Introduction To Voltage Drop

You might also like

Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 19

INTRODUCTION TO

VOLTAGE DROP

IDENTIFY VOLTAGE
DROP CALCULATION
FROM TNB SUBSTATION
TO FEEDER PILLAR
TNB
SUBSTATION

FEEDER
PILLAR

TNB 800m
SUBSTATION

FEEDER
PILLAR
(FP)
4C XLPE / SWA / PVC

1 x 185mm2 /

(TCL= 8kW , 13.58 A, 3 PHASE)

Refer Table 4E4B


Vd for 1 x 185mm2 /4C XLPE / SWA / PVC
= 0.26mV / A / m

TNB 800m
SUBSTATION

FEEDER
PILLAR
(FP)
4C XLPE / SWA / PVC

1 x 185mm2 /

(TCL= 8kW , 13.58 A, 3 PHASE)

Voltage Drop, Vd

=0.26 x 13.58 x 800 =


2.82V
1000
Voltage Phase at FP = 400V 2.82V = 229.31V
3

IDENTIFY VOLTAGE
DROP CALCULATION
FROM FEEDER PILLAR
TO STREET LIGHTING
45
m

45
m

FEEDER
PILLAR
(FP)

R11
45
m

Y11

45
m
R12

45
m

Y12

45
m

45
m

45
m

R13

R14

45
Y1- m
3

Y14

R15
45
m

Y15

45
m

45
m
R11

FEEDER
PILLAR
45
m

Y11

45
m
R12

45
m

Y12

45
m

45
m

45
m

R13

R14

45
Y1- m
3

Y14

R15
45
m

Y15

1 x 16mm2 /2C PVC / SWA / PVC


Refer Table 4D4B
Vd for 1 x 16mm2 / 2C PVC/ SWA / PVC = 2.80mV / A / m
Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)

45
m

45
m
R11

FEEDER
PILLAR
45
m

Y11

45
m
R12

45
m

Y12

45
m

45
m

45
m

R13

R14

45
Y1- m
3

Y14

R15
45
m

Y15

Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
IRI-1

R1-1
=
10 X
436
229.31 X
= 0.85

22.36A

V
d

= 22.36 X 45 X
2.80
1000
=
2.83V

Vd at R1-1

= 229.31
2.83
=
226.54

45
m

45
m
R11

FEEDER
PILLAR
45
m

Y11

45
m
R12

45
m

Y12

45
m

45
m

45
m

R13

R14

45
Y1- m
3

Y14

R15
45
m

Y15

Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
IRI-2

R1-2
=
8X 436
226.54X
0.85
=
18.11A

V
d

= 18.11 X 45 X
2.80
1000
=
2.28V

Vd at R1-2

= 226.54
2.28
=
224.26V

45
m

45
m
R11

FEEDER
PILLAR
45
m

6X 436
224.26 X
0.85

=
13.72A

R12
45
m

Y12

45
m

45
m

45
m

R13

R14

45
Y1- m
3

Y14

R15
45
m

Y15

Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)

R1-3
IRI-3 =

Y11

45
m

V
d

= 13.72 X 45 X
2.80
1000
=
1.73V

Vd at R1-3

= 224.26
1.73
=
222.53V

45
m

45
m
R11

FEEDER
PILLAR
45
m

R12
45
m

Y12

45
m

45
m

45
m

R13

R14

45
Y1- m
3

Y14

R15
45
m

Y15

Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)

R1-4
IRI-4 R1-3
=
4X 436
222.53 X
0.85
=
9.22A

Y11

45
m

V
d

= 9.22 X 45 X
2.80
1000
=
1.16V

Vd at R1-4

= 222.53
1.16
=
221.37V

45
m

45
m
R11

FEEDER
PILLAR
45
m

R12
45
m

Y12

45
m

45
m

45
m

R13

R14

45
Y1- m
3

Y14

R15
45
m

Y15

Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)

R1-5
IRI-5 R1-3
=
2X 436
221.37 X
0.85
=
4.63A

Y11

45
m

V
d

= 4.63 X 45 X
2.80
1000
=
0.58V

Vd at R1-5

= 230.34
0.56
=
220.79V

Voltage Drop (R-1 Phase)


= 2.83 V + 2.28 V + 1.73 V + 1.16 V +
0.58 V
= 8.58 V
8.58 x 100% = 3.73% < 4% (OK)
230
Regulation 525-01-02
Based on IEE Regulation 16th edition, Regulation 525-0102, the maximum permissible voltage drop must not
exceed 4% of the nominal voltage of the supply

45
m

45
m
R11

FEEDER
PILLAR
45
m

Y11

45
m
R12

45
m

Y12

45
m

45
m

45
m

R13

R14

45
Y1- m
3

Y14

R15
45
m

Y15

Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
IYI-1

Y1-1
= 10 X 436
229.31 X
0.85
=
22.36A

V
d

= 22.36 X 45 X
2.80
1000
=
2.83V

Vd at Y1-1

= 229.31
2.83
=
226.54

45
m

45
m
R11

FEEDER
PILLAR
45
m

Y11

45
m
R12

45
m

Y12

45
m

45
m

45
m

R13

R14

45
Y1- m
3

Y14

R15
45
m

Y15

Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)
IYI-2

Y1-2
= 8X 436
226.54X
0.85
=
18.11A

V
d

= 18.11 X 45 X
2.80
1000
=
2.28V

Vd at Y1-2

= 226.54
2.28
=
224.26V

45
m

45
m
R11

FEEDER
PILLAR
45
m

R12
45
m

Y12

45
m

45
m

45
m

R13

R14

45
Y1- m
3

Y14

R15
45
m

Y15

Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)

Y1-3
IYI-3 = 6X 436
224.26 X
0.85
=
13.72A

Y11

45
m

V
d

= 13.72 X 45 X
2.80
1000
=
1.73V

Vd at Y1-3

= 224.26
1.73
=
222.53V

45
m

45
m
R11

FEEDER
PILLAR
45
m

R12
45
m

Y12

45
m

45
m

45
m

R13

R14

45
Y1- m
3

Y14

R15
45
m

Y15

Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)

Y1-4
IYI-4 R1-3
= 4X 436
222.53 X
0.85
=
9.22A

Y11

45
m

V
d

= 9.22 X 45 X
2.80
1000
=
1.16V

Vd at Y1-4

= 222.53
1.16
=
221.37V

45
m

45
m
R11

FEEDER
PILLAR
45
m

R12
45
m

Y12

45
m

45
m

45
m

R13

R14

45
Y1- m
3

Y14

R15
45
m

Y15

Ballast Losses
i)25w/lamp(lantern 250w)
ii)36w/lamp(lantern 400w)

Y1-5
IYI-5 R1-3
= 2X 436
221.37 X
0.85
=
4.63A

Y11

45
m

V
d

= 4.63 X 45 X
2.80
1000
=
0.58V

Vd at Y1-5

= 230.34
0.56
=
220.79V

Voltage Drop (Y-1 Phase)


= 2.83 V + 2.28 V + 1.73 V + 1.16 V + 0.58
V
= 8.58 V
8.58 x 100% = 3.73% < 4% (OK)
230
Regulation 525-01-02
Based on IEE Regulation 16th edition, Regulation 525-0102, the maximum permissible voltage drop must not
exceed 4% of the nominal voltage of the supply.

QUESTION
Q1: Refer to table 4D4B. What is the
voltage drop for cable 25mm2?
A1: 1.50mV/A/m
Q2: Refer to table 4E4B. What is the
voltage drop for cable 70mm2?
A2: 0.60mV/A/m