FOUNDATION Fieldbus

FISCO vs HPT

Comparison of Technical Data


High Power
trunk

FISCO
Rating
Typ.
operating
voltage
Max. supply
current
1)

Ex ia IIC

Ex ib IIC

Ex ib IIB

12.8 V

12.4 V
(12.2 V) 1

13.1 V
(12.9 V)1

28 V

100 mA

120 mA
(105 mA) 1

265 mA
(245 mA) 1

500 mA

Values in brackets are valid for redundant layout

Compared to the FISCO solutions HPT


provides
More voltage longer cable runs
More current more instruments per segment
26/01/2011

Thomas Klatt

page 2

Redundant FISCO???

26/01/2011

Thomas Klatt

page 3

FISCO
PS

FISCO
PS

Functional Advantage: Redundancy

Logic
solver

It is NOT allowed to have 2 FISCO


power supplies connected to a
segment, therefore:
During the switch over the segment is for
a (short) time unpowered
This can cause telegram losses

To avoid the loss of field devices or


the whole segment a quick switch
over is essential!
To ensure a quick switch over the
redundant power supply must be in a
hot stand by mode
Heat dissipation

26/01/2011

Thomas Klatt

page 4

Size of Hot stand by FISCO


Same scale
HD Power Hub
150 mm * 200 mm

Stand by solution
requires approx.
3 times more
cabinet space
30000 mm comp. to
81600 mm
In practice space
saving can be
higher due to more
field devices per
segment compared
to FISCO

26/01/2011

Thomas Klatt

page 5

Space Requirements

Hot standby
FISCO

High
Density
Power Hub

Dimensions [mm]

320 * 255

200 * 150

Square footage
[mm]

81,600

30,000

Space
requirement

272%

100%

32

96

segments per
cabinet

26/01/2011

Thomas Klatt

page 6

Space Requirements

26/01/2011

Thomas Klatt

page 7