Bubbler System
A bubbler system in an inexpensive
yet accurate way to measure the fluid
level in open or vented containers. A
complete bubbler level measurement
system consists of a source of
compressed air, an air flow restrictor,
sensing tube, and pressure
transmitter.

Closed tank application for


bubbler system
If the bubbler system is to be applied to measure level in a closed tank, some
pressure-regulating scheme must be provided for the gas space in the tank.
Otherwise, the gas bubbling through the liquid will pressurize the gas space to a point
where bubbler supply pressure cannot overcome the static pressure it acts against.
The result would be no bubble flow and, therefore, inaccurate measurement signal.
Also, as in the case of a closed tank inferential level measurement system, the lowpressure side of the level transmitter has to be connected to the gas space in order to
compensate for the effect of gas pressure.

If the bubbler system is to be applied to measure level


in a closed tank, some pressure- regulating scheme
must be provided for the gas space in the tank.
Otherwise, the gas bubbling through the liquid will
pressurize the gas space to a point where bubbler
supply pressure cannot overcome the static pressure it
acts against. The result would be no bubble flow and
therefore, inaccurate measurement signal. Also as in
the case of a closed tank inferential level measurement
system, the low pressure side of the level transmitter
has to be connected to the gas space in order to
compensate for the effect of gas pressure.