Procontrol p13/42
Procontrol p13/42
Date: 14/03/2012
Liji P C&I
A common misconception in process control is that it is all about the controller that you can force a particular process response just by getting the right tuning parameters. In reality, the controller is just a partner. A process will respond to a controllers commands only in the manner which it can. To understand process control you must understand the other partners as well: sensors, final control elements and the process itself. All of these determine what type of response the controller is capable of extracting out of the process. It is not the other way around.
Objectives:
Why do we need process control? What is a process? What is process control? What is open loop control? What is closed loop control? What are the modes of closed loop control? What are the basic elements of process control?
Operational Objectives
1. 2. 3. 4. 5.
Confidential
Slide 4
HIERARCHY OF CONTROL
High
Unit Level
DEGREE OF AUTOMATION
Particular Process
Function group Level SUB GROUP LEVEL Sub loop Control Sub loop Control Sub loop Control
Individual Equipment and drives
PROCESS
Slide
Confidential
Components of DDCMIS
MAN MACHINE INTERFACE & PROCESS INFORMATION SYSTEM
( DATA HIGHWAY)
CONTROL SYSTEM
Confidential
Slide 6
Architecture
Confidential
Slide 7
Main Characteristics
Confidential
Slide
Components of DDCMIS
Functional Division
S&G - C&I system T&G - C&I system BOP - C&I system
Hardware Components
Confidential
Slide
Data Transmission
Confidential
Slide
Confidential
Slide 11
Local Bus
Heart of the station and connects to all modules in the station Features
Transmission reliability
Parity check, cyclic transmission, data valency , clock signal
Redundancy Time cycle : 40ms Type of modulation : Pulse modulation No of addresses : 256
Confidential
Slide 12
Local Bus..
Confidential
Slide 13
Local Bus..
Confidential
Slide 14
Local Bus..
Confidential
Slide 15
Local Bus..
Confidential
Slide 16
Link all station with local bus, process computer with diagnostic station with redundant line Features
Transmission reliability
Parity check, Amplitude tolerance check ,Redundancy
Time cycle : 40ms Type of modulation : Digital Pulse Width modulation No of addresses : 256 x No of stations (63) Amplitude: 15 v Transmission medium: Coaxial cable
Confidential
Slide 17
Confidential
Slide 18
Confidential
Slide 19
Confidential
Slide 20
Confidential
Slide 21
Type
BV01 FA01
Application
Local bus traffic director
Description
transfer of data signals into the IPB cable and for transfer of address and data signals from the IPB cable in to local bus stations
Contains FA01 modules
FK01
Confidential
Slide 22
Confidential
Slide 23
INPUT MODULES
OUTPUT MODULES
CONTROLLER MODULES
INTERFACE
. BK02 . XV7713 ANALOG . EA01 . EA02 . EA03 . EA04 BINARY . EB01 . EB02 . EB03 . EB10 ANALOG . AA01 . AA02 BINARY .AB01 .AB02 TRA . DIRS . XV7715 PROCS . PR03 . PR05 . XV7717 . XV7718 . FA01 . BK03 . BA01 ANALOG . AS06 BINARY .AS04
DRIVE MODULES
POWER SUPPLY
. XT382 . XT383 .XT370
Confidential
Slide
Control Modules
Confidential
Slide
Control Module..
Confidential
Slide 26
Control Module..
Confidential
Slide 27
Confidential
Slide
1 A
3 F
2 A
EB
EA
AA
AB
PR
Confidential
Slide
Processor Module..
Type
PR05
Application
Description
4 channel 2 code sw for address setting 4 channel 2 code sw for address setting Short circuit proof supply to contacts
Confidential
Slide 30
IO Modules
Mounted on local bus Both normal and reverse data Functions Power to transmitter/switches
Signal Veriication power, Zero/Span Digitalization 10 bit data,sign,disturbance Address allocation Serial/Pareellel Conversion
-
Confidential
Slide
Address allocation
Confidential
Slide
IO Modules
Power for transmitters and transducers Signal verification Digitalization Address allocation Serial / Parallel conversation Process interface
Confidential
Slide
I/O Modules..
Application
0 - 20 mA or 0 - 10 VDC
Description
4 channel 2 code sw for address setting Selection of input via jumpers.*
4 channel 2 code sw for address setting 16- 24vDC supply for txr.* RTD(Pt 100) 4 channel 2 code sw for address setting Linearisation for measurement.* Thermoelectric voltages Correction with coldjunction temperture 8 channel 2 code sw for address setting Linearisation for measurement.*
Slide 34
EA02
4 20 mA
EA03
Temperature measurement
EA04
Temperature measurement
Confidential
I/O Modules..
Application
24vdc binary signal Conversion of 0/24v to local bus signal
Interrogation voltage of 48vdc Conversion of 0/24v to local bus signal Module for supervised contact Five double throw contact No effect on earth fault
Description
16 channel 2 code sw for address setting
16 channel 2 code sw for address setting Short circuit proof supply to contacts 5 channel 2 code sw for address setting Linearisation for measurement Short circuit proof supply to contacts *
EB02
EB03
Confidential
Slide 35
I/O Modules..
Type
AA01 AA02
Application
Voltages 10Vdc For 0- 20 mA
Description
4 channel 2 code sw for address setting 4 channel 2 code sw for address setting Short circuit proof supply to contacts
Confidential
Slide 36
I/O Modules..
Type
AB01 AB02
Application
Description
16 channel 2 code sw for address setting
Interrogation voltage of 48vdc Conversion of digital local bus signal into output with potential free contacts
Confidential
Slide 37
SOFTWARE
for processor
-
Functional diagrams
Confidential
Slide
MMI
Confidential
Slide
WSPOSE
Client server architecture Residing on P42 bus Engineering station and operator ws WSPOSE panel VME(Versa module Europa) Cage CPU and interface cards Signal conditioning ,processing and filtering
Confidential
Slide
VME Cage
2 way communication b/w server and IPB redundant RT20 CPU Compatible with VME bus GBNIC Ethernet controller RT20 CPU (bnc ) and server PCIF
Confidential
Slide
CPU RT20 is designed using Motorola M68020 microprocessor .Power Rewuirement : +5VDC @2.5A, +12 VDC @200 MA, -12V DC @200MA RT 20 has 6 front panel LEDs. RUN Illuminated Green always on during running HALT- When halt condition initiated from process. OFF in healthy condition. VME ( YELLOW) Illuminated when RT20 acesses any resources. Continuous flashing in healthy conditions. BLO(RED) is illuminated when Battery voltage is low.OFF during healthy condition AP1,AP2 (GREEN YELLOW) -User application LEDs .Off during healthy condition
Confidential
Slide
GBINC
COMMUNICATION MODULE ,2 SEPARATE ETHERNET CABLE IS CONNECTED TO SERVER 1 &2 . Rx/Tx( RED) ILLUMINATES WHEN RECEIVES OR SEND DATA. CONTINOUS FLASHING IN HEALTHY CONDITION STATUS LED 1 &2 GLOWS WHEN PROCESSOR HALTS AT ANY TIME. OFF DURING HEALTHY CONDITION SYS FAIL INDICATION DURING SYSTEM FAILURE . NORMALLY OFF
Confidential
Slide
Function: Data Processing and broadcast the process data on ehthernet to MMI and send them on P42 P42 Bus is a coaxial cable connected to acess coupler FA.This acess coupler is connector in Buscoupler . Each PCIF acts as a local station on IPB. PCIF (Processor Control Interface Controller) interfaces VME bus and P42 bus controller The 70CK01 Module connects P42 bus and PCIF.The modules PCIF and 70CK01 are interconnected. 70CK01 is connected to coupler FA01 of Intraplant bus by means of two 8 line connecting cables
Slide
Confidential
Small window in the top right corner of OPTASK indicate the status.The user name, MW,frequency and status of server indicated in the window. Green : Server 1 Active, Yellow : server 2 active Red :. Lone active Server status is indicated as Active ,Standby , Lone active : This will come when one server is active or communication between the servers are lost. WSPOSE System will act as two local stations in the IPB with 02 and 03 as address. The address selection mis made through PCIF.
Confidential
Slide
REDUNDANCY LOGIC
Failure of one server, network link,operator station will not affect operation. Both servers operate in parallel.Active server collects data from IPB and transmits the same to operator work station and LAN. Standby server collects data from IPB but refrain from sending it to LAN.Standby server accepts all data from Active server and operator workstations. Both servers exchange messages in every 500ms. When there is a break the other server will take up. Server will go bad if communication failures from the VME or any data transfer error from IPB. Control commands can be issued through FKB or mouse .Any drive can be operated from any workstation . Each work station is operating separately . Failure of one work station will not affect the other system. In the Procontrol system ID signals are ORed for final controls,hence control operations proceed unhindered even if one server fails
Slide
Confidential
5 numbers of FKB are available to receive signals from the OWS to WSPOSE systems. Each FKB. Each one has 4 connectors at the back. J1 connector is the serial portion and P4,P5,P6 connectors are parallel portion of FKB.Serial Portion is connected to serial port of OWS .One end of 32 Pair cable with D-37Pin connector is connected to FKB port and EB01 modules of the Procontrol Panel.
Confidential
Slide
Thank You..
Confidential
Slide
APPENDIX
Confidential
Slide
Serial Communication
Serial Communication is the process of sending data one bit at a time, sequentially, over a communication channel or computer bus. This is in contrast to parallel communication, where several bits are sent as a whole, on a link with several parallel channels Designer :Compaq, DEC, IBM, Intel, Microsoft, NEC and Nortel Designed :1994 Manufacturer: Intel, Compaq, Microsoft, NEC, Digital Equipment Corporation, IBM, Nortel Signal : 5 volt DC Max. voltage: 5 V(5%) Max. current :500900 mA @ 5 V (depending on version) Data signal: Packet data, defined by specifications Width: 1 bit Bitrate : 1.5/12/480/5,000 Mbit/s (depending on version) Max. devices :127 Protocol :Serial
Confidential
Slide
Servers are powerful computers or processes dedicated to managing disk drives (file servers), printers (print servers), or network traffic (network servers ). Clients are PCs or workstations on which users run applications. Clients rely on servers for resources, such as files, devices, and even processing power. File and Network security Increased reliability; decreased workflow interruptions Centralized data storage and shared resources
Centralized Backup
Confidential
Slide
VME Bus
Confidential
Slide
Thank you
Confidential
Slide
Confidential
Slide
TURBINE PROTECTION
The turbine Protection System can be actuated by any of the following trip system.
Both the trip system when initiated act on the hydraulic control system and cause trip oil pressure to collapse which in turn closes the emergency stop valves & control valves
Confidential
Slide
A pressure switch sensing the low pressure condition of the hydraulic fluid or limit switches sensing the closed position of the stop valves is usually used as a verification that the turbine has tripped.
Confidential
Slide
TURBINE TRIP
All HRSG Trip Emergency turbine trip Turbine speed >3300 rpm
>1
B
C
Confidential
Slide
TURBINE TRIP
Axial Displacement Axial Displacement
>1
>1
GCB closed Gen class A trip
& >1
Confidential
Slide
TURBINE TRIP
Trip oil Pressure Very Low Lube Oil Pressure Very Low MOT Level Turb Exht Pr Very High
2/3 Logic 2/3 Logic
2/3 Logic
2/3 Logic
>1
2/3 Logic
2/3 Logic
Confidential
Slide
>1
Confidential
Slide
>1
SHAFT V V.HIGH
>1
SHAFT V V.HIGH
HOUSING V V.HIGH
>1
Confidential
Slide