GEMSS-E-30-R01 (0) MV Cables
GEMSS-E-30-R01 (0) MV Cables
CERT.
ORIGD
GENERATION ENGINEERING & MATERIALS STANDARD SPECIFICATION
GEMSS-E-30
Revision No. 01
Volume - 1
REVISIONS
DESCRIPTION
PROPRIETARY INFORMATION
This document contains proprietary information developed by and for exclusive use of
Saudi Electricity Company. Your acceptance of the document is an acknowledgement that
it must be used for the identified purpose/application and during the period indicated. It
cannot be used or copied for any other purposes nor released to others without prior
written authorization of Saudi Electricity Company. Saudi Electricity Company will not be
responsible for misuse and/or misapplication, and any harm resulting therefrom. Saudi
Electricity Company also reserves the right to take any necessary actions to protect its
interest against unauthorized use.
1.
2.
3.
Generation Engineering & Materials
Standard Specifications
GEMSS-E-30,Rev.01 Volume - 1
Medium Voltage Cables
Document Responsibility:- Engineering and Design Division
Next Planned Update : Based on new development & technology with the consent of designated division
Table of Contents
2.0 SCOPE 2
5.0 MATERIALS 3
Page 1 of 5
Document Responsibility: Engineering and Design Division Volume - 1
Next Planned Update:- Based on new development & technology GEMSS-E-30,Rev.01
with the consent of designated division Medium Voltage Cables
MV power cables shall be single core or multicore XLPE insulated, unarmoured with a red LSF
sheath.
2.0 SCOPE
This section details the technical requirements for the design, construction and testing of the
medium voltage cables.
The latest version of the following codes and standards shall be followed, unless stated
otherwise by this specification:
- IEC 60332-3-22 Tests on electric and optical fibre cables under fire conditions. Test for
vertical flame spread of vertically mounted bunched wires or cables
Category A
- IEC 60502-2 Cables for rated voltages from 6 kV ((Um = 7,2 kV) & up to 30 kV (Um
= 36 kV)
- IEC 60811 Common test methods for insulating and sheathing materials of
electric cables
Proposed recommendations and requirements stated in above referenced codes and standards shall be
followed, unless stated otherwise by this Specification.
In case of any conflict between the reference codes, or this Specification and codes, the more stringent
applies.
The plant shall be designed, constructed and installed such that every reasonable safeguard
and provision for the safety of all personnel concerned with the construction, commissioning, operation and
maintenance of the plant is incorporated.
All equipment shall be designed, constructed and installed to ensure satisfactory and safe
operation under all operating conditions including load and voltage variation, frequency variation, transients
from starts and stops, transients due to short circuits and other internal and external fault conditions.
Page 2 of 5
Document Responsibility: Engineering and Design Division Volume - 1
Next Planned Update:- Based on new development & technology GEMSS-E-30,Rev.01
with the consent of designated division Medium Voltage Cables
The failure of any single electrical component or piece of equipment shall not compromise the
safe operation of the plant and shall not cause a loaded generator to trip.
The design, construction and installation of the plant shall be carried out under the consideration
of maximising the continuity of supply, availability of service and reliability.
The electrical plant and equipment shall be provided with suitable means for electrical
disconnection, isolation and earthing of connections to facilitate maintenance and reconfiguration of any part
of the electrical power system during the normal operation of the power station.
All equipment shall be of proven concept and design under commercial operation and shall be
manufactured by reputable and approved manufacturers to ensure high reliability.
Prototype or experimental equipment that has not been proven shall be excluded.
5.0 MATERIALS
All equipment and components shall be new and designed and manufactured for the specific
purpose for which they shall be used within the plant.
The design, construction and installation of the plant and equipment shall be such as to minimise
the risk of the outbreak of fire and to minimise the potential and consequential injury to personnel and damage
to equipment.
Materials shall not support combustion and shall be fire retardant where possible.
The cable conductors shall comprise of stranded, annealed, high conductivity copper.
The degree of compaction of stranded conductors shall comply with DIN VDE 0295.
For power supply cables the voltage drop between the point of supply and the fixed equipment
shall be limited to four per cent [4%].
In the case of motor power supply circuits the voltage drop shall be limited to ten percent (10%)
under motor starting conditions However for large motors above 10MW voltage drop shall be limited to
fifteen per cent [15%] under motor starting conditions.
Part of cable system Voltage drop under load Voltage drop under motor
conditions starting conditions
(% nominal voltage) (% nominal voltage)
Page 3 of 5
Document Responsibility: Engineering and Design Division Volume - 1
Next Planned Update:- Based on new development & technology GEMSS-E-30,Rev.01
with the consent of designated division Medium Voltage Cables
Cable insulation for all power cables and multicore control cables shall be cross-linked
polyethylene (XLPE).
The insulation of each conductor shall be identified throughout its length either by colour or
embossed numbers.
All cables shall have the length identified in a per metre basis on the outer sheath. The voltage
rating of the cable shall also be identified on the outer sheath.
The bedding and outer sheaths of cables shall have low smoke and fume characteristics.
The colour of outer sheaths shall remain stable when exposed to UV radiation and to the general
environmental conditions in which they are installed.
Cable through joints shall not be used in the installation unless the route of the cable exceeds
the maximum drum capacity. Maximum drum capacities of each cable type shall be provided.
Single core cables shall be identified by coloured tape over the conductor insulation beneath the
gland.
All cables shall comply with the test requirements of IEC 60332-3-22.
Each cable shall be identified by a securely fixed fade-free and dirt resistant identification label
adjacent to the gland at each end of the cable.
All cable cores shall be unambiguously identified at each end to ensure correlation with the
cable schedules.
- The mechanical bursting capability of any multicore power cable will not be exceeded
under short circuit fault conditions,
- The maximum short circuit rated conductor temperature will not be exceeded under fault
conditions. The initial conductor temperature shall be taken as equal to the maximum
continuously rated temperature of the insulation for the purpose of these calculations,
All calculations shall take into account abnormal running arrangements resulting from the outage
of one switchboard, transformer or circuit.
The conductor cross section of each cable shall be adequate for carrying the prospective fault
current determined by the next relevant short circuit protection device.
Short circuit fault calculations shall take full account of both the ac and dc components of the
fault current.
Routine and type tests and methods, taking account of applicable codes and standards, shall be
agreed with and approved by the Company.
Technical Schedule and data sheets shall be completed and submitted along with the proposal
for Company/ Engineer review. (Please refer to Volume 2).
Page 5 of 5