Professional Documents
Culture Documents
Protection Apparatus Schemes: Unit Ii Vi-Sem 2016 St. Joseph University (TZ)
Protection Apparatus Schemes: Unit Ii Vi-Sem 2016 St. Joseph University (TZ)
Protection Apparatus Schemes: Unit Ii Vi-Sem 2016 St. Joseph University (TZ)
Generators
Motors
Transformer
Buses
Lines (transmission and distribution)
Utilization equipment (domestic loads)
Note: Protective system cost is 4-5% of the total
cost in industries per IEEE
2
Protection Zones
3
Quantities Affected in Electrical
System
In electrical system, the generator, transformer and
motors are the most expensive equipments and
hence it is desirable to employ a protective system
Relay
Circuit breaker
Multilin
6
VT VS
Relay
Current Transformers
Current transformers are used to step primary system currents to
values usable by relays, meters, SCADA, transducers, etc.
CT ratios are expressed as primary to secondary; 2000:5,
Energizing an Alarm
11
Basic Functioning of Protection
Relay
12
Functioning of Protection Relay
13
Our current discussion will be
based on: Generator Protection
SEMINAR
Transformer Protection(2.5marks for
Assignment1)
14
TYPES OF GENERATOR
AC Generator DC Generator
Induction Generator
Self Excited DC Generator
Separately Excited
SYNCHRONOUS GENERATOR
AC GENERATOR
Synchronous Generator
Synchronous Generator : in this type the rotor speed is just equal to the flux
produce by the stator . And receiving field excitation from separate field supply
Asynchronous(Induction) Generator
Asynchronous or Induction : in this type Rotor speed is not equal the Flux
produced by the stator
Induction generator takes reactive power from the power system for field
excitation. If an induction generator is meant to supply a standalone load, a
capacitor bank needs to be connected to supply reactive power.
Due to lack of a separated field excitation , these machines are rarely used as
generator
AC GENERATOR
Synchronous Generator
Field excitation
Asynchronous Generator
GENERATOR MAIN PARTS
Parts: By Mechanical
Parts: By Electrical
Armature winding
The winding which carries only the load current.
Field winding
The winding which carries only the field current required to produce
the magnetic flux.
SCHEME OF GENERATOR
PROTECTION
CLASS A TRIPPING
This is adopted for those electrical faults of Generator and
Generator transformer(TG) and unit auxiliary transformer(UAT)
for which tripping can not be delayed.
- Generator HV side CB
- Field Circuit Breaker
- LV side incomer breakers of UAT
- Auto changeover from unit to station for unit auxiliaries and
tripping of turbine
CLASS B TRIPPING
This is adopted for all turbine faults (Mechanical) and for
some Electrical faults of Generator, Generator transformer
and unit Auxiliary transformer for which it is safe to trip the
turbine after sometime
19
SCHEME OF GENERATOR
PROTECTION
CLASS C TRIPPING
This is adopted for all faults beyond the Generator system
which can be cleared by tripping of Generator transformer HV
side CB alone
20
FAULT OCURRENCE & FAULT
CLASSIFICATION
Insulation failure
Stator Fault
Tends to increase with rising
Rotor fault
temp
Abnormal Running Condition
Insulation failure may cause LLL
or LLG.
Bring winding in to direct contact
with core plates.
Any failure to restrict earth fault
may result into core plate
damage.
Insulation of rotor winding is also
important
INSULATION FAILURE FAULT
Insulation failure.
Tends to deteriate with rising temp.
26
GENERATOR DIFFERENTIAL
PROTECTION
Differential protection is a very reliable method of protecting
generators from the effects of internal faults
27
Phase to Earth Fault
mmmmmm
mmmmmm
mmmmmm
mmmmmm
Loading
Over voltage relay
resistor
With time delay
38
Negative phase sequence
protection:
1250 1160
1200
46
Loss of Field Protection
47
Reverse Power Protection
When prime-mover fails machine starts motoring
and draws electrical power from the system and
this is known as inverted operation .
The generator can be protected from inverted
operation by using single-element directional
power relay(reverse power relay) which senses
the direction of power flow.
Failure of the prime mover of a generator set ,will
keep the set running as asynchronous
compensator
Reverse power relay scheme
Over voltage protection:
Over voltage may be caused due to-
Transient over voltage in the transmission line
due to lightening.
Defective operation of the voltage regulator.
Sudden loss of load due to line tripping.
The protection is provided with an over voltage
relay.
Overcurrent protection:
52
EQUIPMENT GROUNDING