WRITE UP FOR BOILER DRIVE INTERLOCK SCHEMES


(REV-0)

CLIENT:

DHARANI SUGARS & CHEMICALS LIMITED, UNIT-III

CONSULTANT: M/s. AVANT-GARDE ENGINEERS & CONSULTANTS (P) LIMITED

DOCUMENT NUMBER: 4-28058-DOC-043 TOTAL NO. OF SHEETS: 16 (INCLUDING COVER PAGE)

0 REV.NO.

12.08.08 DATE

G.Suresh PREPARED

P.Gunasekaran CHECKED

K.Ramani. APPROVED

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

LOGIC FOR BFP #1: BFP #1 shall be started in Auto/Manual mode, when BFP #1 shall be selected in remote mode of operation. Local / remote selection shall be from DCS only. BFP #1 shall be switched on in auto mode, only when the following conditions are satisfied: a. BFP #1 standby selected. b. BFP #2 is running & BFP #2 discharge pressure low or BFP #3 is running and BFP #3 discharge pressure low c. BFP #2 tripped or BFP #3 tripped. d. Deaerator level not low. e. DP across suction strainer BFP #1 not high. f. BFP #1 suction manual valve opened. BFP#1 shall be switched on manually, only when the following conditions are satisfied: a. b. c. d. Deaerator level not low. DP across suction strainer BFP #1 not high. BFP #1 suction manual valve shall be opened. BFP#1 Start Push Button Pressed.

BFP #1 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. Deaerator level very low. DP across suction strainer BFP #1 is high. BFP #1 bearing temperatures are very high. BFP #1 motor bearing temperatures are very high. BFP #1 motor winding temperatures are very high.

LOGIC FOR BFP #2: BFP #2 shall be started in Auto/Manual mode, When BFP # 2 shall be selected in remote mode of operation. Local / remote selection shall be from DCS only. BFP #2 shall be switched on in auto mode, only when the following conditions are satisfied: a. BFP #2 standby selected. b. BFP #1 is running BFP #1 discharge pressure low or BFP#3 is running and BFP #3 discharge pressure low. c. BFP #1 tripped or BFP #3 tripped. d. Deaerator level not low.
------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 1 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

e. DP across suction strainer #2 not high. f. BFP #2 suction manual valve opened. BFP #2 shall be switched on manually, only when the following conditions are satisfied: a. b. c. d. Deaerator level not low. DP across suction strainer BFP #2 not high. BFP #2 suction manual valve opened. BFP#2 Start Push Button Pressed

BFP #2 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions occurred: a. b. c. d. e. Deaerator level very low. DP across suction strainer #2 is high. BFP #2 bearing temperatures are very high. BFP #2 motor bearing temperatures are very high. BFP #2 motor winding temperatures are very high.

LOGIC FOR BFP #3: BFP #3 shall be started in Auto/Manual mode, when BFP #1 shall be selected in remote mode of operation. Local / remote selection shall be from DCS only. BFP #3 shall be switched on in auto mode, only when the following conditions occurred: a. BFP #3 standby selected. b. BFP #1 is running and BFP #1 discharge pressure low or BFP#2 is running and BFP #2 discharge pressure low c. BFP #1 or BFP #2 tripped. d. Deaerator level not low. e. DP across suction strainer BFP #3 not high. f. BFP #3 suction manual valve opened. BFP #3 shall be switched on manually, only when the following conditions are satisfied: a. b. c. d. Deaerator level not low. DP across suction strainer BFP #3 not high. BFP #3 suction manual valve opened. BFP#3 Start Push Button Pressed.

BFP #3 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred:
------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 2 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

a. b. c. d. e.

Deaerator level very low. DP across suction strainer #3 is high. BFP #3 bearing temperatures are very high. BFP #3 motor bearing temperatures are very high. BFP #3 motor winding temperatures are very high.

LOGIC FOR ID FAN #1: ID fan #1 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. ID Fan #1 inlet guide vane closed. b. ID Fan #1 remote selected. c. ID fan #1 start PB pressed. ID fan #1 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. ID fan #1 motor bearing temperatures are very high. b. ID fans #1 bearing temperatures are very high. c. ID fan #1 motor winding temperatures are very high. LOGIC FOR ID FAN #2: ID fan #2 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. ID Fan #2 inlet guide vane closed. b. ID Fan #2 remote selected. c. ID fan #2 start PB pressed. ID fan #2 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. ID fan #2 motor bearing temperatures are very high. b. ID fans #2 bearing temperatures are very high. c. ID fan #2 motor winding temperatures are very high. LOGIC FOR FD FAN #1: FD fan #1 shall be started, only when the following conditions are occurred:
------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 3 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

Local / remote selection shall be from DCS only. a. b. c. d. e. f. Drum level normal. Both the emergency PB not pressed. Any one of the ID fan is running. FD fan#1 remote selected. FD fan #1 start PB pressed. FD fan #1 inlet guide vane closed.

FD fan #1 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. f. g. Drum level very low. Furnace pressure is very high. Both the emergency PB pressed. Both the ID fans stopped. FD fan #1 bearing temperatures are very high. FD fan #1 motor bearing temperatures are very high. FD fan #1 motor winding temperatures are very high.

LOGIC FOR FD FAN #2: FD fan #2 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. f. Drum level normal. Both the emergency PB not pressed. Any one of the ID fan is running. FD fan#2 remote selected. FD fan #2 start PB pressed. FD fan #2 inlet guide vane closed.

FD fan #2 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. f. g. Drum level very low. Furnace pressure is very high. Both the emergency PB pressed. Both the ID fans stopped. FD fan #2 bearing temperatures are very high. FD fan #2 motor bearing temperatures are very high. FD fan #2 motor winding temperatures are very high.

------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 4 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

LOGIC FOR SA FAN #1: SA fan # 1 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. Any one of the FD fan is running. Any one of the ID fan is running. SA fan #1 remote selected. SA fan #1 start PB pressed SA fan #1 inlet guide vane closed.

SA fan #1 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. SA fan #1 bearing temperatures are very high. SA fan #1 motor bearing temperatures are very high. SA fan #1 motor winding temperatures are very high. Both the ID fans stopped. Both the FD fans stopped.

LOGIC FOR SA FAN #2: SA fan # 2 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. Any one of the FD fan is running. Any one of the ID fan is running. SA fan #2 remote selected. SA fan #2 start PB pressed SA fan #2 inlet guide vane closed.

SA fan #2 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. SA fan #2 bearing temperatures are very high. SA fan #2 motor bearing temperatures are very high. SA fan #2 motor winding temperatures are very high. Both the ID fans stopped. Both the FD fans stopped

LOGIC FOR DRUM FEEDER #1: Drum feeder #1 shall be started, only when the following conditions are occurred:
------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 5 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

Local / remote selection shall be from DCS only. a. b. c. d. e. f. g. h. Drum feeder #1 remote selected. Screw feeder #1 running Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Drum feeder #1 start PB pressed.

Drum feeder # 1 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. f. c. d. e. Screw feeder #1 is not running. Furnace pressure is abnormal. Both the ID fans stopped. Both the FD fans stopped. Drum level is abnormal. Both the SA fans stopped.

LOGIC FOR DRUM FEEDER #2: Drum feeder #2 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. f. g. h. Drum feeder #2 remote selected. Screw feeder #2 running Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Drum feeder #2 starts PB pressed.

Drum feeder #2 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. f. Screw feeder #2 is not running Furnace pressure is abnormal Both the ID fans stopped. Both the FD fans stopped Drum level is abnormal. Both the SA fans stopped.

------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 6 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

LOGIC FOR DRUM FEEDER #3: Drum feeder #3 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. f. g. h. Drum feeder #3 remote selected. Screw feeder #3 running Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Drum feeder #3 starts PB pressed.

Drum feeder #3 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. f. Screw feeder #3 is not running. Furnace pressure is abnormal. Both the ID fans stopped. Both the FD fans stopped Drum level is abnormal. Both the SA fans stopped.

LOGIC FOR DRUM FEEDER #4: Drum feeder #4 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. f. g. h. Drum feeder #4 remote selected. Screw feeder #4 running Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Drum feeder #4 starts PB pressed.

------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 7 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

Drum feeder #4 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. f. g. Drum feeder #4 remote selected. Screw feeder #4 is not running Furnace pressure is abnormal. Both the ID fans stopped. Both the FD fans stopped Drum level abnormal. Both the SA fans stopped.

LOGIC FOR DRUM FEEDER #5: Drum feeder #5 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. f. g. h. Drum feeder #5 remote selected. Screw feeder #5 running Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Drum feeder #5 starts PB pressed.

Drum feeder #5 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. f. Screw feeder #5 is not running Furnace pressure not normal Both the ID fans stopped. Both the FD fans stopped Drum level not normal. Both the SA fans stopped.

LOGIC FOR DRAG CHAIN FEEDER #1: Drag chain feeder #1 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. Drag chain feeder #1 remote selected. b. Furnace pressure normal c. Any one of the ID fan is running.
------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 8 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

d. e. f. g.

Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Drag chain feeder #1 start PB pressed.

Drag chain feeder #1 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. Furnace pressure is abnormal. Both the ID fans stopped. Both the FD fans stopped Drum level is abnormal. Both the SA fans stopped.

LOGIC FOR DRAG CHAIN FEEDER #2: Drag chain feeder #2 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. f. g. Drag chain feeder #2 remote selected. Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Drag chain feeder #2 starts PB pressed.

Drag chain feeder #2 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. Furnace pressure is abnormal. Both the ID fans stopped. Both the FD fans stopped Drum level is abnormal. Both the SA fans stopped.

LOGIC FOR DRAG CHAIN CONVEYOR #3: Drag chain feeder #3 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only.
------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 9 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

a. b. c. d. e. f. g.

Drag chain feeder #3 remote selected. Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Drag chain feeder #3 starts PB pressed.

Drag chain feeder #3 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. Furnace pressure is abnormal. Both the ID fans stopped. Both the FD fans stopped Drum level is abnormal. Both the SA fans stopped.

LOGIC FOR DRAG CHAIN FEEDER #4: Drag chain feeder #4 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. f. g. Drag chain feeder #4 remote selected. Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Drag chain feeder #4 starts PB pressed.

Drag chain feeder #4 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. Furnace pressure is abnormal Both the ID fans stopped. Both the FD fans stopped Drum level is abnormal. Both the SA fans stopped.

LOGIC FOR DRAG CHAIN FEEDER #5: Drag chain feeder #5 shall be started, only when the following conditions are occurred:
------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 10 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

Local / remote selection shall be from DCS only. a. b. c. d. e. f. g. Drag chain feeder #5 remote selected. Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Drag chain feeder #5 starts PB pressed.

Drag chain feeder #5 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. Furnace pressure is abnormal Both the ID fans stopped. Both the FD fans stopped Drum level is abnormal. Both the SA fans stopped.

LOGIC FOR SCREW FEEDER #1: Screw feeder #1 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. f. g. Screw feeder #1 remote selected. Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Screw feeder #1 start PB pressed.

Screw feeder #1 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. Furnace pressure is abnormal. Both the ID fans stopped. Both the FD fans stopped Drum level is abnormal. Both the SA fans stopped.

------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 11 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

LOGIC FOR SCREW FEEDER #2: Screw feeder #2 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. f. g. Screw feeder #2 remote selected. Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Screw feeder #2 start PB pressed.

Screw feeder #2 shall stop automatically, either in remote mode or in Local mode of operation, when the following conditions are occurring: a. b. c. d. e. Furnace pressure is abnormal Both the ID fans stopped. Both the FD fans stopped Drum level is abnormal. Both the SA fans stopped.

LOGIC FOR SCREW FEEDER #3: Screw feeder #3 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. f. g. Screw feeder #3 remote selected. Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Screw feeder #3 start PB pressed.

Screw feeder #3 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. Furnace pressure is abnormal Both the ID fans stopped. Both the FD fans stopped Drum level is abnormal. Both the SA fans stopped.

------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 12 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

LOGIC FOR SCREW FEEDER #4: Screw feeder #4 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. f. g. Screw feeder #4 remote selected. Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Screw feeder #4 start PB pressed.

Screw feeder #4 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. Furnace pressure is abnormal. Both the ID fans stopped. Both the FD fans stopped Drum level is abnormal. Both the SA fans stopped.

LOGIC FOR SCREW FEEDER #5: Screw feeder #5 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. b. c. d. e. f. g. Screw feeder #5 remote selected. Furnace pressure normal Any one of the ID fan is running. Any one of the FD fan is running. Drum level normal. Any one of the SA fan is running. Screw feeder #5 start PB pressed.

Screw feeder #5 shall be stopped automatically, either in remote mode or Local mode of operation, when the following conditions are occurred: a. b. c. d. e. Furnace pressure is abnormal. Both the ID fans stopped. Both the FD fans stopped Drum level is abnormal. Both the SA fans stopped.

------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 13 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

LOGIC FOR HP DOSING PUMP #1: HP Dosing pump #1 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. HP Dosing pump #1 remote selected. b. HP Dosing tank level not low. c. HP Dosing pump #1 start PB pressed. HP Dosing pump #1 shall be stopped automatically, either in remote mode or Local mode of operation, when the HP Dosing tank level becomes low. LOGIC FOR HP DOSING PUMP #2: HP Dosing pump #2 shall be started, only when the following conditions are satisfied: a. HP Dosing pump #2 remote selected. b. HP Dosing tank level not low. c. HP Dosing pump #2 starts PB pressed. HP Dosing pump #2 shall be stopped automatically, either in remote mode or Local mode of operation, when the HP Dosing tank level becomes low. LOGIC FOR LP DOSING PUMP #1: LP Dosing pump #1 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. LP Dosing pump #1 remote selected. b. LP Dosing tank level not low. c. LP Dosing pump #1 start PB pressed. LP Dosing pump #1 shall be stopped automatically, either in remote mode or Local mode of operation, when the LP Dosing tank level becomes low.

------------------------------------------------------------------------------BOILER-INTERLOCK WRITE UP 14 AVANT-GARDE

FIVES CAIL KCP LIMITED DHARANI SUGARS & CHEMICALS LTD, BAGASSE BASED COGENERATION PROJECT
-----------------------------------------------------------------------------

LOGIC FOR LP DOSING PUMP #2: LP Dosing pump #2 shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. LP Dosing pump #2 remote selected. b. LP Dosing tank level not low. c. LP Dosing pump #2 start PB pressed. LP Dosing pump #2 shall be stopped automatically, either in remote mode or Local mode of operation, when the LP Dosing tank level becomes low. LOGIC FOR HP DOSING STIRRER: HP Dosing stirrer shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. HP Dosing stirrer remote selected. b. HP Dosing stirrer start PB pressed. HP Dosing stirrer shall be stopped automatically, when the stop push button pressed. LOGIC FOR LP DOSING STIRRER: LP Dosing stirrer shall be started, only when the following conditions are occurred: Local / remote selection shall be from DCS only. a. LP Dosing stirrer remote selected. b. LP Dosing stirrer start PB pressed. LP Dosing stirrer shall be stopped automatically, when the stop push button pressed. LOGIC FOR DEAERATOR OVERFLOW SOLENOID VALVE: Whenever the Level in deaerator becomes very high, which is sensed by Level switch LSHH 502, overflow solenoid valve shall be energized. And water shall be dumped to DM water tank.