Professional Documents
Culture Documents
Designing of A GSS and Power Line Communication
Designing of A GSS and Power Line Communication
Why Bother?
Introductio
n Introduction
Design layout
Project Assumptions
We know that the generated voltage do not exceed 20-25 kilo volts.
The assembly of apparatus used to change some characteristic (e.g. voltage, a.c. to
d.c., frequency, pf etc.) of electric supply is called a sub-station.
Therefore, we need a substation for the transmission and distribution system.
INTRODUCTION
3.2MW
A 33kV
132/33KV
16.2kV 20 MVA
Stepped 3.2MW
G up to B 33kV
132kv
3.2MW
36MW
C 33kV
D 132kV
Assumptions:
In our substation, we have chosen ONE MAIN BUS AND ONE TRANSFER BUS system.
The buses are coupled using a bus-coupler which facilitates load transfer while
maintenance and fault conditions.
Load catered = 200 MW
Voltage = 132 KV
P = 3 VI cos
We take power factor as 0.9
Rated current is taken to be I ampere, we get I = 971.97 ampere
Going by the rated current that is required to be catered we chose twin moose
conductor for the purpose of main bus and normal single moose for transfer bus.
Decision of Designing a Substation
When we decide to designing a substation we need to put the following points into
consideration
Load Growth
System Stability
System Reliability
System Capacity
Power Line Communication
[PLC]
Introduction
General modulation principle
Introduction
Basic principle of PLCC
Arrangements
Line traps
Project Tuning Capacitor
Maintenance
Fault Procedure
traction
Introduction
The power line as a rigid long conductor parallel to ground, guides the carrier
waves to travel along the transmission line.
The voice/data are mixed with radio frequency carrier (40-500kHz), amplified to a
level of 10-80W RF power and injected in to high voltage power line using a suitable
coupling capacitor.
This is economic and reliable for inter grid message transfer as well as low bit rate
RTU signals.
Point to point communication takes place between two SSB transceivers at both
ends.
Understanding PLC extra
1. Narrowband PLC
2. Broadband PLC
Narrowband PLC works at lower frequencies (3-500 kHz), lower data rates (up to 100s
of kbps), and has longer range (up to several kilometers), which can be extended
using repeaters.
Broadband PLC works at higher frequencies (1.8-250 MHz), high data rates (up to 100s
of Mbps) and is used in shorter-range applications.
Components
PLCC Terminal: translates voice and data into high frequency carrier. Output
power =10 to 80W
Line matching unit(LMU): for impedance matching between line and coaxial
cable, includes high voltage protection devices like drainage coil (20mH), lightening
arrestor (500V) and an earth switch.
Coupling Capacitor (C.C): couples high frequency carrier with power line
( 4000 to10000 pF)
Line Trap (L.T): Do not allow the transmitted HF carrier to enter inside the Sub-
station. (L = 0.5 to 2mH) without line trap HF carrier get by- passed to some other line
on the same bus bar and may leak to ground (a earth switch inside the yard provided
for each bay ,is kept closed during maintenance)
Pictorial Diagram
L.T
Power Line
(50Hz)
C.C
RF carrier
(40-500kHz)
PAX
RTU
PLCC TERMINAL
RTU Remote Terminal Unit extra
In an effort to aggregate these multiple signal types, Remote Terminal Units, or RTUs,
were deployed.
RTUs have the ability to communicate with different generations of equipment and
data protocols, and many use a relatively modern T1 interface to provide a standard
way of communicating status and control to central sites.
Each 1.544 Mbps T1 carries the equivalent of 24 separate phone conversations-more
than enough capacity to support most existing substation communication needs.
Line trap function = PLC signal
blocking
Power
energy
Line Trap: It offers high
PLC
impedance for PLC signal and
Signal
Low impedance for Power
energy Substatio
n
Line Traps Mounting Options
Matching + Protection
Cabinet Module
PLCC Panel Tx Block
Carrier
Signal
Line
Input Modulat Coupling
Filter Amplifier Matchin
signal or Device
g Unit
PLCC Panel Rx Block
Fault analysis:
In fault analysis the faulty devices are checked in this serial or manner:
The battery terminal should be connected first and AC input after that.
1:TELEPHONE FACILITES
2:COMPRESSOR & EXPANDER
3:EMERGENCY CALL
4:SIGNAL BOOSTING
5:SUPERVISION & ALARMS
Key learning
Power line carrier communication has been found to be the most economical and
reliable method for communication in a medium and over long distance in a power
system.
Thank you