Breakdown voltage of liquid insulation depends upon water content in that liquied.
> If water is dissolved in the oil, breakdown voltage is quit higher (i.e 65KV)
>If water is emulsified in oil, Break down voltage falls.
Majority of Moisture in paper & pressboard, a small portion in oil.
Oxyegn: reacts with oil molecule to form water, CO/CO2 (mainly, by oxidation)
Paper Test
>DOP -Mechanical Strength of Paper
>Furfural Analysis -Permanent byproducts
>Moisture Content -Sample
>Tensile Strength -Mechanical Stress
Dielectric Test
>Voltage Test Electrical withstand strength of insulation
>Partial Discharge Test Detect and locate harmful local discharge
>Dielectric Response Diagnostic measurement, Moisture content