Trafo Erection and MAINTENANCE
Trafo Erection and MAINTENANCE
Transformer Checking
Visual Inspection
Is the outer body damaged or not?
Is there oil leakage or not ?
Oil level checking.
Horn-Gaps checking.
Is the silica gel dry(blue in color) ?
Continuity Test (using Megger Insulation Tester)
Test the insulation between Primary side or High Voltage
Side (b/n R&S,R&T and S&T)
Contd
Test the insulation between Secondary Side or
Insulation Test
Test the insulation between Primary Side and
Secondary Side (b/n R&r,R&s, R&t and S&r,S&s,
S&t and T&r,T&s, T&t )
Transformer Winding
R
Secondary Side
neutral
Primary Side
s
T
t
Accessories Checking
Check all the accessories are available
Cross arms
Lightening - Arresters
Insulators
Drop out or Cut out Fuse( with proper Fuse Links)
Earthing rods & copper conductors.
Fused Box ( with proper HRC Fuses)
Conductors
And other accessories as show on the picture
Check all the accessories are in appropriate size and rate
The rating of Lighting arrester, drop out fuse and HRC fuse
has to match to the transformer rate.
Transportation
How to Uplift on Vehicle
How to Transport to the site
How to drop from Vehicle
Special care for Bushings, Radiators
Erection
Pole Selection(for wooden pole)
Pole Erection
The pole shall be plant 2m deep.
The diameter of planting hole shall be kept minimizing but not lessthan50 cm.
The H-pole shall be exact plumb (i.e. Absolutely vertical)
Both the pole shall be buried to exactly at the same level(not as shown on the
picture)
Properly Stamped according to the nature of soil
Installation of transformer cross-arm
It has to be erected at height of 2.2m from ground level.
It shall be fixed on poles exactly horizontal.
The level shall be checked with spirit level.
Contd
Installation of drop-out fuses.
It shall be erected at least a height of 7.2 m from ground.
It shall be checked for proper alignment and matching.
It shall also be connected to earth wire provided
Installation of Surge Arrestors
It uses to protect the transformer against lightning over-
voltage.
They are three in numbers and connected at the top of the Hpole structure.
The earth terminal at the bottom of all the three lightning
arrestors are joined together and connected to the earth wire
provided.
Trafo capacity
Voltage
level
fuse Ratings
(KVA)
(KV)
HRC
25
15
63
50
15
63
100
15
100
200
15
10
160
25
33
63
50
33
63
100
33
100
200
33
160
Contd
Installation of Transformer
It has to be lifted using pulley or crane machine.
During the process of lifting , the transformer has
not to be unbalanced.
It shall be ensured that all cover bolts are tightened
before lifting.
Fixing it properly with the cross arm base and poles
The Transformer body and the neutral terminal shall
be connected together with 2xCu25 conductors and
then the body shall be connected through the
earthing wire to earthing rode provided.
Insulation and continuity test
Transformer Maintenance
Transformer Fault
Transformer faults at rural substation
Contd
Lightning arrestor.
HV/MV substation.
Arcing Horns