are supplied with lugs. EZM main devices ending in -CBU or -FSU are congured for underground (bottom feed) service only, and are equipped with lug landing pads (lugs must be ordered separately). Circuit Breaker Main Devices (Fed from Overhead or Underground Service)
Line Phase TerminalWire Line Neutral Range TerminalWire (AWGRange (AWGkcmil, kcmil, Al/Cu) Al/Cu) Service Ground Terminal Wire Range (AWGkcmil, Al/Cu)

Service Type

Ampere Rating

Catalog Number

Circuit Breaker (Supplied Factory Installed)

1f IN Circuit Breaker Main Devices (Fed from Overhead or Underground Service)

EZM1800CB

400 600 800 1f3W, 120/240 Vac 1000 1200 1600

EZM1400CB EZM1600CB EZM1800CB EZM11000CB EZM11200CB EZM11600CB

LHP26400 c MHP26600 c MHP26800 c MHP261000 c PAF2026 with PA21200RC PAF2026 with PA21600RC

(1) 1/0 600 or (2) 1/0 250 f (3) 3/0 500 f (3) 3/0 500 f (3) 3/0 500 f (4) 1/0 750 (6) 1/0 750

(1) 1/0 600 or (2) 1/0 250 q (4) 3/0 500 p (4) 3/0 500 p (4) 3/0 500 p (4) 1/0 750 (6) 1/0 750

(1) 6 300 (1) 6 300 (1) 6 300 (1) 6 300 (1) 6 300 (1) 6 300

3f IN Circuit Breaker Main Devices (Fed from Overhead or Underground Service) 400 600 3f4W, 208Y/ 120 Vac or 240/120 Vac Delta 800 1000 1200 1600 c f q p EZM3400CB EZM3600CB EZM3800CB EZM31000CB EZM31200CB EZM31600CB LHP36400 c MHP36600c MHP36800 c MHP361000 c PAF2036 with PA31200RC PAF2036 with PA31600RC (1) 1/0 600 or (2) 1/0 250 f (3) 3/0 500 f (3) 3/0 500 f (3) 3/0 500 f (4) 1/0 750 (6) 1/0 750 (1) 1/0 600 or (2) 1/0 250 q (4) 3/0 500 p (4) 3/0 500 p (4) 3/0 500 p (4) 1/0 750 (6) 1/0 750 (1) 6 300 (1) 6 300 (1) 6 300 (1) 6 300 (1) 6 300 (1) 6 300

Handle extension available, order kit, AHEXLI, handle is hinged allowing it to be tucked under door on cover. Alternate lugs kits are available for use on line side of circuit breaker (refer to Digest). Alternate neutral lug available, order one (1) kit, MMLK500 for (2) 3/0 AWG500 kcmil Al/Cu (kit includes three, 2-barrel lugs), Neutral will accommodate one, 2-barrel lug only. Alternate neutral lugs available, order one (1) kit, MMLK250 for (1) 1/0 AWG600 kcmil or (2) 1/0 AWG250 kcmil Al/Cu (kit includes three, 2-barrel lugs), Neutral will accommodate two, 2-barrel lugs only.

EZM31600CB

60
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Circuit Breaker Main Devices (Fed from Underground Service only)
Circuit Breaker (Supplied Factory Installed) Line Phase and Neutral Lug Landing Pads provided for use with Crimp-Type Lugs (2-Hole Mounting) Quantity of Lugs permitted per Pad Service Ground Terminal Wire Range (AWGkcmil, Al/Cu)

Service Type

Ampere Rating

Catalog Number

1f IN Circuit Breaker Main Devices (Fed from Underground Service only) 400 600 1f3W, 120/240 Vac 800 1000 1200 EZM1400CBU a EZM1600CBU a EZM1800CBU a LHF26400 c MHF26600 c MHF26800 c 1 (order lugs separately) 2 (order lugs separately) 2 (order lugs separately) 3 (order lugs separately) 3 (order lugs separately) (1) 6 300 (1) 6 300 (1) 6 300 (1) 6 300 (1) 6 300

EZM11000CBUa MHF221000 c EZM11200CBUa MHF221200 c

3f IN Circuit Breaker Main Devices (Fed from Underground Service only) 400 3f4W, 208Y/120 Vac or 240/120 Vac Delta 600 800 1000 1200 c a EZM3400CBUa EZM3600CBUa EZM3800CBUa LHF36400 c MHF36600 c MHF36800 c 1 (order lugs separately) 2 (order lugs separately) 2 (order lugs separately) 3 (order lugs separately) 3 (order lugs separately) (1) 6 300 (1) 6 300 (1) 6 300 (1) 6 300 (1) 6 300

EZM31000CBUa MHF321000 c EZM31200CBUa MHF321200 c

Handle extension available, order kit, AHEXLI, handle is hinged allowing it to be tucked under door on cover. Meets Electrical Utility Service Equipment Requirements Committee (EUSERC) Standards for West Coast based utilities.

Grounding Provisions Service Grounding


EZM1800CBU

Each main device is equipped with a service ground lug, and provisions to bond the neutral to the enclosure when required. EZM main devices are suitable for use as service equipment.

Ground Lug and Isolated Main Neutral Bus as Installed at Factory on Main Devices

Service Ground Lug, Bonding Strap and Bonded Main Neutral Bus as Installed on Main Devices at Job Site as Required for Use as Service Equipment EZM1800CBU

61
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Fusible Switch Main Devices (Fed from Overhead or Underground Service)
Line Neutral Terminal Wire Range (AWGkcmil, Al/Cu) Service Ground Terminal Wire Range (AWGkcmil, Al/Cu)

Service Type

Ampere Rating

Catalog Numberk

Molded Case Switch (Supplied Factory Installed)

Line Phase Terminal Wire Range (AWG-kcmil, Al/Cu)

1f IN Fusible Switch Main Devices (Fed from Overhead or Underground Service) 400 1f3W, 120/ 240 Vac 600 800 1200 EZM1400FS EZM1600FS EZM1800FS EZM11200FS LHP26000M c MHP260006M c MHP260008M c PHF260000M (1) 1/0 600 or (2) 1/0 250 f (3) 3/0 500 f (3) 3/0 500 f (4) 1/0 750 (1) 1/0 600 or (2) 1/0 250 q (4) 3/0 500 p (4) 3/0 500 p (4) 1/0 750 p (1) 6 300 (1) 6 300 (1) 6 300 (1) 6 300

3f IN Fusible Switch Main Devices(Fed from Overhead or Underground Service) 3f4W, 208Y/120 Vac or 240/ 120 Vac Delta 400 600 800 EZM3400FS EZM3600FS EZM3800FS LHP36000M c MHP360006M c MHP360008M c (1) 1/0 600 or (2) 1/0 250 f (3) 3/0 500 f (3) 3/0 500 f (1) 1/0 600 or (2) 1/0 250 q (4) 3/0 500 p (4) 3/0 500 p (1) 6 300 (1) 6 300 (1) 6 300

Fusible Switch Main Devices (Fed from Underground Service only)


EZM3800FS Molded Case Switch (Supplied Factory Installed) Line Phase and Neutral Lug Landing Pads provided for use with Crimp-Type Lugs (2-Hole Mounting) Quantity of Lugs permitted per Pad Service Ground Terminal Wire Range (AWGkcmil, Al/Cu)

Service Type

Ampere Rating

Catalog Numberk

1f IN Fusible Switch Main Devices (Fed from Underground Service only) 400 1f3W, 120/240 Vac 600 800 1200 EZM1400FSUa EZM1600FSUa EZM1800FSUa EZM11200FSUa LHF26000M c MHF260006M c MHF260008M c PHF260000M 1 (order lugs separately) 2 (order lugs separately) 2 (order lugs separately) 3 (order lugs separately) (2) 6 300 (2) 6 300 (2) 6 300 (2) 6 300

3f IN Fusible Switch Main Devices (Fed from Underground Service only) 3f4W, 208Y/120 Vac or 240/ 120 Vac Delta c f q p a k 400 600 800 EZM3400FSUa EZM3600FSUa EZM3800FSUa LHF36000M c MHF360006M c MHF360008M c 1 (order lugs separately) 2 (order lugs separately) 2 (order lugs separately) (2) 6 300 (2) 6 300 (2) 6 300

Handle extension available, order kit AHEXLI, handle is hinged allowing it to be tucked under door on cover. Alternate lugs kits are available for use on line side of molded case switch (refer to Digest). Alternate neutral lug available, order one (1) kit, MMLK500 for (2) 3/0 AWG 500 kcmil Al/Cu (kit includes three, 2-barrel lugs), Neutral will accommodate one, 2-barrel lug only. Alternate neutral lugs available, order one (1) kit, MMLK250 for (1) 1/0 AWG 600 kcmil or (2) 1/0 AWG 250 kcmil Al/Cu (kit includes three, 2-barrel lugs), Neutral will accommodate two, 2-barrel lugs only. Meets Electrical Utility Service Equipment Requirements Committee (EUSERC) Standards for West coast based utilities. Fuses not included. Order 300 V Class T fuses.

EZM3800FS

62
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
Main Lugs Terminal Boxes (Fed from Overhead or Underground Service)
Line Phase and Neutral Terminal Wire Range (AWGkcmil, Al/Cu) Service Ground Terminal Wire Range (AWGkcmil, Al/Cu)

Service Ampere Type Rating

Catalog Number

Terminal Box can be Fed from Upstream Service Disconnect and Attain a Short Circuit Current Rating Based on Overcurrent Protection Provided as Follows

1f IN Main Lugs Terminal Boxes (Fed from Overhead or Underground Service) Class R Fuse (600 A max.) 100K Class T Fuse 300 Vac (800 A max.) 100K Square D Circuit Breaker Rated 65K 65K Square D Circuit Breaker Rated 42K 42K Square D Circuit Breaker Rated 22K 22K Class R Fuse (600 A max.) 100K Class T Fuse 300 Vac (800 A max.) 100K Square D Circuit Breaker Rated 65K 65K Square D Circuit Breaker Rated 42K 42K Square D Circuit Breaker Rated 22K 22K Class R Fuse (600 A max.) 100K Class T Fuse 300 Vac (800 A max.) 100K Square D Circuit Breaker Rated 65K 65K Square D Circuit Breaker Rated 42K 42K Square D Circuit Breaker Rated 22K 22K

400

EZM1400TB

(2) 3/0 500q

(1) 6 300

1f3W, 120/ 240 Vac

800

EZM1800TB

(4) 3/0 500p

(1) 6 300

1600

EZM11600TB

(6) 2 600

(1) 6 300

3f IN Main Lugs Terminal Boxes (Fed from Overhead or Underground Service)

EZM1800TB
400 EZM3400TB (2) 3/0 500c (1) 6 300

Class R Fuse (600 A max.) 100K Class T Fuse 300 Vac (800 A max.) 100K Square D Circuit Breaker Rated 65K 65K Square D Circuit Breaker Rated 42K 42K Square D Circuit Breaker Rated 22K 22K Class R Fuse (600 A max.) 100K Class T Fuse 300 Vac (800 A max.) 100K Square D Circuit Breaker Rated 65K 65K Square D Circuit Breaker Rated 42K 42K Square D Circuit Breaker Rated 22K 22K Class R Fuse (600 A max.) 100K Class T Fuse 300 Vac (800 A max.) 100K Square D Circuit Breaker Rated 65K 65K Square D Circuit Breaker Rated 42K 42K Square D Circuit Breaker Rated 22K 22K

3f4W, 208Y/ 120 Vac or 240/ 120 Vac Delta

800

EZM3800TB

(4) 3/0 500k

(1) 6 300

1600

EZM31600TB

(6) 2 600

(1) 6 300

q p c k

Alternate lug kit available, order one (1) kit, MMLK250 kits for (1) 1/0 AWG 600 kcmil or (2) 1/0 AWG 250 kcmil Al/Cu (kit includes three 2-barrel lugs), each bus bar will accept one 2-barrel lug. Alternate lug kit available, order two (2) MMLK250 kits for (2) 1/0 AWG 600 kcmil or (4) 1/0 AWG 250 kcmil Al/Cu (each kit includes three 2-barrel lugs), each bus bar will accept two 2-barrel lugs. Alternate lug kit available, order two (2) MMLK250 kits for (1) 1/0 AWG 600 kcmil or (2) 1/0 AWG 250 kcmil Al/Cu (each kit includes three 2-barrel lugs), each bus bar will accept one 2-barrel lug. Alternate lug kit available, order three (3) MMLK250 kits for (2) 1/0 AWG 600 kcmil or (4) 1/0 AWG 250 kcmil Al/Cu (each kit includes three 2-barrel lugs), each bus bar will accept two 2-barrel lugs.

EZM1800TB

63
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Application Data
EZM Main Device Standard and Alternate Lugs
Standard Lugs (Supplied Factory Installed) Alternate Lugs by Manufacturer, Catalog Number, Wire Range AWG-kcmil, Crimping Tool, and Quantity Per Line Side Phase and Neutral (Order Lugs Separately) ANDERSON ILSCO CMC VACL-1000-12BN VHCL-600-12BN VHCL-750-12BN A1B2-600-2 TA-600-2Nl AU-600-2N (2-Barrel) 2ACL-600 2AB2-600 (2-Barrel)
... ... ... ... 2 3 ... ... ... ... 2 3 1 1 1 2 2 1 1 1 2 2 ... ... ... 2 ... ... ... 1 1 1 2 1 1 1 ... ... 3 ... ... 3

Catalog Number

Line Side Phase Terminals

Line Side Neutral Terminals

250-600 500-750 500-750 2-600 250-600 2-600 (2) 2-600 2-600 (2) 2-600 Cu Cu Cu Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu VC-6 VC-7 VC-8 Mechanical IDT-12 Mechanical Mechanical Mechanical Mechanical
EZM1400CB fj EZM1600CB ft EZM1800CB ft EZM11200CB a EZM11600CB a EZM3400CB fj EZM3600CB ft EZM3800CB ft EZM31200CB a EZM31600CB a EZM1400CBU EZM1600CBU EZM1800CBU EZM11000CBU EZM11200CBU EZM3400CBU EZM3600CBU EZM3800CBU EZM31000CBU EZM31200CBU EZM1400FS fj EZM1600FS ft EZM1800FS ft EZM11200FS a EZM3400FS fj EZM3600FS ft EZM3800FS ft EZM1400FSU EZM1600FSU EZM1800FSU EZM11200FSU EZM3400FSU EZM3600FSU EZM3800FSU EZM1400TB q EZM1800TB p EZM11600TB EZM3400TB c EZM3800TB k EZM31600TB f j t a l q p c k (1)AL400LA (1) AL900MA (1) AL900MA (4) AL2500PA (6) AL2500PA (1) AL400LA (1) AL900MA (1) AL900MA (4) AL2500PA (6) AL2500PA Studs 1 lug Studs 2 lugs Studs 2 lugs Studs 3 lugs Studs 3 lugs Studs 1 lug Studs 2 lugs Studs 2 lugs Studs only Studs 3 lugs (1) AL400LA (1) AL900MA (1) AL900MA (4) AL2500PA (1) AL400LA (1) AL900MA (1) AL900MA Studs 1 lug Studs 2 lugs Studs 2 lugs Studs 3 lugs Studs 1 lug Studs 2 lugs Studs 2 lugs MMLK500 (one lug) MMLK500 (two lug) (6) AL2500PA MMLK500 (one lug) MMLK500 (two lug) (6) AL2500PA MMLK250 (one lug) MMLK500 (two lugs) MMLK500 (two lugs) MMLK500 (two lugs) (4) AL2500PA (6) AL2500PA MMLK250 (one lug) MMLK500 (two lugs) MMLK500 (two lugs) MMLK500 (two lugs) (4) AL2500PA (6) AL2500PA Studs 1 lug Studs 2 lugs Studs 2 lugs Studs 3 lugs Studs 3 lugs Studs 1 lug Studs 2 lugs Studs 2 lugs Studs only Studs 3 lugs MMLK250 (one lug) MMLK500 (two lugs) MMLK500 (two lugs) (4) AL2500PA MMLK250 (one lug) MMLK500 (two lugs) MMLK500 (two lugs) Studs 1 lug Studs 2 lugs Studs 2 lugs Studs 3 lugs Studs 1 lug Studs 2 lugs Studs 2 lugs MMLK500 (one lug) MMLK500 (two lug) (6) AL2500PA MMLK500 (one lug) MMLK500 (two lug) (6) AL2500PA ... ... ... ... 4 6 ... ... ... ... 4 6 1 2 2 3 3 1 2 2 3 3 ... ... ... 4 ... ... ... 1 2 2 3 1 2 2 ... ... 6 ... ... 6 ... ... ... ... 4 6 ... ... ... ... 4 6 1 2 2 3 3 1 2 2 3 3 ... ... ... 4 ... ... ... 1 2 2 3 1 2 2 ... ... 6 ... ... 6 ... ... ... 1 ... ... ... 1 ... ... ... ... 6 ... ... 6 ... ... ... ... ... ... ... ... ... ... ... ... 1 ... ... ... ... 1 ... ... ... ... ... ... ... ... ... ... ... 4 6 ... ... ... ... 4 6 1 2 2 3 3 1 2 2 3 3 ... ... ... 4 ... ... ... 1 2 2 3 1 2 2 ... ... 6 ... ... 6 ... ... ... ... 4 6 ... ... ... ... 4 6 1 2 2 3 3 1 2 2 3 3 ... ... ... ... ... ... ... 1 2 2 3 1 2 2 ... ... 6 ... ... 6 ... ... ... ... 4 6 ... ... ... ... 4 6 1 2 2 3 3 1 2 2 3 3 ... ... ... 4 ... ... ... 1 2 2 3 1 2 2 ... ... 6 ... ... 6 ... ... ... ... 2 3 ... ... ... ... 2 3 1 1 1 2 2 1 1 1 2 2 ... ... ... 2 ... ... ... 1 1 1 2 1 1 1 ... ... 3 ... ... 3 ... ... ... ... 4 6 ... ... ... ... 4 6 1 2 2 3 3 1 2 2 3 3 ... ... ... 4 ... ... ... 1 2 2 3 1 2 2 ... ... 6 ... ... 6

EZM11000CB ft (1) AL900MA

EZM31000CB ft (1) AL900MA

Alternate lugs kits are available for use on line side terminals of molded case circuit breaker, or molded case switch (refer to Digest). Alternate neutral lug available, order one (1) kit, MMLK500 for (2) 3/0 AWG 500 kcmil Al/Cu (kit includes three 2-barrel lugs), neutral will accommodate one 2-barrel lug only. Alternate neutral lugs available, order one (1) kit, MMLK250 for (1) 1/0 AWG 600 kcmil or (2) 1/0 AWG 250 kcmil Al/Cu (kit includes three 2-barrel lugs), neutral will accommodate two 2-barrel lugs only. Lugs are supplied factory installed on the lug landing pads of this device, but alternate lugs are available. This lug is available from Square D Company, order catalog number CMELK4, kit includes 4 lugs. Alternate lug kit available, order one (1) kit, MMLK250 kits for (1) 1/0 AWG 600 kcmil or (2) 1/0 AWG 250 kcmil Al/Cu (kit includes three 2-barrel lugs), each bus bar will accept one 2-barrel lug. Alternate lug kit available, order two (2) MMLK250 kits for (2) 1/0 AWG 600 kcmil or (4) 1/0 AWG 250 kcmil Al/Cu (each kit includes three 2-barrel lugs), each bus bar will accept two 2-barrel lugs. Alternate lug kit available, order two (2) MMLK250 kits for (1) 1/0 AWG 600 kcmil or (2) 1/0 AWG 250 kcmil Al/Cu (each kit includes three 2-barrel lugs), each bus bar will accept one 2-barrel lug. Alternate lug kit available, order three (3) MMLK250 kits for (2) 1/0 AWG 600 kcmil or (4) 1/0 AWG 250 kcmil Al/Cu (each kit includes three 2-barrel lugs), each bus bar will accept two 2-barrel lugs.

64
1999 Square D All Rights Reserved 5/99

LID2-600

EZ METER-PAK Meter Centers Class 4161


Single Phase Catalog Number Logic
EZM Mains Devices
EZM 1 1000 CB U FEED DIRECTION
Blank = Overhead/Underground U = Underground Only, Meets EUSERC Standards

MAIN TYPE
CB = Main Circuit Breaker FS = Main Fusible Switch TB = Terminal Box

MAINS RATING
400, 600, 800, 1000, 1200, 1600 A

SERVICE FEED
1 = 1f3W

DEVICE NAME
EZ METER-PAK

EZM Branch Units


EZM R 1 1 3 125 MAXIMUM TENANT CIRCUIT BREAKER AMPERAGE
125, 200 A

NUMBER OF METER SOCKETS


Meter Sockets Available 1, 2, 3, 4, 5, 6

LOAD FEED
1 = 1f3W

SERVICE FEED
1 = 1f3W

SOCKET/BYPASS TYPE
Blank = Ring Type R = Ringless with 5th Jaw H = Ringless with Horn Bypass and 5th Jaw L = Lever Bypass with 5th Jaw T = Ring Type Test-Block Bypass EUSERC

DEVICE NAME
EZ METER-PAK

65
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161


Single Phase Product Selection
Select EZM meter center short circuit current rating RMS symmetrical amperes from table on pages 4 and 5. Using this table as a reference, make the following selections:

STEP 1: CHOOSE A MAINS DEVICE

Main Circuit Breaker 65,000 AIR Ampere Rating


400 600 800 1000 1200 1600

Main Fusible Switch 100,000 AIR Catalog Number Standard OH/UG


EZM1400FS EZM1600FS EZM1800FS EZM11200FS

Main Lugs Terminal Box Catalog Number Standard OH/UG


EZM1400TB EZM1800TB EZM11600TB

Catalog Number Standard OH/UG


EZM1400CB EZM1600CB EZM1800CB EZM11000CB EZM11200CB EZM11600CB

EUSERCc
EZM1400CBU EZM1600CBU EZM1800CBU EZM11000CBUf EZM11200CBUf

EUSERCc
EZM1400FSU EZM1600FSU EZM1800FSU EZM11200FSU

STEP 2: CHOOSE BRANCH DEVICES

Branch Device Catalog Numbers Ampere Rating Number of Meter Sockets


3 125 A Branch 4 5 6 1 200 A Branch 2 3 4

Residential (Use QO or Q2M p Circuit Breakers) Ring-Type (4-Jaw Socket)


EZM113125 EZM114125 EZM115125 EZM116125 EZM112200 EZM113200 EZM114200

Commercial (Use QE2 Circuit Breakers) Ringless-Type Lever Bypass


EZML111200 EZML112200 EZML113200 EZML114200

Ringless-Type with 5th Jaw


EZMR113125 EZMR114125 EZMR115125 EZMR116125 EZMR112200 EZMR113200 EZMR114200

Ringless-Type Ring-Type with Horn Bypass Test Block Bypass and 5th Jaw EUSERC
EZMH113125 EZMH114125 EZMH115125 EZMH116125 EZMH112200 EZMH113200 EZMH114200 EZMT111200q EZMT112200q EZMT113200q

STEP 3: CHOOSE BRANCH CIRCUIT BREAKERS

Device Type

Ampere Rating
40 50 60 QO240 QO250 QO260 QO270 QO280 QO290 QO2100 QO2125

Circuit Breaker Catalog Numbers


QO240VH QO250VH QO260VH QO270VH QO280VH QO290VH QO2100VH QO2125VH QOH240 QOH250 QOH260 QOH270 QOH280 QOH290 QOH2100 QOH2125

125 A Branch

70 80 90 100 125

Device Type

Ampere Rating
70 80 90

Circuit Breaker Catalog Numbers Residential


For 40125 A use QO, QO-VH, or QOH Circuit Breakers listed above with EZM125QOA Adapter Kit (1 kit per Circuit Breaker required) Q2M2100 Q2M2125 Q2M2150 Q2M2175 Q2M2200 Q2M2100VH Q2M2125VH Q2M2150VH Q2M2175VH Q2M2200VH Q2MH100VH Q2MH125VH Q2MH150VH Q2MH175VH Q2MH200VH

Commercial
QE270VH QE280VH QE290VH QE2100VH QE2125VH QE2150VH QE2175VH QE2200VH

200 A Branch (only)

100 125 150 175 200

c f q p

Underground Feed Only. EUSERC (Electrical Utility Service Equipment Requirements Committee). 100,000 RMS symmetrical amperes Consult factory for availability. Q2M circuit breakers for use in 200 A residential branch devices only.

66
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161


Single Phase Product Selection
STEP 4: CHOOSE ACCESSORIES AND/OR REPLACEMENT PARTS
1f AccessoriesDescription
Fifth Jaw Kit (one per kit) Horn Bypass Kit (use on EZMR11 prex devices only) Manual Bypass-Slider Sealing Rings: Snap-Type Aluminum Screw-Type Aluminum Snap-Type Stainless Steel Latch-Type Stainless Steel Meter Socket Closing PlateLEXAN (Residential use only) Meter Socket Closing PlateMetal (Ringless-Type use only) Secondary Surge Arrestor Mounting Kit for Main Devicesuse with SDSA1175 Bussed Extension, 1200 A (NEMA Type 3R) Inside Corner Elbow, 1200 A (NEMA Type 1) QO Adapter for Bolt-on Q2M (QO 40125 A) Transition Section, 1200 A (add right) Transition Section, 1200 A (add left) Al/Cu Lugs (1) 4-250 per lug (1) 1/0-600 or (2) 1/0-250 per lug (2) 3/0-500 per lug (2) 2-600 per lug Busway Transition Section, 1200 A (right) Busway Transition Section, 1200 A (left) q Consult factory for availability. Order Only. Not stocked in PDS. For use with ring-type only. Limits AIR rating to 10K for entire lineup.

Catalog Number
5J MMHB MM200MBf 29209-100-01 29008W 29209-100-02 29008G 29007 RSG-4 MM1SAKq EZM1EXT EZM1CORNER EZM125QOA EZM1TRAN-R q EZM1TRAN-Laq MMLK300 MMLK250 MMLK500 MMLK600 EZM1BUS-Rq EZM1BUS-Lq

a
f

1f Replacement PartsRefer to page 95 for details


End Closing Plate Left/Right Replacement Socket/Jaw/Bus/Circuit Breaker Base Assemblies (order horn bypass kits separately, as needed) 125 A Standard Socket, 5th Jaw 200 A Standard Socket, 5th Jaw 200 A Lever Bypass Socket 100 A EUSERC Safety Socket 200 A EUSERC Safety Socket Replacement Socket Covers Ring Cover, 125 A/200 A Ring Cover, 200 A Commercial Ringless Cover, 125 A/200 A Residential Ringless Cover, 200 A Commercial

Catalog Number
EZMCAP MM125KIT MM200KIT EZML1200KIT EZMT1100KIT EZMT1200KIT MMC EZMCC MMRC EZMCRC

67
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4162


Three Phase Catalog Number Logic
EZM Mains
EZM 3 1000 CB U FEED DIRECTION
Blank = Overhead/Underground U = Underground Only, Meets EUSERC Standards

MAIN TYPE
CB = Main Circuit Breaker FS = Main Fusible Switch TB = Terminal Box

MAINS RATING
400, 600, 800, 1000, 1200, 1600 A

SERVICE FEED
3 = 3f4W

DEVICE NAME
EZ METER-PAK

EZM Branches
EZM R 3 1 3 125 MAXIMUM TENANT CIRCUIT BREAKER AMPERAGE
125, 200, 400 A

NUMBER OF METER SOCKETS


Meter Sockets Available 1, 2, 3, 4, 5, 6

LOAD FEED
1 = 1f3W 3 = 3f4W

SERVICE FEED
3 = 3f4W

SOCKET/BYPASS TYPE
Blank = Ring Type R = Ringless H = Ringless with Horn Bypass L = Lever Bypass T = Test-Block Bypass EUSERC K = K-Base Bolt-on Type

DEVICE NAME
EZ METER-PAK

68
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4162


Three Phase Product Selection
Select EZM meter center short circuit current rating RMS symmetrical amperes from table on pages 4 and 5. Using this table as a reference, make the following selections:

STEP 1: CHOOSE A MAINS DEVICE

Main Circuit Breaker 65,000 AIR Ampere Rating


400 600 800 1000 1200 1600

Main Fusible Switch 100,000 AIR Catalog Number Standard OH/UC


EZM3400FS EZM3600FS EZM3800FS

Main Lugs Terminal Box Catalog Number Standard OH/UC


EZM3400TB ... EZM3800TB ... ... EZM31600TB

Catalog Number Standard OH/UC


EZM3400CB EZM3600CB EZM3800CB EZM31000CB EZM31200CB EZM31600CB

EUSERC c
EZM3400CBU EZM3600CBU EZM3800CBU EZM31000CBU f EZM31200CBU f

EUSERC c
EZM3400FSU EZM3600FSU EZM3800FSU

STEP 2: CHOOSE BRANCH DEVICES

Branch Device Catalog Numbers (5-Jaw Socket Standard) EZM 3f In 1f Out Number of Meter Sockets
3 125 A Branch 4 5 6 1 200 A Branch 2 3 4 400 A Branch 1 2

Residential (Use QO or Q2Mk Circuit Breakers) Ring-Type


EZM313125 EZM314125 EZM315125 EZM316125 EZM312200 EZM313200 EZM314200

Commercial (Use QE2 Circuit Breakers) Ring-Type Test Block Bypass EUSERC
EZMT311200q EZMT312200q EZMT313200q

Ringless-Type No Bypass
EZMR313125 EZMR314125 EZMR315125 EZMR316125 EZMR312200 EZMR313200 EZMR314200

Ringless-Type Horn Bypass


EZMH313125 EZMH314125 EZMH315125 EZMH316125 EZMH312200 EZMH313200 EZMH314200

Ringless-Type Lever Bypass


EZML312200 EZML313200 EZML314200 EZML311400h EZML312400h

EZM 3f In 3f Out

Number of Meter Sockets


1

Branch Device Catalog Numbers, Commercial (Use QE3 Circuit Breakers) 7-Jaw Socket Standard Ring-Type Test Block Bypass EUSERC
EZMT331200 q EZMT332200 q EZMT333200 q

Ringless-Type No Bypass
EZMR332200 EZMR333200 EZMR334200

Ringless-Type K-Base Meter Socket


EZMK331400q EZMK332400q

Ringless-Type Lever Bypass


EZML331200 EZML332200 EZML333200 EZML334200 EZML331400 h EZML332400 h

200 A Branch

2 3 4

400 A Branch c f q k h

1 2

Underground Feed Only. EUSERC (Electrical Utility Service Equipment Requirements Committee). 100,000 AIR Consult factory for availability. Q2M circuit breakers for use in 200 A residential branch devices only. Supplied with Class 320 meter socket. 400 A LAL circuit breaker supplied factory installed. Device has limited short circuit capabilities, see pages 4 and 5 for details.

69
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4162


Three Phase Product Selection
STEP 3: CHOOSE BRANCH CIRCUIT BREAKERS
Residential Device Type Ampere Rating
40 50 60 70 125 A Branch 80 90 100 110 125 QO240 QO250 QO260 QO270 QO280 QO290 QO2100 QO2110 QO2125

Circuit Breaker Catalog Numbers 2-Pole 120/240 Vac


QO240VH QO250VH QO260VH QO270VH QO280VH QO290VH QO2100VH QO2110VH QO2125VH QOH240 QOH250 QOH260 QOH270 QOH280 QOH290 QOH2100 QOH2110 QOH2125

For 40125 A use QO, QO-VH, or QOH Circuit Breakers listed above with EZM125QOA Transition Kit (one kit per Circuit Breaker required) 100 200 A Branch (only) 125 150 175 200 Q2M2100 Q2M2125 Q2M2150 Q2M2175 Q2M2200 Q2M2100VH Q2M2125VH Q2M2150VH Q2M2175VH Q2M2200VH Q2MH2100 Q2MH2125 Q2MH2150 Q2MH2175 Q2MH2200

Commercial Device Type

Ampere Rating
70 80 90 100 125 150 175 200

Circuit Breaker Catalog Numbers 2-Pole 120/240 Vac


QE270VH QE280VH QE290VH QE2100VH QE2125VH QE2150VH QE2175VH QE2200VH

3-Pole 240 Vac


QE370VH QE380VH QE390VH QE3100VH QE3125VH QE3150VH QE3175VH QE3200VH

200 A Branch

70
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4162


Three Phase Product Selection
STEP 4: CHOOSE ACCESSORIES AND/OR REPLACEMENT PARTS
3f AccessoriesDescription
Fifth Jaw Kit (one per kit) Horn Bypass Kit (use on EZMR31 only) Manual Bypass-Slider, 1-Phase Socket Sealing Rings: Snap-Type Aluminum Screw-Type Aluminum Snap-Type Stainless Steel Latch-Type Stainless Steel Meter Socket Closing PlateLEXAN (Residential use only) Meter Socket Closing PlateMetal (Ringless-Type use only) Secondary Surge Arrestor Mounting Kit for Main Devicesuse with SDSA3650 Bussed Extension, 1200 A (NEMA Type 3R) Inside Corner Elbow, 1200 A (NEMA Type 1) QO Adapter for Bolt-on Q2M (QO 40125 A) Transition Section, 1200 A (add right) Transition Section, 1200 A (add left) Al/Cu Lugs (1) 1/0-600 or (2) 1/0-250 per lug (2) 3/0-500 per lug (2) 2-600 per lug Busway Transition Section, 1200 A (right) Busway Transition Section, 1200 A (left) q

Catalog Number
5J MMHB MM200MBk 29209-100-01 29008W 29209-100-02 29008G 29007 RSG-4 MM3SAKq EZM3EXT EZM3CORNER EZM125QOA EZM3TRAN-Rq EZM3TRAN-Laq MMLK250 MMLK500 MMLK600 EZM3BUS-Rq EZM3BUS-Lq

a
k

Consult factory for availability. Order Only. Not stocked in PDS. For use with ring-type only. Limits AIR rating to 10K for entire lineup.

3f Replacement PartsRefer to page 95 for Details


End Closing Plate Left/Right Replacement Socket/Jaw/Bus/Breaker Base Assemblies (order Horn Bypass Kits separately, as needed) 125 A Standard Socket, 5th Jaw 200 A Standard Socket, 5th Jaw 200 A 1-Phase Lever Bypass Socket 200 A 3-Phase Socket, No Bypass 200 A 3-Phase Lever Bypass Socket 400 A 1-Phase Lever Bypass Socket 400 A 3-Phase Lever Bypass Socket Replacement Socket Covers Ring Cover 125 A/200 A Residential Ring Cover 200 A Commercial Ringless Cover 125 A/200 A Residential Ringless Cover 200 A/400 A Commercial

Catalog Number
EZMCAP MM125KIT MM200KIT EZML1200KIT EZM3200KIT EZML3200KIT EZML1400KIT EZML3400KIT MMC EZMCC MMRC EZMCRC

71
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Dimensions and Knockouts
18.66
474 368

14.50

11.50
292 Box Side

Nut Torque to 50 lb-in

Omitted on 1f Units

Captive Screw Hanging Mounting Rail Hex Nut Gasket

Equipment Ground Path 2.00


51 Captive Screw Box Side Left

3.44
87 Omitted on 1f Units

2.00
51 Hex Nut

53.97
1371 Line Phase Lugs

Sealing Wing Nut

Box Side Right

Sealing Wing Nut Closing Cap

34.30
871

Closing Cap

24.75
629 Gasket

Square Neck Bolt

Gasket

Left Side Closing Cap

Right Side Closing Cap

14.50
368

9.13 5.09
129 232

11.06
281

18.48
469 E,F,G,H,I,J

30.19
767

24.00
610 A,B

18.33
465

3.00
76

11.06
281 Omitted on 1f Units Hanging Mounting Rail

1.12
28

2.92
74

5.61 5.61
142 142

.91
23

3.44
87 Omitted on 1f Units

EZM1400CB, EZM3400CB EZM1600CB, EZM3600CB EZM1800CB, EZM3800CB EZM11000CB, EZM31000CB

61.19
1554

38.13
968

21.91 19.38
492 556

24.00
610

17.83
453

Symbol
A B C D E F G H I J

Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

30.00
762

Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

E,F,G,H,I,J

3.07
78

A,B

17.83
453

1.16
29

4.81
122

6.75 6.75 6.75


171 171 171

.92
23

EZM11200CB, EZM31200CB EZM11600CB, EZM31600CB

72
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Dimensions and Knockouts
18.66
474

14.50
368

11.50
292

Box Side

Nut Torque to 50 lb-in

17.72
450 Omitted on 1f Units Hanging Mounting Rail

Captive Screw Gasket

Equipment Ground Path


Hex Nut

3.44
87 Omitted on 1f Units

2.00
51 Captive Screw Box Side Left

2.00
51 Hex Nut

53.97
1371

Sealing Wing Nut

Box Side Right

Sealing Wing Nut Closing Cap

34.30
871 Line Phase Lugs

Closing Cap

Square Neck Bolt

16.50
419

Gasket

Gasket

Left Side Closing Cap

Right Side Closing Cap

14.50
368

11.06 5.09
129 281

18.48
469 E,F,G,H,I,J

30.19
767

24.00
610 A,B

18.33
465

3.00
76

11.06
281

1.12
28

3.44
87 Hanging Mounting Rail

2.92
74

5.61 5.61
142 142

.91
23

EZM1400FS, EZM3400FS EZM1600FS, EZM3600FS EZM1800FS, EZM3800FS

61.19
1554

38.13
968

21.91 19.38
492 556

24.00
610

17.83
453

Symbol
A B C D E F G H I J

Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

30.00
Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118 E,F,G,H,I,J 762

3.07
78

17.83
A,B 453

1.16
29

4.81
122

6.75 6.75 6.75


171 171 171

.92
23

EZM11200FS

73
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Dimensions and Knockouts
18.66
474

14.50
368

11.50
292 Box Side

Nut Torque to 50 lb-in

16.12
409 Captive Screw Hanging Mounting Rail Hex Nut Gasket

Equipment Ground Path 2.00


51 Captive Screw Box Side Left

3.44
87 Omitted on 1f Units

2.00
51 Hex Nut

53.97
1371 Sealing Wing Nut

Box Side Right

Sealing Wing Nut Closing Cap

34.30
871

Closing Cap

26.59
675 Gasket

Square Neck Bolt

Gasket

Left Side Closing Cap

Right Side Closing Cap

14.50
368

9.13
232

30.19
767

18.48
469 E,F,G,H,I,J

11.06
281 A,B

24.00
610

18.31
465

3.00
76

11.06
281

18.24
463

1.12
28

2.92
74

5.61 5.61
142 142

.91
23

3.44
87 Omitted on 1f Units

Hanging Mounting Rail

EZM1400TB, EZM3400TB EZM1800TB, EZM3800TB

61.19
1554

38.12
968

26.39
670

24.00
610

14.79
376

Symbol
A B C D E F G H I J

Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

30.00
762

17.83
453

Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

E,F,G,H,I,J

3.07
78

17.83
A,B 453

1.16
29

4.81
122

6.75 6.75 6.75


171 171 171

.92
23

EZM11600TB EZM31600TB

74
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Dimensions and Knockouts
20.46
520

Box Side

16.30
414

11.50
292

Nut Torque to 50 lb-in

Captive Screw Gasket Omitted on 1f Units

Equipment Ground Path


Hanging Mounting Rail Hex Nut

2.00
51 Captive Screw Box Side Left

2.00
51 Hex Nut

3.44
87 Omitted on 1f Units

Sealing Wing Nut

Box Side Right

Sealing Wing Nut Closing Cap

69.03
1753

Closing Cap

Square Neck Bolt

Gasket

Gasket

4.00
102

49.37
1254

Left Side Closing Cap

Right Side Closing Cap

20.46
520 414

30.25
768

16.30

11.50
292

3.44
87

16.30
414

11.06
281

Hanging Mounting Rail

20.28
515 E,F,G,H,I,J

3.03
77

A,B

11.06
281

69.03
1753

1.12
28

4.00
102

4.34
110

5.80 5.80
147 147

.91
23

49.37
1254

EZM1400CBU EZM3400CBU

31.16
791

16.30
414

11.06
281

Symbol
A B C D E F G H I J

Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

20.28
515 E,F,G,H,I,J

3.03
77

A,B

11.06
281

1.12
28

4.34
110

5.80 5.80
147 147

.91
23

EZM1600CBU EZM1800CBU

75
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Dimensions and Knockouts
26.19
665 508

Box Side

20.00

11.65
296

Nut Torque to 50 lb-in

Captive Screw Gasket

Equipment Ground Path


Hanging Mounting Rail Hex Nut

2.00
51 Captive Screw Box Side Left

2.00
51 Hex Nut

3.44
87

Sealing Wing Nut

Box Side Right

Sealing Wing Nut Closing Cap

69.03
1753

Closing Cap

Square Neck Bolt

4.00
102

Gasket

Gasket

49.37
1254

Left Side Closing Cap

Right Side Closing Cap

34.19
868

24.00 31.16
791 610

18.33
466

Omitted on 1f Units

20.00
508 660

11.10
282

26.00

3.44
87 Omitted on 1f Units

Hanging Mounting Rail

E,F,G,H,I,J

3.04
77

A,B

11.10
282

70.05
1779

1.13
29

4.75
121

8.25
209

8.25
209

.92
23

46.99 4.28
109 1193

EZM3600CBU EZM3800CBU

26.08
662

24.00
610

17.83
453

34.00
Symbol
A B C D E F G H I J

Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

864

Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

E,F,G,H,I,J

3.06
78

A,B

17.83
453

1.16
29

5.37
136

7.75
197

7.75
197

7.75
197

.92
23

EZM11000CBU, EZM31000CBU EZM11200CBU, EZM31200CBU

76
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Dimensions and Knockouts

20.46
520 414

Box Side

16.30

11.50
292

Nut Torque to 50 lb-in

Captive Screw Gasket Omitted on 1f Units

Equipment Ground Path


Hanging Mounting Rail Hex Nut

2.00
51 Captive Screw Box Side Left

2.00
51 Hex Nut

3.44
87 Omitted on 1f Units

Sealing Wing Nut

Box Side Right

Sealing Wing Nut Closing Cap

Closing Cap

Square Neck Bolt

69.03
1753 Gasket Gasket

49.37
1254

Left Side Closing Cap

Right Side Closing Cap

20.46 5.00
127 520 414

16.30

11.50
292

22.00
559

3.44
87

16.30
414

11.06
281

Hanging Mounting Rail

20.28
515 E,F,G,H,I,J

3.03
77

A,B

11.06
281

69.03 1.12
28 1753

4.34
110

5.80 5.80
147 147

.91
23

49.37 4.75
121 1254

EZM1400FSU EZM3400FSU

26.06
662

16.30
Symbol
A B C D E F G H I J

Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

414

11.06
281

Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

20.28
515 E,F,G,H,I,J

3.03
77

A,B

11.06
281

1.12
28

4.34
110

5.80 5.80
147 147

.91
23

EZM1600FSU EZM1800FSU

77
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Dimensions and Knockouts
26.19
665

Box Side

20.00
508

11.65
296

Nut Torque to 50 lb-in

Captive Screw Gasket

Equipment Ground Path


Hanging Mounting Rail Hex Nut

2.00
51 Captive Screw Box Side Left

2.00
51 Hex Nut

3.44
87

Sealing Wing Nut

Box Side Right

Sealing Wing Nut Closing Cap

Closing Cap

Square Neck Bolt

69.03
1753 Gasket Gasket

49.37
1254

Left Side Closing Cap

Right Side Closing Cap

4.75
121

34.19
868

24.00 26.06
662 610

18.33
466

20.00
508

11.10
282 E,F,G,H,I,J

3.44
87 Hanging Mounting Rail

26.00
660

3.04
77

A,B

11.10
282

70.05 1.13
29 1779

4.75
121

8.25
209

8.25
209

.92
23

46.99 6.25
159 1193

EZM3600FSU EZM3800FSU

26.08
662

24.00
610

17.83
453

Symbol
A B C D E F G H I J

Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

34.00
Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118 864 E,F,G,H,I,J

3.06
78

A,B

17.83
453

1.16
29

5.37
136

7.75
197

7.75
197

7.75
197

.92
23

EZM11200FSU

78
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Dimensions and Knockouts
12.25
311

2.21
56

3.75
95

7.09
180

40 (Typical)

1.56

87 (Typical)

3.44

Hanging Mounting Rail Omitted on 1f Units

132 (Typical)

5.20

42.37
1076

229 (Typical)

9.00

31.30
795

7.10 180 4.79


122

11.19
284

C,D,E

2.48 63 4.59
117

1.65
42

6.59
167

12.25
311

7.54
192

2.21
56

3.75
95

7.09
180

10.48
266

40 (Typical)

1.56

12.12
308

8.50
216

A,B

5.75 1.78
45

3.00
76

146

2.44
62

87 (Typical)

3.44

Hanging Mounting Rail Omitted on 1f Units

6.59
167

48.12
1222 132 (Typical)

5.20

1.62 41 1.67
42

C,D,E

229 (Typical)

9.00

31.30
795

2.72
69

EZM113125, EZM313125 EZMR113125, EZMR313125 EZMH113125, EZMH313125

7.10 180 4.79


122

11.19
284

C,D,E

2.48 63 4.59
117

1.65
42

6.59
167

7.54
192

10.48
266

12.12
308

8.50
216

A,B

Symbol
A B C D E F G H I J

Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

5.75
Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

1.78
45

3.00
76

146

2.44
62

6.59
167

1.62 41 1.67
42

C,D,E

2.72
69

EZM114125, EZM314125 EZMR114125, EZMR314125 EZMH114125, EZMH314125

79
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Dimensions and Knockouts
12.25
311

2.21
56

3.75
95

7.09
180

40 (Typical)

1.56

87 (Typical)

3.44

57.12
1451 Omitted on 1f Units

Hanging Mounting Rail

12.25
132 (Typical)

5.20

311

2.21
56 229 (Typical)

3.75
95

7.09
180

9.00

31.30
795

40 (Typical)

1.56

7.10 180 4.79


122

11.19
284

C,D,E

2.48 63 4.59
117

1.65
42

6.59
167

87 (Typical)

3.44

Hanging Mounting Rail Omitted on 1 Units

7.54
192

10.48
266

66.12
1679

12.12
305

8.50
216

A,B

5.75 1.78
45

3.00
76

146

2.44
62

132 (Typical)

5.20

40.30
1024 229 (Typical)

9.00

6.59
167

1.62 41 1.67
42

C,D,E

7.10 180 4.79


122

11.19
284

C,D,E

2.72
69

EZM115125, EZM315125 EZMR115125, EZMR315125 EZMH115125, EZMH315125

2.48 63 4.59
117

1.65
42

6.59
167

7.54
192

10.48
266

12.12
308

8.50
216

A,B

Symbol
A B C D E F G H I J

Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

5.75
Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

1.78
45

3.00
76

146

2.44
62

6.59
167

1.62 41 1.67
42

C,D,E

2.72
69

EZM116125, EZM316125 EZMR116125, EZMR316125 EZMH116125, EZMH316125

80
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Dimensions and Knockouts
17.38
441

3.75
95 Top Meter Position Omitted on 2-Position Device Omitted on 1f Units

8.09
205

40 (Typical)

1.56

87 (Typical)

3.44

Hanging Mounting Rail

43.41
1103 229 (Typical)

9.00

32.34
821

2.12
54

12.23 6.00
152 311

17.38
441

8.30 2.25
57 211

2.18
55 C,D,E,F

7.50
190

3.75
95

8.09
205

40 (Typical)

1.56

5.75
146

6.75
171

10.50
267

15.00
381

87 (Typical) Omitted on 1f Units C,D,E,F A,B

3.44

Hanging Mounting Rail

17.25 6.59
167 438

52.00
1321

4.12
105

7.50
190 229 (Typical)

9.00

32.34
821

1.61
41

1.93
49

2.12
54

3.34
85

EZM112200, EZM312200 EZM113200, EZM313200 EZMR112200, EZMR312200 EZMR113200, EZMR313200 EZMH112200, EZMH312200 EZMH113200, EZMH313200

12.23 6.00
152 311

8.30 2.25
57 211

2.18
55 C,D,E,F

7.50
190

5.75
146

6.75
171

10.50
267

15.00
381

Symbol
A B C D E F G H I J

Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

17.25
Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

6.59
167

438

C,D,E,F A,B

4.12
105

7.50
190

1.61
41

1.93
49

3.34
85

EZM114200, EZM314200 EZMR114200, EZMR314200 EZMH114200, EZMH314200

81
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Dimensions and Knockouts
19.44
494

19.44
494

12.09
307 140 Top Meter Position Omitted on Single Position Device Omitted on 1f Units

12.09 5.50 9.44


240 307

5.50
140

9.44
240

(Typical) 152

3.44 6.00 87

Hanging Mounting Rail

14.00
356

39.06
992

25.50 3.20
81 648

87 (Typical)

3.44

Hanging Mounting Rail Omitted on 1f Units

13.33
339

67.06
1703

6.62
168

12.09 2.07
53 307

D,E,F.G

8.83
224

3.97
101

5.86
149

EZML111200, EZML312200 EZML112200, EZML331200 EZMR332200, EZML332200

356 (Typical)

14.00

39.50
1003

3.20
81

9.65
245

13.33
339

13.45
342

6.62
168

17.24
438

D,E,F.G

12.09 2.07
53 307

8.83
224

(See Typical Bottom View)

3.97 19.44
494 101

EZML114200, EZML314200 EZMR334200, EZML334200

5.86
149

12.09
307

5.50
140

9.44
240

9.65
245

13.45
342

17.24
438

87 (Typical)

3.44

Hanging Mounting Rail Omitted on 1f Units

19.31 3.91
99 490 D,E,F,G A,B

53.06
1348

4.60
117

8.83
224

356 (Typical)

14.00

2.00 39.50
1003 51

2.24
57

3.79
96 Typical Bottom View

3.20
81

13.33
339

6.62
168

D,E,F.G

2.07
53

12.09
307

8.83
224

Symbol
A B C D E F G H I J

Knockouts Conduit Size IN mm


.50 .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 13 19 25 32 38 51 64 76 89 102

Hole Diameter IN mm
.88 1.25 1.38 1.75 2.00 2.50 3.00 3.63 4.13 4.63 22 32 35 44 51 64 76 92 105 118

3.97
101

EZML113200, EZML313200 EZMR333200, EZML333200

5.86
149

9.65
245

13.45
342

17.24
438 (SeeTypical Bottom View)

82
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Dimensions
23.21
590

23.21
590

12.09
307

12.09 5.50
140

9.44
240 Hanging Mounting Rail

307

5.50
140

9.44
240

87 (Typical)

3.44

14.58
370

45.55
1157

37.81
960 87 (Typical)

3.44

Hanging Mounting Rail

16.60
422

21.53
547

27.44
697

69.61
1768

10.11
257

37.81
960

EZML311400 EZML331400

16.60
422

21.53
547

10.11
257

EZML312400 EZML332400

14.40
366

8.02
204

14.40
366

1.71
43

1.80
46

11.66
296

6.37
162

7.20
183

Omitted on 1 Units Omitted on 1 Units

19.34
491

19.50
495

1.74
44

1.69 43

11.50
292

5.87
149

EZM1CORNER EZM3CORNER NEMA Type 1 Indoor Only

EZM1EXT EZM3EXT

83
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161


Wiring Diagrams
f Load f N Circuit Breaker f Line f Omitted on 400 A Device Main Bonding Jumper N When Ground Required When Required Load Af Bf Load Cf N Use 300 V Class T Fuses (Order Separately) Molded Case Switch Af Bf Line Cf Omitted on 400 A Device Main Bonding Jumper N When Ground Required When Required

Load

EZM1400CB, EZM1600CB, EZM1800CB, EZM11000CB

EZM3400FS, EZM3600FS, EZM3800FS


Af Bf Load Cf N Circuit Breaker Af Bf Line Cf Omitted on 400 A Device Main Bonding Jumper N When Ground Required When Required f Load f N Use 300 V Class T Fuses (Order Separately) Molded Case Switch f Line f Load f N Circuit Breaker Omitted on 1200 A Device f Line f Omitted on 1200 A Device Main Bonding Jumper When N Required Ground When Required Load f f N Omitted on 400 A Device Main Bonding Jumper When Required f Main Bonding Jumper When Required Load

Load

N Ground When Required

EZM3400CB, EZM3600CB, EZM3800CB, EZM31000CB

EZM11200FS

EZM11200CB, EZM11600CB

Ground When Required

EZM1400TB, EZM1800TB
Af Bf Load Cf N Circuit Breaker Omitted on 1200 A Device Af Bf Line Cf Omitted on 1200 A Device Main Bonding Jumper When N Ground Required When Required

Load

Af Bf Cf N Omitted on 400 A Device Main Bonding Jumper When Required

Af

Bf

Cf

Ground When Required

EZM3400TB, EZM3800TB

EZM31200CB, EZM31600CB
f f Load f N Use 300 V Class T Fuses (Order Separately) Molded Case Switch f Line f Omitted on 400 A Device Main Bonding Jumper N When Ground Required When Required f f N Load f N Main Bonding Jumper When Required

Ground When Required

EZM11600TB

EZM1400FS, EZM1600FS, EZM1800FS

84
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161


Wiring Diagrams
Af Bf Cf N Main Bonding Jumper When Required Circuit Breaker f Load f N Load Neutral Disconnect Link Box Bonding When Required Ground When Required N

Af

Bf

Cf

Service Ground Lugs When Required

Ground When Required

EZM31600TB
f f Load f N Circuit Breaker f f Load Neutral Disconnect Link Box Bonding When Required Ground When Required N Af Bf Load Cf N Circuit Breaker Line f

EZM11000CBU, EZM11200CBU

Service Ground Lugs When Required

Load Neutral Disconnect Link Box Bonding When Required Ground When Required N

Service Ground Lugs When Required

Line

EZM1400CBU
Af Af Bf Load Cf N Circuit Breaker Af Bf Cf Neutral Disconnect Link Box Bonding When Required Ground When Required N Molded Case Switch f f Load f N Circuit Breaker Load Neutral Disconnect Link Box Bonding When Required Ground When Required N Line f Bf Line Cf

EZM31000CBU, EZM31200CBU
Load f Load f N Use 300 V Class T Fuses (Order Separately) Load Neutral Disconnect Link Box Bonding When Required Ground When Required N

Service Ground Lugs When Required

Line

Service Ground Lugs When Required

EZM3400CBU

EZM1400FSU
Service Ground Lugs When Required

Af Bf Load Cf N Use 300 V Class T Fuses (Order Separately) Molded Case Switch Neutral Disconnect Link Box Bonding When Required Af Bf Cf Ground When Required N

Load

Line

EZM1600CBU, EZM1800CBU

Service Ground Lugs When Required

Af Bf Load Cf N Circuit Breaker Neutral Disconnect Link Box Bonding When Required Ground When Required N

Load

Line Service Ground Lugs When Required

EZM3400FSU

Af

Bf Line

Cf

EZM3600CBU, EZM3800CBU

85
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161


Wiring Diagrams
f Load f N Use 300 V Class T Fuses (Order Separately) Molded Case Switch f f Load Neutral Disconnect Link Box Bonding When Required Ground When Required

Service Ground Lugs When Required

f Line f N

f f

Tighten 50 lb-ft (600 lb-in)

N f f

Line

EZM1600FSU, EZM1800FSU

Tenant Circuit Breaker 125 A Max. f f Load Neutral and Service Ground Equipment Grounding

Af Bf Load Cf N Use 300 V Class T Fuses (Order Separately) Molded Case Switch Af Bf Cf Neutral Disconnect Link Box Bonding When Required Ground When Required

EZM113125, EZMR113125, EZMH113125


Service Ground Lugs When Required

B C

N f f A B Line C N

Line

EZM3600FSU, EZM3800FSU

Tighten 50 lb-ft (600 lb-in) A B C

Load

f f N

Load Neutral Disconnect Link Box Bonding When Required f f Ground When Required N f f Service Ground Lugs When Required Tenant Circuit Breaker 125 A Max. f f Neutral and Service Ground Each socket line connector may by moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC and AC top to bottom. Equipment Grounding

Use 300 V Class T Fuses (Order Separately) Molded Case Switch

Line

EZM313125, EZMR313125, EZMH313125

EZM11200FSU

86
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161


Wiring Diagrams
A B C

f f f f

f f f Line f N f f Tighten 50 lb-ft (600 lb-in) A B Line C N Tighten 50 lb-ft (600 lb-in) A B C

f f Tenant Circuit Breaker 125 A Max. f f Neutral and Service Ground Equipment Grounding Tenant Circuit Breaker 125 A Max.

f f Each socket line connector may by moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, AC, and AC top to bottom. Equipment Grounding

f f Neutral and Service Ground

EZM114125, EZMR114125, EZMH114125

EZM314125, EZMR314125, EZMH314125

B C

f f Tenant Circuit Breaker 125 A Max. f f Tenant Circuit Breaker 125 A Max.

f f

f f

f f f Line f N f f Tighten 50 lb-ft (600 lb-in) A B Line C N Tighten 50 lb-ft (600 lb-in) A B C

f f

f f Each socket line connector may by moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, AC, AB, and BC top to bottom. Equipment Grounding

f f Neutral and Service Ground Equipment Grounding

f f Neutral and Service Ground

EZM115125, EZMR115125, EZMH115125

EZM315125, EZMR315125, EZMH315125

87
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161


Wiring Diagrams
A B C

f f Tenant Circuit Breaker 125 A Max. f f Tenant Circuit Breaker 125 A Max.

f f f Line f N f f Tenant Circuit Breaker 200 A Max.

Tighten 50 lb-ft (600 lb-in)

f f f Line f N f f Tighten 50 lb-ft (600 lb-in) A B Line C N Tighten 50 lb-ft (600 lb-in)

Neutral and Service Ground

Equipment Grounding

EZM112200, EZMR112200, EZMH112200

f f

f f

B C

f f

f f Each socket line connector may by moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, AC, AB, BC, and AC top to bottom. Equipment Grounding

f f Neutral and Service Ground Equipment Grounding

f f Neutral and Service Ground

EZM116125, EZMR116125, EZMH116125

EZM316125, EZMR316125, EZMH316125

A B

f Line f N Tenant Circuit Breaker 200 A Max.

Tighten 50 lb-ft (600 lb-in)

A Line B C N Tenant Circuit Breaker 200 A Max.

Tighten 50 lb-ft (600 lb-in)

B C

Neutral and Service Ground Equipment Grounding

Equipment Grounding

Each socket line connector may by moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB and BC top to bottom.

Neutral and Service Ground

EZM312200, EZMR312200, EZMH312200

EZM113200, EZMR113200, EZMH113200

88
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161


Wiring Diagrams
A B C A B C

A Line B C N

Tighten 50 lb-ft (600 lb-in) A B C A Line B C N


f f

Tenant Circuit f f Breaker 200 A Max. Each socket line connector may by moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, and AC top to bottom.

Tighten 50 lb-ft (600 lb-in) A B C

Neutral and Service Ground

Equipment Grounding

Tenant Circuit f f Breaker 200 A Max.

EZM313200, EZMR313200, EZMH313200


f f
f f

Neutral and Service Ground

Equipment Grounding

Each socket line connector may by moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, AC, and AC top to bottom.

EZM314200, EZMR314200, EZMH314200

f f

f Line f N Tenant Circuit Breaker 200 A Max.

Tighten 50 lb-ft (600 lb-in)

f Line f N f f Tenant Circuit Breaker 200 A Max.

Tighten 50 lb-ft (600 lb-in)

Neutral and Service Ground


f f

Equipment Grounding f f

EZML112200
Equipment Grounding

A B C

Neutral and Service Ground

EZM114200, EZMR114200, EZMH114200

f Line f N f f Tenant Circuit Breaker 200 A Max.

Tighten 50 lb-ft (600 lb-in)

A Line B C N Tenant Circuit Breaker 200 A Max.

Tighten 50 lb-ft (600 lb-in) f f

B C

Neutral and Service Ground

Equipment Grounding

Neutral and Service Ground

Equipment Grounding

Each socket line connector may by moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB and BC top to bottom.

EZML111200

EZML312200

89
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161


Wiring Diagrams
A C B High Leg (Power Leg) for 3f4W Delta System Tighten 50 lb-ft (600 lb-in) A BC A Line B C N Tenant Circuit Breaker 400 A Max. Equipment Grounding f f Tighten 50 lb-ft (600 lb-in) A B C f f A B C

A B C N Tenant Circuit Breaker 200 A Max. Line

High Leg (Power Leg) for 3f4W Delta System (All Tenant Breaker Positions) Neutral and Service Ground

EZML331200

f f Each socket line connector may by moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, and AC top to bottom.

High Leg (Power Leg) for 3f4W Delta System (All Tenant Breaker Positions)

A A BC

B Equipment Grounding

High Leg (Power Leg) for 3f4W Delta System

Neutral and Service Ground

EZML313200
High Leg (Power Leg) for 3f4W Delta System (All Tenant Breaker Positions)

A B C N Tenant Circuit Breaker 200 A Max. Line

A BC

Tighten 50 lb-ft (600 lb-in) High Leg (Power Leg) for 3f4W Delta System

A BC

High Leg (Power Leg) for 3f4W Delta System

Neutral and Service Ground

Line Equipment Grounding

A B C N A BC

Tighten 50 lb-ft (600 lb-in) High Leg (Power Leg) for 3f4W Delta System

EZML332200, EZMR332200

f f Tenant Circuit Breaker 200 A Max. f Line f N f f Tenant Circuit Breaker 125 A Max. f f Neutral and Service Ground Equipment Grounding Tighten 50 lb-ft (600 lb-in) A BC

EZML333200, EZMR333200

Neutral and Service Ground

Equipment Grounding

EZML113200

90
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161


Wiring Diagrams
A B C f f f f

f f

f f

f Line f N f f Tenant Circuit Breaker 125 A Max. f f

Tighten 50 lb-ft (600 lb-in)

A Line B C N Tenant Circuit Breaker 125 A Max.

Tighten 50 lb-ft (600 lb-in) A f f B C

f f Each socket line connector may by moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB, BC, AC, and AC top to bottom.

Neutral and Service Ground

Equipment Grounding

Neutral and Service Ground

Equipment Grounding

EZML114200

EZML314200

A A BC

C B A B C N f f

A B

Line High Leg (Power Leg) for 3f4W Delta System (All Tenant Breaker Positions)

Tighten 50 lb-ft (600 lb-in)

B C

A BC

High Leg (Power Leg) for 3f4W Delta System

Tenant Circuit Breaker 400 A Max. Each socket line connector may by moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AC.

Line

A B C N A BC

Neutral and Service Ground Tighten 50 lb-ft (600 lb-in) High Leg (Power Leg) for 3f4W Delta System

Equipment Grounding

EZML311400

B High Leg (Power Leg) for 3f4W Delta System

Tenant Circuit Breaker 200 A Max.

A BC

Line

A B C N

Tighten 50 lb-ft (600 lb-in) A BC High Leg (Power Leg) for 3f4W Delta System

Neutral and Service Ground

Equipment Grounding

EZML334200, EZMR334200

Tenant Circuit Breaker 400 A Max. High Leg (Power Leg) for 3f4W Delta System (All Tenant Breaker Positions)

Neutral and Service Ground

Equipment Grounding

EZML331400

91
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161


Wiring Diagrams
A B f f C High Leg (Power Leg) for 3f4W Delta System (All Tenant Breaker Positions) A C B

A BC

Line

A B C N f f

High Leg (Power Leg) for 3f4W Delta System

Tighten 50 lb-ft (600 lb-in)

B C Line A B C N Tighten 50 lb-ft (600 lb-in) A BC High Leg (Power Leg) for 3f4W Delta System

Tenant Circuit Breaker 400 A Max. Each socket line connector may by moved to balance loading. Phase AC, BC, or AB. This device leaves the factory phased AB and BC top to bottom.

Tenant Circuit Breaker 400 A Max.

Neutral and Service Ground

Equipment Grounding

EZML312400

Neutral and Service Ground

Equipment Grounding

EZML332400

92
1999 Square D All Rights Reserved 5/99

MP METER-PAK Meter Centers Class 4141


Replacement Parts

B D D A C C B C 2-Position 3-Position 4-Position C C A C A C C

B D C C C C C C C C

B C C C

A - LC

5-Position

A - RC

6-Position

Front View

Rear View

125 A MP METER-PAK Replacement Covers and Repair Kit


Number of Positions Catalog Number
MP22125 2 MPR22125 MPH22125 MP33125 3 MPR33125 MPH33125 MP44125 4 MPR44125 MPH44125 MP55125 5 MPR55125 MPH55125 MP66125 6 MPR66125 MPH66125

A Customer Cover
MP2125C MP2125C MP2125C MP3125C MP3125C MP3125C MP4125C MP4125C MP4125C MP5125LC MP5125RC MP5125LC MP5125RC MP5125LC MP5125RC MP6125C MP6125C MP6125C

B Pull Box Cover


MP2125PC MP2125PC MP2125PC MP34125PC MP34125PC MP34125PC MP34125PC MP34125PC MP34125PC MP56125PC MP56125PC MP56125PC MP56125PC MP56125PC MP56125PC

C Meter Socket Covers (refer to drawings above for quantity)


MMC MMRC MMRC MMC MMRC MMRC MMC MMRC MMRC MMC MMRC MMRC MMC MMRC MMRC

D Other Covers
MP2125TMC MPR2125TMC MPR2125TMC MMCBK MMCBK MMCBK ... ... ... MMCBK MMCBK MMCBK ... ... ...

E Repair Parts Kits


MM125KIT MM125KIT MM125KIT and MMHB MM125KIT MM125KIT MM125KIT and MMHB MM125KIT MM125KIT MM125KIT and MMHB MM125KIT MM125KIT MM125KIT and MMHB MM125KIT MM125KIT MM125KIT and MMHB

93
5/99 1999 Square D All Rights Reserved

MP METER-PAK Meter Centers Class 4141


Replacement Parts

B B D A C C A C A C C B C C C C

2-Position B D C C

3-Position 4-Position B C C C C C C C C C

A - LC

5-Position

A - RC

6-Position

E Front View

Rear View

200 A MP METER-PAK Replacement Covers and Repair Kit


Number of Positions A Catalog Number
MP42200 2 MPR42200 MPH42200 MP43200 3 MPR43200 MPH43200 MP64200 4 MPR64200 MPH64200 MP85200 5 MPR85200 MPH85200 MP86200 6 MPR86200 MPH86200

B Pull Box Cover


MP23200PC MP23200PC MP23200PC MP23200PC MP23200PC MP23200PC MP4200PC MP4200PC MP4200PC MP56200PC MP56200PC MP56200PC MP56200PC MP56200PC MP56200PC

C Meter Socket Covers (refer to drawings above for quantity)


MMC MMRC MMRC MMC MMRC MMRC MMC MMRC MMRC MMC MMRC MMRC MMC MMRC MMRC

D Other Covers
MMCBK MMCBK MMCBK ... ... ... ... ... ... MMCBK MMCBK MMCBK ... ... ...

E Repair Parts Kits


MP200KIT MP200KIT MP200KIT and MMHB MP200KIT MP200KIT MP200KIT and MMHB MP200KIT MP200KIT MP200KIT and MMHB MP200KIT MP200KIT MP200KIT and MMHB MP200KIT MP200KIT MP200KIT and MMHB

Customer Cover
MP2200C MP2200C MP2200C MP3200C MP3200C MP3200C MP4200C MP4200C MP4200C MP5200LC MP5200RC MP5200LC MP5200RC MP5200LC MP5200RC MP6200C MP6200C MP6200C

94
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Replacement Parts
EZ METER-PAK Meter Center Circuit Breaker Main Device Replacement Covers
Utility Covers (two piece construction) Ampere Rating Catalog Number Utility Cover (one piece construction, order one per device)
EZM1400CBC EZM1600CBC EZM1800CBC EZM11000CBC EZM11200CBC EZM11600CBC EZM3400CBC EZM3600CBC EZM3800CBC EZM31000CBC EZM31200CBC EZM31600CBC

System

Top Cover (Breaker Compartment, order one per device)


EZM1400CBUTC EZM1600CBUTC EZM1800CBUTC EZM11000CBUTC EZM11200CBUTC EZM3400CBUTC EZM3600CBUTC EZM3800CBUTC EZM31000CBUTC EZM31200CBUTC

Bottom Cover (Lug Landing Compartment, order one per device)


EZM1400CBUBC EZM1600CBUBC EZM1800CBUBC EZM11000CBUBC EZM11200CBUBC EZM3400CBUBC EZM3600CBUBC EZM3800CBUBC EZM31000CBUBC EZM31200CBUBC

1f3W, 120/240 Vac

400 600 800 1000 1200 1600 400 600 800 1000 1200 400 600 800 1000 1200 1600 400 600 800 1000 1200

EZM1400CB EZM1600CB EZM1800CB EZM11000CB EZM11200CB EZM11600CB EZM1400CBU EZM1600CBU EZM1800CBU EZM11000CBU EZM11200CBU EZM3400CB EZM3600CB EZM3800CB EZM31000CB EZM31200CB EZM31600CB EZM3400CBU EZM3600CBU EZM3800CBU EZM31000CBU EZM31200CBU

EZM1800CBC, EZM1600CBC, EZM3600CBC, and EZM3800CBC Circuit Breaker Main Device Cover

EZM1600CBUTC, EZM1800CBUTC, EZM3600CBUTC EZM3800CBUTC, EZM1600CBUBC, EZM1800CBUBC EZM3600CBUBC, and EZM3800CBUBC Underground Feed Circuit Breaker Main Device Cover

3f4W, 208Y/120 Vac or 240/120 Vac delta

EZ METER-PAK Meter Center Fusible Switch Main Device Replacement Covers


Utility Cover (one piece construction, order one per device)
EZM1400FSC EZM1600FSC EZM1800FSC EZM11200FSC EZM3400FSC EZM3600FSC EZM3800FSC

Utility Covers (two piece construction) Top Cover (Breaker Compartment, order one per device)
EZM1400FSUTC EZM1600FSUTC EZM1800FSUTC EZM11200FSUTC EZM3400FSUTC EZM3600FSUTC EZM3800FSUTC

System

Ampere Rating

Catalog Number

Bottom Cover (Lug Landing Compartment, order one per device)


EZM1400FSUBC EZM1600FSUBC EZM1800FSUBC EZM11200FSUBC EZM3400FSUBC EZM3600FSUBC EZM3800FSUBC

1f3W, 120/240 Vac

400 600 800 1200 400 600 800 1200 400 600 800 400 600 800

EZM1400FS EZM1600FS EZM1800FS EZM11200FS EZM1400FSU EZM1600FSU EZM1800FSU EZM11200FSU EZM3400FS EZM3600FS EZM3800FS EZM3400FSU EZM3600FSU EZM3800FSU

EZM11200CBC, EZM11600CBC, EZM31200CBC EZM31600CBC Circuit Breaker Main Device Cover

3f4W, 208Y/120 Vac or 240/120 Vac delta

EZ METER-PAK Meter Center Terminal Box Device Replacement Covers


System Ampere Rating
400 800 1600 400 800 1600

Catalog Number
EZM1400TB EZM1800TB EZM11600TB EZM3400TB EZM3800TB EZM31600TB

Utility Cover (one piece construction, order one per device)


EZM1400TBC EZM1800TBC EZM11600TBC EZM3400TBC EZM3800TBC EZM31600TBC

1f3W, 120/240 Vac 3f4W, or delta

EZM1600FSC, EZM1800FSC EZM3600FSC, and EZM3800FSC Fusible Switch Main Device Cover

EZM1800TBC, and EZM3800TBC Terminal Box Device Cover

95
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Replacement Parts

C C A D A C C C A C C C C A C C C C C C C C C

3-Position

4-Position

5-Position

6-Position

Front View

Rear View

125 A Residential EZ METER-PAK Meter Center Branch Unit Replacement Covers and Repair Kits
Number of Positions Catalog Number 1f IN / 1f OUT
EZM113125 EZMR113125 3 EZMH113125 ... ... ... EZM114125 EZMR114125 4 EZMH114125 ... ... ... EZM115125 EZMR115125 5 EZMH115125 ... ... ... EZM116125 EZMR116125 6 EZMH116125 ... ... ...

A Customer Cover
EZM113125C EZM113125C EZM113125C EZM313125C EZM313125C EZM313125C EZM114125C EZM114125C EZM114125C EZM314125C EZM314125C EZM314125C EZM115125C EZM115125C EZM115125C EZM315125C EZM315125C EZM315125C EZM116125C EZM116125C EZM116125C EZM316125C EZM316125C EZM316125C

C Meter Socket Covers (refer to drawings above for quantity)


MMC MMRC MMRC MMC MMRC MMRC MMC MMRC MMRC MMC MMRC MMRC MMC MMRC MMRC MMC MMRC MMRC MMC MMRC MMRC MMC MMRC MMRC

D Other Covers
EZM23TBKC EZM23TBKC EZM23TBKC EZM23TBKC EZM23TBKC EZM23TBKC ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...

E Repair Parts Kits


MM125 KIT MM125 KIT MM125 KIT and MMHB MM125 KIT MM125 KIT MM125 KIT and MMHB MM125KIT MM125 KIT MM125 KIT and MMHB MM125KIT MM125 KIT MM125 KIT and MMHB MM125KIT MM125 KIT MM125 KIT and MMHB MM125KIT MM125 KIT MM125 KIT and MMHB MM125KIT MM125 KIT MM125 KIT and MMHB MM125KIT MM125 KIT MM125 KIT and MMHB

3f IN / 1f OUT
... ... ... EZM313125 EZMR313125 EZMH313125 ... ... ... EZM314125 EZMR314125 EZMH314125 ... ... ... EZM315125 EZMR315125 EZMH315125 ... ... ... EZM316125 EZMR316125 EZMH316125

96
1999 Square D All Rights Reserved 5/99

EZ METER-PAK Meter Centers Class 4161, 4162


Replacement Parts

D - TBKC A A

D C C C A

C C C C

D - BK C C

2-Position

3-Position

4-Position

Front View

Rear View

200 A Residential EZ METER-PAK Meter Center Branch Unit Replacement Covers and Repair Kits
Catalog Number Number of Positions 1f IN / 1f OUT
EZM112200 EZMR112200 EZMH112200 2 ... ... ... EZM113200 EZMR113200 EZMH113200 3 ... ... ... EZM114200 EZMR114200 EZMH114200 4 ... ... ... EZM314200 EZMR314200 EZMH314200 EZM314200C EZM314200C EZM314200C MMC MMRC MMRC ... ... ... MM200KIT MM200KIT MM200KIT and MMHB EZM313200 EZMR313200 EZMH313200 ... ... ... EZM313200C EZM313200C EZM313200C EZM114200C EZM114200C EZM114200C MMC MMRC MMRC MMC MMRC MMRC EZM23TBKC EZM23TBKC EZM23TBKC ... ... ... MM200KIT MM200KIT MM200KIT and MMHB MM200KIT MM200KIT MM200KIT and MMHB EZM312200 EZMR312200 EZMH312200 ... ... ... EZM312200C EZM312200C EZM312200C EZM113200C EZM113200C EZM113200C MMC MMRC MMRC MMC MMRC MMRC EZM23TBKC and MMCBK EZM23TBKC and MMCBK EZM23TBKC and MMCBK EZM23TBKC EZM23TBKC EZM23TBKC MM200KIT MM200KIT MM200KIT and MMHB MM200KIT MM200KIT MM200KIT and MMHB

A Customer Cover
EZM112200C EZM112200C EZM112200C

C Meter Socket Covers (refer to drawings above for quantity)


MMC MMRC MMRC

D Other Covers
EZM23TBKC and MMCBK EZM23TBKC and MMCBK EZM23TBKC and MMCBK

E Repair Parts Kits


MM200KIT MM200KIT MM200KIT and MMHB

3f IN / 1f OUT
... ... ...

97
5/99 1999 Square D All Rights Reserved

EZ METER-PAK Meter Centers Class 4161, 4162


Replacement Parts

200 A C A D - BK C A C C C A C 2-Position C C C A C

1-Position

3-Position

4-Position D - BK2

400 A

D - BK1 C A C C D - BK1 D - BK2 2-Position A

Front View

D - BK2

Rear View

1-Position

200 A Commercial EZ METER-PAK Meter Center Branch Unit Replacement Covers and Repair Kits
Number of Positions
1 2 3 4

Catalog Number 1f IN / 1f OUT with 3f IN / 1f OUT with Lever Bypass Lever Bypass
EZML111-200 EZML112-200 ... EZML113-200 ... EZML114-200 ... ... ... EZML312-200 ... EZML313-200 EZML314-200

A Customer Cover
EZML111-200-C EZML112-200-C EZML312-200-C EZML113-200-C EZML313-200-C EZML114-200-C EZML314-200-C

C Meter Socket Covers (refer to drawings above for quantity)


EZMCRC EZMCRC EZMCRC EZMCRC EZMCRC EZMCRC EZMCRC

D Other Covers
EZMCBK ... ... ... ... ... ...

E Repair Parts Kits


EZML1200KIT EZML1200KIT EZML1200KIT EZML1200KIT EZML1200KIT EZML1200KIT EZML1200KIT

200 A Commercial EZ METER-PAK Meter Center Branch Unit Replacement Covers and Repair Kits
Number of Positions
1 2 3 4

Catalog Number 3f IN / 3f OUT 3f IN / 3f OUT without Bypass with Lever Bypass


... EZMR332200 ... EZMR333200 ... EZMR334200 ... EZML331200 ... EZML332200 ... EZML333200 ... EZML334200

A Customer Cover
EZML331200C EZML332200C EZML332200C EZML333200C EZML333200C EZML334200C EZML334200C

C Meter Socket Covers (refer to drawings above for quantity)


EZMCRC EZMCRC EZMCRC EZMCRC EZMCRC EZMCRC EZMCRC

D Other Covers
EZMCBK ... ... ... ... ... ...

E Repair Parts Kits


EZML3200KIT EZM3200KIT EZML3200KIT EZM3200KIT EZML3200KIT EZM3200KIT EZML3200KIT

400 A Commercial EZ METER-PAK Meter Center Branch Unit Replacement Covers and Repair Kits
Number of Positions
1 2 q c

Catalog Number 3f IN / 1f OUT with 3f IN / 3f OUT Lever Bypass with Lever Bypass
EZML311400 ... EZML312400 ... ... EZML331400 ... EZML332400

A Customer Cover
EZML311400C EZML331400C EZML312400C EZML332400C

C Meter Socket Covers (refer to drawings above for quantity)


EZMCRC EZMCRC EZMCRC EZMCRC

D Other Covers
EZML400BK1q EZML400BK2c

E Repair Parts Kits


EZML1400KIT EZML3400KIT EZML1400KIT EZML3400KIT

Kit includes 2 blank covers. Kit includes 3 blank covers.

98
1999 Square D All Rights Reserved 5/99

AC Disconnects

SQUARE D COMPANY OFFERS A FULL LINE OF AIR CONDITIONING DISCONNECTS

Pull-Out Type Disconnect SwitchNot-Fusible and Fusible, NEMA Type 3ROutdoor 240 Vac, 1, 2 Wire with Ground
Wire Range Al/Cu Catalog Number Description Hp Max. Equipment Grounding Terminals Al/Cu
(2) 144 (2) 144 (2) 144

Line

Load

UFP222R FP221R FP222R

60 A Not Fusiblec 30 A Fusibleq 60 A Fusibleq

10 3 10

143 143 143

143 146 143

FP Series Devices

Enclosed Molded Case SwitchNot-Fusible NEMA Type 3R Outdoor 240 Vac, 1, 2 Wire with Ground
Wire Range Al/Cu Catalog Number Description Hp Max. Equipment Grounding Terminals Al/Cu
(2) 144

Line

Load

QO200TR PKHB c q

60 A Not Fusiblec

10

144

146

Mounting bracket used with QO200TR for stucco and lapped siding applications10 per box.

Does not contain overcurrent protection. Suitable for use on system with up to 10K RMS symmetrical amperes available fault current at 240 Vac when protected by a fuse or circuit breaker rated 60 A or less. Suitable for use on systems with up to 10K RMS symmetrical amperes available fault current at 240 Vac.

QO200TR

99
5/99 1999 Square D All Rights Reserved

Square D Company 1601 Mercer Road Lexington, KY 40511 (606) 243-8000 www.squared.com

QO, I-LINE, VISI-TITE, Square D and are Registered Trademarks of Square D Company or related companies. All other trademarks are the intellectual property of their respective companies. Catalog No. 4100CT9801 May 1999 1999 Square D All Rights Reserved.