DigitalLineProtection GE DLPD
DigitalLineProtection GE DLPD
Microprocessor Based Protection, Control and Monitoring System Waveform Sampling Proven Protection Economical Ease of Retrofit
Industrial Systems
DLP-D Enhancements
Three Phase & Single Phase Tripping
ASCII SUBSET
DLP-C Repackaged
Proven Design
Industrial Systems
I V
MMI
RECURSIVE FOURIER TRANSFORM PHASOR QUANTITIES EMULATION OF: PHASE ANGLE COMPARATORS, AMPLITUDE COMPARATORS, ETC. MEASURING FUNCTIONS
LOGIC
OUTPUTS
3
Industrial Systems
DLP Application
For Three Phase or Single Phase Tripping on any Uncompensated Transmission Line
Typical Operating Times are 3/4 to 1-1/2 Cycle 6 Protection Schemes
Step Distance Directional Comparison Blocking POTT PUTT Hybrid Zone 1 Extension
Industrial Systems
50
Milliseco nds
Industrial Systems
50
Milliseco nds
Industrial Systems
Settings:
Scheme Selection
STEP POTT PUTT HYBRID BLOCKING (BLK1, BLK2, BLK3) ZONE 1 EXTENSION
Industrial Systems
Measuring Functions
DISTANCE
Zone 1 Zone 2 (Pilot Zone) Zone 3 Zone 4 (Reversible/Blocking)
*Settable Offset
8
MHO MHO*
MHO MHO
Industrial Systems
Measuring Functions
OVERCURRENT (3|I0| - KT|I1|) IPT (3|I0| - KB|I1|) IPB IT IB FD (3|I0| - KD|I1|) IDT (3|I0|) GTOC
DIRECTIONAL NT NB
9
- Pilot Trip - Pilot Block - Trip Supervision - Block Supervision - Fault Detector - Inst. Direct Trip (Directional Control) - Time Overcurrent (Directional Control)
- Trip - Block
Industrial Systems
Inverse
Very Inverse
?
Custom Extremely Inverse
10
Definite Time
Industrial Systems
11
Out-of-Step Blocking PT Fuse Failure Line Pickup (Close Into Fault) Remote Open Detector Line Overload Adaptive Reach (Zone 1 Ground Reactance - Supervising MHO) Current Unbalance Alarm Continuous Monitor Alarm Detects Internal Relay Changes if FD is Not Picked Up Carrier Start Options for Improved Coordination in Blocking Schemes with Other Relays. Trip Bus Check when Settings are Changed
Industrial Systems
Recloser (Optional)
Single breaker reclosing Programmable up to 2 reclose attempts Manual Lockout Panel Switch Additional Inputs
Reclose Initiate, Reclose Inhibit, Reclose Cancel, Reclose Reset
Additional Outputs
Zone 1 Reach Reset, Lockout Alarm, Reclose in Progress
12
Industrial Systems
Industrial Systems
Industrial Systems
Configurable Inputs
(1701)
CONCCI SELECT SETTINGS GROUP DEFAULT
0 1 2 3 4 5 6
CC4
RECEIVER 2 EXTERNAL TRIGGER CONFIG. INPUT 1 RECEIVER 2 EXTERNAL TRIGGER CONFIG. INPUT 1 RECEIVER 2 EXTERNAL TRIGGER CONFIG. INPUT 1
CC5
SELECT GROUP BIT 1 SELECT GROUP BIT 1 SELECT GROUP BIT 1 STOP CARRIER STOP CARRIER STOP CARRIER CONFIG. INPUT 2 CONFIG. INPUT 2 CONFIG. INPUT 2
CC6
SELECT GROUP BIT 0 SELECT GROUP BIT 0 SELECT GROUP BIT 0 BLOCK PILOT TRIP BLOCK PILOT TRIP BLOCK PILOT TRIP CONFIG. INPUT 3 CONFIG. INPUT 3 CONFIG. INPUT 3
USER INPUT
7 8
15
Industrial Systems
CC6
0 1 0 1
Settings Group G1 G2 G3 G4
16SB1______ G3 X G2 G1
SETTINGS GROUP
G1 G4 G3
16
+ G2 SG 3
CC5
(bit 1)
+ -
CC6
(bit 0)
Industrial Systems
6 6 2 2 1 1 1 1 5
2 2 1 1 1
Industrial Systems
2 2 2 1 5
1
2
2 2 1 1 1
Industrial Systems
Configurable Outputs
EXAMPLE: Configure the BC-1 Output to Close when Zone 1 BG, GRD DIR TRIP, and CONF. INPUT 1 are ON and CONF. INPUT 3 is OFF.
(1801) (1802) (1803) (1804) (1805) (1806) CONOUT 1 CO1 IN1 CO1 IN2 CO1 IN3 CO1 IN4 CO1 IN5 . . CO1 IN8 = = = = = = . . = 2 (AND gate) 2 (Z1BG) 35 (GRD DIR TRIP) 50 (CONF. INPUT 1) 152 (NOT of CONF. INPUT 3) 0
(1809)
19
Industrial Systems
Provides Analog Output Proportional to Distance to Fault Location in 0 to 1mA DC or 0 to 5 Vdc Output (Selectable) Four (4) Contact Outputs Provide Fault Type Example:
A B C G Phase A to Neutral Fault Indication
20
Industrial Systems
TRIP
AB
Z1
44
21
Industrial Systems
22
Industrial Systems
Communications
23
Industrial Systems
Communications
[-] Relay Functions Login Logout Change access level Hang up phone Actions . . . Information . . . Settings . . . DLP COMMUNICATIONS 2.80 Local Functions Setup Help
Remote Access
Via RS232 & DLP-LINK Software Front and Rear RS232 Ports 3 Level Password Protection
Access to:
Present Values Fault Report Sequence of Events Oscillography Manual Breaker Control Relay Settings
Phone disconnected
24
Industrial Systems
STATION: MALVERN LINE: LINE 1 UNIT ID: 0 DATE: 08/24/96 TIME: 10:57:51 MODEL NUMBER: DLP3512CDH PROM VERSION NUMBER: V002.320B
INFORMATION ONLY
25
Industrial Systems
Fault Report
Sample DLP FAULT REPORT Station ID: PLACE TRANSMISSION Line ID: CREEK 115KV OCB 5512 TRIP DATE: 09/11/95 FAULT TYPE: AB TRIP TYPE: Z4 TRIP TIME: 15:16:10.295 DISTANCE: **** MILES OPERATING TIME: 01496 5512
Prefault
Currents Voltages
Post Fault
Currents Voltages Trip Targets Operating Time
FAULT Ia: 057.60 A Ib: 048.00 A Ic: 050.40 A In: 014.40 A Va: 066.0 KV Vb: 066.0 KV Vc: 066.1 KV
Selected Events
15:16:10.295 TRIP SIGNALS ON 15:16:12.119 TRIP SIGNALS RESET 15:16:12.119 TRIP CIRCUIT #1 NOT ENERGIZED
26
Industrial Systems
Present Values
Sample DLP PRESENT VALUES Station ID: CREEK TRANSMISSION Line ID: 115KV OCB 5072
09/18/95 14:23:44.455
IA: 001.16 A IB: 001.26 A IC: 001.26 A -001 DEGS 119 DEGS -119 DEGS IN: 000.03 A VA: 066.3 V VB: 066.3 V VC: 066.3 V **** DEGS 000 DEGS 121 DEGS -119 DEGS
WATTS: 056.6 MW BREAKER 1: CLOSED PLC #1 SIGNAL: OFF PLC #1 STATUS: N/A
VARS: 003.1 MVAR BREAKER 2: N/A PLC #2 SIGNAL: OFF PLC #2 STATUS: N/A
Currents Voltages Angles Watts Vars Breaker Status Carrier Status Active Setting Group
STOP CARRIER: OFF SETTING GROUP NUMBER: 1 BLOCK PILOT TRIP: OFF
27
Industrial Systems
Sequence of Events
Sample DLP Events Station ID: CREEK TRANSMISSION Line ID: 115KV OCB 5072
Operational Events
Setting Changes Fault Data Status
07/25/95 19:06:21.121 TRIP SIGNALS RESET 07/25/95 19:06:21.121 TRIP CIRCUIT #1 NOT ENERGIZED 07/25/95 19:06:21.048 TRIP SIGNALS ON 07/25/95 19:06:21.038 OSC TRIGGER 05/31/95 12:16:42.091 TRIP CIRCUIT #1 MONITOR ALARM ON 05/31/95 12:16:41.915 TRIP CIRCUIT #1 MONITOR ALARM ON 05/31/95 12:16:41.879 REMOTE COMM - SETTINGS CHANGE DONE 05/31/95 12:16:30.720 REMOTE COMM - SETTINGS CHANGE STARTED 05/31/95 12:13:48.392 REMOTE COMM - PASSWORD CHANGED 05/31/95 12:11:53.383 REMOTE COMM - PASSWORD CHANGED 05/31/95 12:10:37.847 UNBALANCED SYSTEM DETECTION ALARM ON 05/31/95 12:10:29.930 REMOTE COMM - PASSWORD CHANGED 05/31/95 12:09:35.302 FUSE FAILURE ALARM ON 05/31/95 12:09:35.175 LOCAL - SETTINGS CHANGE DONE 05/31/95 12:09:30.826 LOCAL - SETTINGS CHANGE STARTED 05/31/95 12:07:22.109 UNBALANCED SYSTEM DETECTION ALARM ON 05/31/95 12:06:00.042 FUSE FAILURE ALARM ON 05/31/95 12:06:00.000 SSP BOARD: QUEUES REINITIALIZED 05/31/95 12:05:30.210 FAIL - TRIP BUS CHECK 05/31/95 12:05:30.177 FUSE FAILURE ALARM ON
28
Industrial Systems
Oscillography Triggers
None Fault Detector Any Zone 2 Any Zone 3 Any Zone 4 Out-of-Step V1 Detector External Contact Input
29
Industrial Systems
Stored Cycles 72 36 18 9
Pre-fault Cycles Selectable from 1 to 8 Settings and Fault Report are stored with Oscillography Data
30
Industrial Systems
Oscillography Data
Internal and External Oscillography Triggering ASCII File Format (Readable by EXCEL/LOTUS/DL-DATA) For Each Sample
4 Currents (IA, IB, IC, IN) 3 Voltages (VA, VB, VC) 6 Flag Groups
Digital Inputs Outputs Phase Zone Flags Breaker Status and Gnd. Zone Flags Protection Logical Input Flags Output Status of Protection Timers
31
Industrial Systems
32
Industrial Systems
Draw-Out Modular Construction with Removable Door Front Panel Power Switch Information Access
MMI RS232 Front & Rear (GE Modem) RS232 Rear (ASCII)
Target Clearing Through Door Optional Mounting Flanges for L2 and KD cutouts and Moveable Mounting Brackets Self-Test Diagnostics
Critical Alarm Non-Critical Alarm
33
Industrial Systems
34
Industrial Systems
* *