Professional Documents
Culture Documents
Intelligent Control of Series FACTS Devices
Intelligent Control of Series FACTS Devices
Intelligent Control of Series FACTS Devices
Devices
Weakly damped power swings result
In unsecure power system operation.
Improvement of damping is done
By power system stabilizer(PSS )
Or Flexible alternating current transmission
devices(FACTS)
Former improves damping by generator excitation
control
Latter by modulating the equivalent
Power angle characteristics of the system
of secondary control
Proper control algorithm and parameter selection at
regulator of series facts device
Leads to stable control of frequency and tie line
interchange process
Above process will be discussed with the help of thyristor
controlled phase angle regulator(TCPAR)
TCPAR acts as a fast phase shifting transformer from
power system view point
Thyristor tap changer can neither generate nor absorb
reactive power.
AC voltage source supplies or absorbs the requisite
reactive power in case of TCPAR
+
+
Supplementary
control
TCPAR
OPTIMAL CONTROL
LIMITATIONS
Standard optimal control uses a linearized model
Valid only for a given operating point
Robustness of such system is limited within this
range
Control based on linearized system model is in
question
When system operating conditions change
Due to line or generator outages.
Moreover stressed power systems are known to
exhibit nonlinear behaviour.
Contd
The state trajectories converge to a point in state space
called the equilibrium point
At this point no states vary with time
If for any constant input vector u(t)=
There exists x(t)= Constant in state space
Such that (t)=0 for all t, then this point
Is called an equilibrium point
Corresponding to input
f(,t)=0 for all t.
The number of solutions depends entirely
on the nature of f(.) and no general statement is
possible
Contd
Free
response of system is said to be stable
of energy.
CONTD
V()=+
V(x)>0 when x0
V(0)=0
This means that the total energy is positive
Unless the system is at rest at the equilibrium
point =0
Where the energy is zero
The rate of change of energy is given by
()=)= + = -B
(b)
(c)
(d)
(d)
FIG 1.3 Stages of developing an incremental model of a transmission line with a phase
shifting transformer
(a) one-line diagram ;(b) admittance model with transmission ratio;(c) incremental
model; (d) phasor diagram
Contd
Fig
1.3 illustrates the stages of developing
A model of a phase shifting transformer
Installed in a tie line
A booster voltage which is in quadrature with
supply
Is injected in the transmission line using a booster
transformer.
=
Where is the controlled variable
Contd
=sin
+cos
Contd
The
tie line flow depends on both the power angle
Also on the quadrature transformation ratio (t)
Taking into account in the vicinity of operating
point
=|= + |now we have
= ( c) - ( c)
From above equations we have
sin= c
Also sin= c
BY back substitution we have
CONTD
=[(1+)(
c) + ]- ( c)
Contd
It
results to = -
This describes the incremental model of the
transmission line
There is an equivalent transmission line between
nodes a&b
A change in the flow in that line corresponds to
The change in voltage angles at both sides
Nodal power injection corresponds to regulation
Of the quadrature transformation ratio (t).
The power injections in nodes a and b are + a
(t)
..
.
network
(a)
-
-+
(b)
(c)
In
analyzing system frequency regulation
Changes in voltage magnitude can be neglected
We have P=H
Where P and are the vectors
Of the real power injections and voltage angles
Matrix H is the Jacobi matrix
It consists of partial derivatives
This equation describes the incremental model of
system
Including a phase shifting transformer in
incremental model
There
are the following node types:
=0
because loads are modelled as constant
powers
By partial inversion eliminating variables related
to nodes L
=
Further it can be transferred by partial inversion
= +
EQN 1
= - + EQN 2
Where
+
Where = Coefficients , can be treated as measures
Of distances from the nodes a and b to the ith generator
The swing equation describing increments in rotor
angles
- -D
For I {G} .As the network equations are derived in matrix form.
M= - -D
Where M and D are diagonal matrices of inertia and
damping coefficients
, and are column matrices of changes in rotor angles,
rotor speed deviations and real power generations.
By back substitution we have
M=- - EQN 3
Here is the control function corresponding
To the transformation ratio change of phase shifting
transformer
affects rotor motions proportional to the
Main
question is how should be changed
We
have v(x +x)= v(x) +(gradv) + x
Where H= is the hessian matrix
V=V(X +x)- v(x)= x=
For the potential energy HESSIAN MATRIX
Corresponds to the gradient of real power
generations
Therefore also forms the Jacobi matrix of form
==
Above
equations leads to
= also
= M
This is quadratic form made up of vector of speed
changes and a diagonal matrix of inertia
coefficients .
Total energy increment V= +
V= M +
This function is a lyapunov function since being a
positive definite
Provided
its time derivative is negative definite
== +
=M +M
Now it is useful to transpose eqn 3
M = - - D - eq 4
Substituting eqn 4 in right hand side of
Adding eq 4 and
We have = + =- -(t)
As matrix d is positive definite the function above
is negative definite
When
(t)=k forms the control law
With
this control law the lyapunov function
+
+}
following a disturbance in one of the subsystems.
There are local swings of generator rotor inside
each subsystem.
Also inter area swings of subsystems with respect
to each other
The frequency of local swings is about 1Hz
While the frequency of inter area swings
Is much lower usually about 0.25hz.
While investigating the interarea swings
The local swings can be neglected.