Power Triangle

You might also like

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 14

Power Triangle

Power Factor Correction


Power Triangle
The representation of a right angle triangle showing the
relation between real power, reactive power, and
apparent power.
Real Power
The power which is actually consumed or utilized in AC
circuits
Denoted by P
Sometimes called true power or active power.
Measured in Watts or kiloWatts
Reactive Power
The power which flows back and forth
Denoted by Q
Measured in volt-ampere reactive(VAR) or kilovolt-
ampere reactive(kVAR)
Apparent Power
The total power in ac circuit
Combination of true power and reactive power
Denoted by S
Measured in volt-ampere(VA) or kilovolt-
ampere(kVA)
Power Factor
The ratio of Real Power over the Apparent Power
Power Factor = Real Power/ Apparent Power
pf = P/S
cos = P/S
Real Power = Apparent Power x cos
Real Power = Voltage x Current x cos
P = VIpf
Example
A single phase load on 220 V AC source takes 100 W at 0.6
lagging power factor. Assume the load power factor will be
brought to about 0.9.

Current at 0.6 lagging power factor


Real Power = Spf
P = Vipf
I = P/Vpf
I = 100/220(0.6)
I = 0.75 Amperes

Apparent Power (S)
S = VI
S = 220(0.75)
S = 165 VA

Reactive Power
Q = Ptan
Q = 100(tan(53.13)
Q = 133.33 VAR
Corrected Power Factor to 0.9
Current
P = Spf
P = Vipf
I = P/Vpf
I = 100/220(0.9)
I = 0.5 Ampere
Reactive Power
Q = Ptan
Q = 100(tan(24.84))
Q = 48.43
Total Reactive Power
Total Reactive Power = Reactive Power old
Reactive Power New Q = Qold Qnew
Q = 133.33 48.43
Q = 84.9 VAR