3500 Engine Monitoring System
3500 Engine Monitoring System
3500 engines
ECM monitors parameters and Initiate an action if a specific operating parameter extends outside an acceptable range
ECM actions
Warning. Derate . Shutdown.
ET
Used to select desired action available for ECM. Used to program monitoring level. Used to program delay time for each action.
Histogram
Displayed by the ET to show the trend of performance for the engine. Available for speed, load, lh exhaust temperature and rh exhaust temperature.
Provide indication when the engine control is shutting down the engine i.e. relay is deenergized.
Relay is de-energized if :Engine is shut down by programmable monitoring system Remote emergency stop switch is activated The customer communication module (CCM) requested a normal shutdown. CCM request an emergency stop shutdown.
Engine is shutdown by over speed verify feature. Engine is in the off or stop state. Personality module inter lock occurs. Speeds drop below crank terminate speed.
ECM hours increment adjustment :Adjusting the hour meter of ECM. Allow the new ECM to be programmed to display the correct no. of operating hours. Allows only increment changes. Need a password.
ECM voltage
Voltage monitoring
Parameter Warning setpoint Warning delay Hysteresis Security level Default setting 20 volts
10 seconds
2 volts No required password