Done by:
-OUBELAID
Adel.
- MESSROUR
Hichem .
Outlines:
Siemens products.
Setting and setting test.
Fault analysis example.
Electromechanical
Relays
1900
years
MicroprocessCommunicatio
n Facility
orBased Relays
AI-based
(Digital)
Methods
Static Digital Proc.
Relays Algorithms Digital ICs
Digital ICs (mP,DSP,A
Elect
DC, neuroCircuits
IC
(mP,ADC,)
fuzzy-IC,
1960
1975
2000FPGA)
Overcurrent protection.
Distance protection.
Differential protection.
What is
DIGSI?
What is SIGRA?
SIGRA is a Siemens application that displays the signals
contained in a fault record on time charts. These time
charts are useful to analyze the protective relay response to
the fault.
Advantages:
Very short operating time.
several protection functions can be
implemented on it.
2.1: Settings
We activate the overcurrent protection function which is suitable for our network
(power system ),We choose one of the following time-current characteristics:
Definite-T1(instantaneous relay).
2.2:Testing(Symmetrical fault).
Step01: (duration is set to 10 s).
During the first step, the internal relay test system emulates
balanced currents of 1.00 A at the current inputs of the relay. This is
equivalent to balanced currents of 1000 A in the electric power
circuit because 1000 A/1 A current transformers are used in this
project.
Step02: (duration is set to 2s).
During the second step, the internal relay test system emulates
balanced currents of 10.00 A at the current inputs of the relay. This
is equivalent to balanced currents of 10 000 A in the electric power
circuit because 1000 :1 current transformers are used.
Conclusion:
The fault record confirms that the protective relay
operated as expected because the protective relay is set
to operate as an instantaneous over current relay with a
current setting of 8000 A .
THANK YOU
Questions?
??