VOLTAGE DROP
IDENTIFY VOLTAGE
DROP CALCULATION
FROM TNB SUBSTATION
TO FEEDER PILLAR
TNB
SUBSTATION
FEEDER
PILLAR
TNB 800m
SUBSTATION
FEEDER
PILLAR
(FP)
4C XLPE / SWA / PVC
1 x 185mm2 /
TNB 800m
SUBSTATION
FEEDER
PILLAR
(FP)
4C XLPE / SWA / PVC
1 x 185mm2 /
Voltage Drop, Vd
IDENTIFY VOLTAGE
DROP CALCULATION
FROM FEEDER PILLAR
TO STREET LIGHTING
45
m
45
m
FEEDER
PILLAR
(FP)
R11
45
m
Y11
45
m
R12
45
m
Y12
45
m
45
m
45
m
R13
R14
45
Y1- m
3
Y14
R15
45
m
Y15
45
m
45
m
R11
FEEDER
PILLAR
45
m
Y11
45
m
R12
45
m
Y12
45
m
45
m
45
m
R13
R14
45
Y1- m
3
Y14
R15
45
m
Y15
45
m
45
m
R11
FEEDER
PILLAR
45
m
Y11
45
m
R12
45
m
Y12
45
m
45
m
45
m
R13
R14
45
Y1- m
3
Y14
R15
45
m
Y15
Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
IRI-1
R1-1
=
10 X
436
229.31 X
= 0.85
22.36A
V
d
= 22.36 X 45 X
2.80
1000
=
2.83V
Vd at R1-1
= 229.31
2.83
=
226.54
45
m
45
m
R11
FEEDER
PILLAR
45
m
Y11
45
m
R12
45
m
Y12
45
m
45
m
45
m
R13
R14
45
Y1- m
3
Y14
R15
45
m
Y15
Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
IRI-2
R1-2
=
8X 436
226.54X
0.85
=
18.11A
V
d
= 18.11 X 45 X
2.80
1000
=
2.28V
Vd at R1-2
= 226.54
2.28
=
224.26V
45
m
45
m
R11
FEEDER
PILLAR
45
m
6X 436
224.26 X
0.85
=
13.72A
R12
45
m
Y12
45
m
45
m
45
m
R13
R14
45
Y1- m
3
Y14
R15
45
m
Y15
Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
R1-3
IRI-3 =
Y11
45
m
V
d
= 13.72 X 45 X
2.80
1000
=
1.73V
Vd at R1-3
= 224.26
1.73
=
222.53V
45
m
45
m
R11
FEEDER
PILLAR
45
m
R12
45
m
Y12
45
m
45
m
45
m
R13
R14
45
Y1- m
3
Y14
R15
45
m
Y15
Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
R1-4
IRI-4 R1-3
=
4X 436
222.53 X
0.85
=
9.22A
Y11
45
m
V
d
= 9.22 X 45 X
2.80
1000
=
1.16V
Vd at R1-4
= 222.53
1.16
=
221.37V
45
m
45
m
R11
FEEDER
PILLAR
45
m
R12
45
m
Y12
45
m
45
m
45
m
R13
R14
45
Y1- m
3
Y14
R15
45
m
Y15
Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
R1-5
IRI-5 R1-3
=
2X 436
221.37 X
0.85
=
4.63A
Y11
45
m
V
d
= 4.63 X 45 X
2.80
1000
=
0.58V
Vd at R1-5
= 230.34
0.56
=
220.79V
45
m
45
m
R11
FEEDER
PILLAR
45
m
Y11
45
m
R12
45
m
Y12
45
m
45
m
45
m
R13
R14
45
Y1- m
3
Y14
R15
45
m
Y15
Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
IYI-1
Y1-1
= 10 X 436
229.31 X
0.85
=
22.36A
V
d
= 22.36 X 45 X
2.80
1000
=
2.83V
Vd at Y1-1
= 229.31
2.83
=
226.54
45
m
45
m
R11
FEEDER
PILLAR
45
m
Y11
45
m
R12
45
m
Y12
45
m
45
m
45
m
R13
R14
45
Y1- m
3
Y14
R15
45
m
Y15
Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
IYI-2
Y1-2
= 8X 436
226.54X
0.85
=
18.11A
V
d
= 18.11 X 45 X
2.80
1000
=
2.28V
Vd at Y1-2
= 226.54
2.28
=
224.26V
45
m
45
m
R11
FEEDER
PILLAR
45
m
R12
45
m
Y12
45
m
45
m
45
m
R13
R14
45
Y1- m
3
Y14
R15
45
m
Y15
Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
Y1-3
IYI-3 = 6X 436
224.26 X
0.85
=
13.72A
Y11
45
m
V
d
= 13.72 X 45 X
2.80
1000
=
1.73V
Vd at Y1-3
= 224.26
1.73
=
222.53V
45
m
45
m
R11
FEEDER
PILLAR
45
m
R12
45
m
Y12
45
m
45
m
45
m
R13
R14
45
Y1- m
3
Y14
R15
45
m
Y15
Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
Y1-4
IYI-4 R1-3
= 4X 436
222.53 X
0.85
=
9.22A
Y11
45
m
V
d
= 9.22 X 45 X
2.80
1000
=
1.16V
Vd at Y1-4
= 222.53
1.16
=
221.37V
45
m
45
m
R11
FEEDER
PILLAR
45
m
R12
45
m
Y12
45
m
45
m
45
m
R13
R14
45
Y1- m
3
Y14
R15
45
m
Y15
Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
Y1-5
IYI-5 R1-3
= 2X 436
221.37 X
0.85
=
4.63A
Y11
45
m
V
d
= 4.63 X 45 X
2.80
1000
=
0.58V
Vd at Y1-5
= 230.34
0.56
=
220.79V
QUESTION
Q1: Refer to table 4D4B. What is the
voltage drop for cable 25mm2?
A1: 1.50mV/A/m
Q2: Refer to table 4E4B. What is the
voltage drop for cable 70mm2?
A2: 0.60mV/A/m