Psychrometric Chart
DBT
Specific Humidity
WBT
RH ()
W
V
Psychrometric Processes
Sensible Cooling- 1
Cooling Coil
Qc ma cp a Ta ma h
Sensible Heating- 2
Heating Coil
Qc ma cp a Ta ma h
Example
Calculate the load on the heating coil used for heating 1.5 m3/s of moist air at
DBT= 21 oC, WBT=15 oC by 20 oC. If the water is working fluid that enters the
coil at 85 oC, and leaves at 75 oC. Calculate the mass flow rate of the water.
3- Evaporative Cooling
Example
1.5 m3 of air at DBT=45 oC, WBT=31 oC, passes through an air washer, if the
Saturation efficiency is 90%, Calculate:
a) The exit condition of air.
b) The quantity of the make-up water
Solution
From Chart
Steam Injection
Example
Solution
The ratio AB/ADP is known as the coil contact factor or coil efficiency
AB
TA TB
CF
A ADP TA ADP
EXAMPLE
Adiabatic Mixing
In most cases, the outdoor fresh air is mixed with the re-circulated air comes
from the conditioned in air handling unit (AHU), this process is carried out
adiabatically so the AHU must be insulated well to prevent the heat loss. The
following figure shows two streams of air of masses m1 at condition (1) and m2
at condition (2) and resulted mixture has the mass m3 at condition (3)
Example
Moist air stream at DBT=60 oC, WBT=32 oC is mixed adiabatically with another moist
air stream at DBT=5 oC, WBT=0.5 oC. If the masses of dry air in both streams are 3 kg
, 2 kg respectively. Find the enthalpy, specific humidity, and dry bulb temperature of air
mixture.
Solution
Example
1m3/s of outdoor moist air at DBT= -1 oC, 100%; RH is mixed with 2 m3/s
of recirculated air at DBT= 22 oC, 50% RH. Draw the process on the
psychrometric chart and find the mixing point by calculations and then find
the properties (RH,w,h,v) of the mixing point.
Solution