CAC THIET B PHU TR

Bao gom : - Tu nguon : Co 5 loai tu chnh la Lorain 50A, Ascom, Postef, Delta ASM, Siemens. - On ap : Co 2 loai chnh la BP va Lioa. - Canh bao ngoai : Co 2 loai chnh la Viet Anh va CT-In. - Chong set : Co 2 loai chnh la Tercel va Proline. - Tu ien AC.

TU NGUON LORAIN 50A


Tu nguon Lorain co chc nang chuyen ien ap AC ngo vao thanh ien ap -48V DC ngo ra. Tu nguon Loain co kch thc nh sau : 2140 x 530 x 380. Ngo vao AC : Ngo AC vao pha ben hong trai cua tu nguon. Khi m module REC au tien ben tay trai ta se thay 01 domino co 6 ngo vao tng ng vi 3 pha cua ien ap AC tng ng nh sau : - Pha th nhat cap nguon AC cho REC th nhat. - Pha th 2 cap nguon cho REC th 2. - Pha th 3 cap nguon cho REC 3. Khi bat c 1 pha nao mat th se mat nguon AC cap cho REC va REC se b canh bao RFA.

NGO RA DC

CB cat Accu

Khi CB v tr OFF th khoi accu se b ngat ra khoi nguon. Do o CB phai luon e v tr ON neu accu tot e duy tr ien ap khi ngo vao AC b mat.
4

Main board canh bao

Cac trang thai hien th cua board canh bao

Khi mat ien AC hay t 02 REC tr len b hong : en MJ va MN se sang va ong thi a canh bao mat ien AC ve OMC. Khi mat 1 pha ien hay co 01 REC b hong : en MJ se sang va a canh bao ve OMC. Neu ien ap ngo ra > 55.8 VDC th en HVA1 sang. Neu ien ap ngo ra > 58.4 VDC th en HVA2 sang va a canh bao ve OMC. Neu ien ap ngo ra < 51.25 VDC th en LVA1 sang. Neu ien ap ngo ra < 48.25 VDC th en LVA2 sang va a canh bao ve OMC. Neu cau ch c noi vi nhng ngo vao canh bao b h th en FA se sang. Khi S3 c nhan th en ACO se sang Khi S2 c bat sang SET mode thu en SET se sang Khi nguon Accu c sac th en EQ se sang.
6

Cac trang thai cua Switch ieu khien

S1 : nut bat ieu khien can bang c dung e chon cac chc nang OFF/RESET, ON, MAN.

Switch S2: chon cac chc nang VOLTS, AMPS, SET - VOLTS : man hnh o hien th ien ap tai. - AMPS: man hnh o hien th dong ien tai. - SET: cai at nhng mc gii han nh mong muon. Switch S3 (ACO) : tat am thanh cua cac canh bao. Switch S4 (SEL) : chon cac chc nang ieu khien va canh bao khi nut S2 v tr SET. - S5 (INC) : tang gia tr cai at hien th tren man hnh o. - S6 (DEC) : giam gia tr cai at hien th tren man hnh o.

- OFF/RESET : nut S1 c nhan en v tr nay se lam ket thuc chu ky nap can bang cho Battery. - ON : nut S1 c nhan en v tr nay cho biet bo nh thi nap can bang ang hoat ong. - MAN : nut S1 c chuyen en v tr nay cho biet mach ieu khien nap can bang c kch hoat cho en khi nut S1 c chuyen en v tr khac.

REC 50A
REC 50A co chc nang bien oi ien ap AC ngo vao thanh ien ap -48VDC ngo ra cua khoi. Cac thao tac khi bat REC : Kiem tra xem cac CB AC INPUT va DC OUTPHUT co ang e v tr OFF hay khong. Neu khong th phai gat xuong v tr OFF. Bat CB AC INPUT len v tr ON. Neu en AC ON sang xanh th tot. Neu en AC ON tat ong thi en RFA sang th hoac la cha co nguon vao hoac la REC b hong hoac la REC cha c ong sat. Neu en AC ON sang bnh thng th tiep theo ta bat CB DC OUTPUT len v tr ON. Neu CB DC OUTPUT khong b nhay la REC tot, ong thi ta se thay en RECT CUR (AMPS) se sang vang len mot vai nac. Neu CB DC OUTPUT b nhay, ong thi en RFA b sang o th REC a b hong hoac REC cha ong sat pha tren. Khi en RFA sang th hoac canh bao cha co AC hoac REC a b hong. Khi en FAN FAIL sang th bo phan quat cua REC b hong khong chay, tuy nhien REC van cung cap ien AC ngo ra trong trng hp nay. Moi Module REC chu c dong toi a la 50A (ke ca dong nap Accu). Do o moi tu phai co t 02 Rec tr len e d phong va can bang ien ap.
8

Tu nguon ASCOM

Tu nguon Ascom co chc nang chuyen ien ap AC ngo vao thanh ien ap -48V DC ngo ra. Tu nguon Loain co kch thc nh sau : 1000 x 600 x 450.
9

Ngo vao nguon AC

Khi ta m ca tu ra se thay co ngan dai ng cac CB. Ke ben day CB ben tay trai co 1 domino tren o co ghi L1, L2, L3 va N. o chnh la ngo vao AC cua tu nguon ASCOM. Khi ta m ca tu ra se thay co ngan dai ng cac CB. Ke ben day CB ben tay trai co 1 domino tren o co ghi L1, L2, L3 va N. o chnh la ngo vao AC cua tu nguDay CB t F11 en F18 tng ng vi cac module REC di cua tu. Ne u co bao nhieu REC th co chng o CB c bat len e cap nguon cho module REC, ong thi ta cung co : - Pha th nhat cap nguon AC cho REC th nhat. - Pha th 2 cap nguon cho REC th 2. - Pha th 3 cap nguon cho REC 3. Khi bat c 1 pha nao mat th se mat nguon AC cap cho REC va REC se b canh bao en o tai LED ALARM tren can h ca tu ben ngoai..
10

Rectifier

Day Rec at gan sat ay tu nguon. - Ngo vao cua Rec : 220V / max = 12 A - Ngo ra cua Rec : 48V / max = 42 A Cac trang thai hien th tren LED cua REC
11

Ngo ra DC cap cho thiet b

Day CB cap nguon cho thiet b nam pha tren cua tu. No bao gom 2 day :

- Day 1 gom 3 CB 63A : cap nguon DC cho tu BTS

- Day 2 gom 5 CB 6 A 12A : cap nguon DC cho cac thiet b phu tr Day cau ch noi vi Accu : gom co 2 cau ch tng ng vi 2 dan bnh.

12

Mainboard hien th
Cac canh bao tren canh ca tu : UA : Canh bao tai h, batt h NUA : Canh bao hong REC AS : Canh bao ien ap thap MF : Canh bao mat ien

Vai tro cua cac phm chc nang : - EXIT : thoat khoi menu hien tai. - Mui ten hng len : La chon menu pha trc hay tang gia tr ang set. - Mui ten hng xuong : La chon menu pha sau hay giam gia tr ang set. - ENTER : chon menu hien tai hay chap nhan gia tr ang ser Trong main menu ta co cac menu sau : Display, Protocol, General, Alarm, Usys, Temp Comp, Boost charge, Battery Test, Equalise, SAE, Auxiliary, PC/Modem.
13

Che o : DISLAY
1.1. Usys : ien ap cua nguon tai ngo ra cua tai. Isys : Tong dong cua he thong = dong tai 1+ tai 2 + tai 3+ Isys 1..3 : Gia tr dong cua tng tai 1.2 Usys : ien ap cua nguon tai ngo ra cua tai. Psys : Tong cong suat cua he thong = cong suat tai 1+ tai 2 + tai 3+ Psys 1..3 Cong suat cua tng tai 1.3 Tamb : Hien th nhiet o xung quanh Tbatt : Hien th nhiet o accu 1.4 Ibatt 12 : Hien th dong cua tng accu. Neu accu nao khong ong cau ch th gia tri **** se hien len. 1.5 Ubatt / Udiff : Hien th ien ap cua tng dan bnh. Neu dan bnh 2 khong co th no se hien th gia tr khac nhiet gia 2 dan bnh (luc nay no hieu ien ap bnh 2 = 1V). 1.6 Irect : Dong tong cua tat ca Rec 1.7 Charge Mode : Che o hien tai cua accu 1.8 Alarm : Hien th canh bao hien co cua nguon.
1. Display 1. Usys: 53,5 V Isys : 200 A 1. 1 Isys 1:50,0 A 2: 100 A 3:50,0 A 2. Usys: 53,5 V Psys: 10,7 kW 1. 1 Psys 1:2,7 kW 2: 5,4 kW 3: 2,7 kW

3. Tamb: 24,8 C Tbatt: 26,2 C

4. Ibatt: 50,0 A 1 : 50,0 A 2: 50,0 A

5. Ubatt / Udiff: 1 : 52,5 V 2: 53,5 V

6. Irect: 300 A

7. Charge Mode: Float charge

8. Alarm: UA Batt Fuse

14

T ngun Postef
Gm c 3 loi

VSR 200 : ch c 01 hc VSR 400 : gm 02 hc VSR 600 : gm 03 hc

15

Mn hnh cnh bo

xem c in p AC vo th nhn nt VSEL, n ACV sng hin ln gi tr in p AC ng vo, nu n DCV sng th hin ln gi tr p DC ng ra. xem c dng DC vo th nhn nt VSEL, n LDA sng th hin ln gi tr dng BTS tiu th, nu n BTA sng th hin ln gi tr dng np ca accu. xem cnh bo th nhn nt F6 (ALARM), nhn F5 (DOWN) xem ln lt cc cnh bo. set cnh bo th nht F2, ri F3, nhn tip F5 cho n khi xut hin dng REC1=ON, REC2=ON, REC3=OFF, REC4=OFF, REC5=OFF,, REC12=OFF, nhn F6 hay F1 chn REC cn sa cnh bo (ON : xut, OFF : khng xut cnh bo), xong nhn F3 chn gi tr sa.
16

CB AC vo ca tng REC

Nu loi ngun VSR 200 th AC R ng vi REC 1, AC S ng vi REC 2, AC T ng vi REC 3 (t tri qua phi). Nu loi ngun VSR 400, 600 th AC R ng vi ngn 1, AC S ng vi ngn 2, AC T ng vi ngn 3 (t trn xung di).
17

V tr REC

18

Rec Postef

Nu REC tt th n POWER ON s sng vng Nu REC hng th n ALARM s Lu kim tra xem cng tc bt ON hay cha.
19

Cng tc Accu

Nu t VSR 200 th c CB accu bn gc phi ca t. Nu t VSR 400, 600 th c cu ch pha bn tay tri t

20

Ngun Siemens
Ng vo AC trn nc t
Ng vo AC

CB AC ng vo cp ngun cho REC (BR21, BR22, BR23)

21

Ng vo AC

V tr u in vo

CB ng vo AC cp in cho REC (BR21,22,23)

22

Ng ra accu
CB accu (BR 33)

V tr u dy accu (trng : cc dng; xanh : cc m)


23

Ng ra DC
CB DC (BR 28,29,30). 3 CB tng ng vi 3 ng ra di

Ng ra DC (xanh : cc m, trng : cc dng)

24

Module ngun
Khi iu khin, trng thi bnh thng th n AC v DC sng xanh) Module ngun, bnh thng n AC ON xanh
25

Ngun Delta AMS

26

Ng vo AC

Nm pha trn cc module REC, pha bn tri dy cu ch chng st mu , c ghi r L1, L2, L3, N, PE (nu khng nhn thy th ng vo AC b ming nha che i)
27

Ng ra DC
Dy CB nm pha tri
Dy CB truyn dn (F1 F4) Cc dng Dy CB BTS (F10 F13)

28

Ng ra Accu
Dy CB nm pha phi

Cc dng

Dy CB accu (F11 F14)

29

CB Rec

Mi module REC tng ng vi 01 CB pha trn (k bn dy cu ch chng st ca t ngun) (LF11 LF 18)


30

Module REC

Cng sut ca REC l 200W (54V 37A DC; 220V 12Amax AC). Khi Rec hot ng bnh thng th LED OK sng xanh bnh thng. Khi n LED OK nhp nhy (200 ms sng 200 ms tt ) l cnh bo REC b hng. Khi n LED OK nhp nhy (20 ms sng 1000 ms tt ) l cnh bo ng vo (in p vo) AC ca REC vt ngng. reset REC th ta nhn nt Config cho n khi n LEC Com bt u nhp nhy (khong 10 giy), khi REC s reset li gi tr mc nh ca nh sn xut.

31

Ngun Emerson

CB DC

Module ngun

Khi iu Khin

32

Ng vo AC

- Ng vo AC nm pha mt sau bn phi ca thit b (m np ra mi thy). - Cung cp ng vo AC pha trn, pha di a in vo ti tng REC. A1, A2, A3 l dy nng tng ng vi pha 1,2,3; a1, a2, a3 A2, A3 l dy ngui tng ng vi pha 1,2,3. A1, a1 cung cp AC cho module ngun 1; A2, a2 cung cp AC cho module ngun 2; A3, a3 cung cp AC cho module ngun 3 (t tri qua phi). PE v v tr u mass. Ng vo AC cho php t 85 V 290V. Khi in p < 110V th cng sut ng ra ca thit b gim 50%.
33

Ng ra DC
-

Ng ra cc ( - )

Ng ra cc ( + )

Cc ( + ) ca ng ra c u chung vi nhau bng thanh ng. Cc ( - ) c cch ly vi nhau qua dy cc CB. CB accu nm ngoi cng tay tri, dung lng 100A DC (trn CB ghi C100) CB cp cho BTS thng thng nm cc v tr k bn tay phi ca CB Accu, dung lng 40A DC (trn CB ghi C40) CB cp cho truyn dn thng thng nm ngoi cng bn tay phi, dung lng 18A DC (trn CB ghi C18). Nu dng CB ny cp cho BTS s hay b nhy CB ngun DC.
34

Module ngun (Rectifier)


Mi module ngun c 3 n hin th t tri qua phi nh sau : n cnh bo ngun AC (c : xanh, khng c : tt) n ch th bo v : cnh bo n vng khi ng vo AC b qu p hay qu thp, khi nhit ca REC qu cao, dng in khng cn bng,. Nu khng c th tt. n cnh bo hng : khi module b hng th n . Thng s k thut ca module ngun : Ng vo AC : 85 290 V Ng ra DC max : 60 A Cng sut thit b : 2900W Nhit cho php : -5OC n 65OC
35

Board iu khin
Hot ng bnh thng : xanh Alarm : Dng s dng hin ti

Cnh bo hin ti

in p ng ra hin ti
36

Password

Password de config la: 1

37

Status : trng thi ca Rec, cnh bo hin ti, lch s cc cnh bo trc .

Nhn ENT

Nhn ENT

Nhn ENT

Nhn

tr v mn hnh trc, nhn ESC. Xut hin mn hnh STATUS, mi tn xung chon Active Alarm

38

39

40

41

Maintenance

42

Setting

43

Password

Users with different password levels have different authorities. See the following table:

Table 4-5 Different password levels and relevant different authorities


Authority Default password Configuration of general parameters 1 Users authority, plus resetting system, resetting password and modifying system type.

Level User Operator

Administrator Operators authority, plus modifying password of all levels, controling alarm sound volume, browsing system parameters that can be set only through the host 640275

44

Battery setting
Among which, the battery parameters are divided into 5 kinds: basic, BLVD, charging management, battery test, temperature coefficient, and they are displayed in two pages, as shown below: What follows is the description of the parameter functions and values by dividing them into 5 small categories and 5 big categories. 4.7.2 Battery Selection 1. The first page of the Battery Selection is shown below:

What follows is the description of the parameter functions and values by dividing them into 5 small categories and 5 big categories. 4.7.2 Battery Selection 1. The first page of the Battery Selection is shown below:

45

LVD Parameter Description


1. Function description LLVD means the monitoring module opens the LLVD contactor, so that the nonpriority load will be powered off. In this way, the battery remaining capacity can sustain the priority load longer. BLVD means the monitoring module opens the BLVD contactor. In this way, the battery will stop powering the load

Parameter
LLVD Enable BLVD Enable Y, N

Range
Y

Default
Select Y to enable LLVD function Select Y to disable the BLVD function

Value description

LLVD Mode LLVD Volt BLVD Volt

Time, voltage 40V ~ 60V

Voltage 44.0V 43.2V

Select Voltage, when the monitoring module detects that the battery voltage is lower than the prestet LLVD Volt, the load will be disconnected, and so is the battery when the battery voltage is lower than the preset BLVD Volt. Select Time, when the discharge time reaches the preset LLVD Time, the monitoring module will disconnect the load; when the discharge time reaches the preset BLVD Time, it will disconnect the battery.

LLVD Time

300min

BLVD Time

3 ~ 1,000 min

600min

46

Charging Management Parameters

47

48

Battery Test Parameters

49

Parameter
Battery test voltage

Range
43.1V ~ 57.9V 45.2V

Default

Value description
The monitoring module can do battery test, and record 10 sets of test data (accessible only through the host). The battery test has to be started manually, then monitoring module will control the rectifier output voltage, make it lower than the battery voltage, and the battery discharge will begin. Monitoring module will stop the test if the battery voltage reaches the Battery test voltage, or the discharge time reaches Battery test time, or the battery capacity reaches Test End Cap. Afterwards, it will restore the rectifier output voltage to the normal FC voltage, begin the battery charge and switch the system to battery auto-management. Meanwhile the test start time/voltage and end time/voltage and battery remaining capacity will be recorded. The records can be queried through the host. During the battery test, if abnormalities occur, the monitoring module will stop the battery test automatically.

Battery test time

5 ~ 1440min

300min

Test End Cap (capacity)

0.01C10 ~ 0.95C10

0.7C10

Scheduled Test Planned Test 1

Y, N

N 00:00, Jan. 1st

Planned Test 2

Month,day,

00:00, April 1st

When the parameter Scheduled Test is set to Y, the monitoring module will test the battery according to the 4 sets of test time. You can set at most 12 sets of test time through the host.

Planned Test 3

hour

00:00, July 1st

Planned Test 4

00:00, Oct. 1st

Alarm Current ShortTest Cycle

1A ~ 100A 24h ~ 8,760h

10A 720h

If the battery have not discharged within the ShortTest Cycle, the monitoring module will start a short test, whose operation time is set by the parameter ShortTest Duration. By the end of the test, if the difference in the discharge currents of batteries is bigger than the Alarm Current, the battery discharge imbalance alarm will be raised. This alarm will automatically end after 5min of delay. Also you can end it by confirming it.

ShortTest Duration

1 ~ 60min

5min

StableTest Enable

Y, N

The stable test is conducted with constant battery current, whose value is set through the parameter StableTest Current. If the parameter StableTest Enable is set to Y, and the test will be started once the battery satisfies the test condition

StableTest Current

0 ~ 9999A

9999A

50

Temperature Compensation Coefficient Parameters

51

AC Settings

Parameter

Range

Default

Value description

The monitoring module will raise an alarm when the AC input voltage is higher than the OverVolt OverVolt 50V ~ 300V 280V

The OverVolt must be higher than the LowVolt. To avoid alrm disorder, it is suggested to use the default values

The monitoring module will raise an alarm when the AC input voltage is lower than the LowVolt. LowVolt 50V ~ 300V 180V

Set this parameter according to the actual situation. In a system with an AC sampling board, you can only select Single Phase or 3-phase; in a system without an AC sampling board, you can select only None.

AC Input

3-phase, Single Phase, None

Dependat on system type

52

DC Settings

Parameter

Range

Default

Value description

Over (over-voltage) 58.5V

The DC Over Voltage alarm will be raised when the system DC output voltage is higher than the value of Over

Low (low-voltage) 40V ~ 60V 45.0V

The DC low voltage alarm will be raised when the system DC output voltage is lower than the value of Low

The values of these three parameters should be: Over > Low > Under

Under (under-voltage) 45.0V

The DC under voltage alarm will be raised when the system DC output voltage is lower than the value of Under

High (high temperature) 10C ~ 100C 40C

The high temperature alarm will be raised when the detected ambient temperature is higher than the value of High

The value of parameter High must be higher than that of parameter Low

Low (low temperature)

-40C ~ 10C

-5C

The low temperature alarm will be raised when the detected ambient temperature is lower than the value of Low

Load shunt

Y, None

None

Set according to the system actual situation In the system with a load shunt, this parameter can be set only when the parameter Shunt (as a system type) is set to Set.

Dependent on system type Shunt Coeff

53

TU IEN AC

54

Dy CB cp ngun

55

Dy CB chng st
Neu qua chong set th 2 CB bat ON, CB th 3 e OFF. Neu khong qua chong set (e chay may no) th 2 CB au e OFF, CB th 3 bat ON

56

S IN AC
TRONG PHOG BTS N

S O THO G IE AC& DC HE N N
1 2 3

OVAG XANH N

E BA PHA N O

O A N P
LI OA 20KVA
1 2 3

CA DAO A U O 3PHA 100A

Gia pha 3

CHO G SE N T
TERCEL

CB 150A
CA DAO A U O

CA DAO A U O

CA DAO A U O

3PHA 60A

3PHA 60A

3PHA 60A

3
1 2 3

3
AC 220V 3 PHA

BTS 2
(HORIZON)

1 N

3 N

2 N

BATTERY
(GNB 265 AH)

BTS 1
(M-CELL)

DC -48V

DC -48V

CB 32A 3 PHA

CB 32A 3 PHA

REC 1

REC 2

REC 3

CB 10A 1 PHA

CB 10A 1 PHA

CB 20A 1 PHA

LORAIN
BTS
DPHOG N Y N M A LA H 1 M A LA H 2 Y N CA H BA N O AC 220V 3 PHA

57