REB500 Protection System

How to avoid blocking of busbar


protection function due to
Transverse Currents

ABB Automation
CHPAU / NSS-2 / Milltown/ F1 / 01-05-17 /Jan Schutter
ABB
Substation Lay Out : Milltown, Ireland

ABB Automation
CHPAU / NSS-2 / Milltown/ F2 / 01-05-17 /Jan Schutter
ABB
Problem : BBP can block due to Transverse Currents
Short circuit at bus Infeed Short Circuit

Isolators parallel
Directional criterion may block BBP
ABB Automation
CHPAU / NSS-2 / Milltown/ F3 / 01-05-17 /Jan Schutter
ABB
Solution : extended blocking function for bus tie breakers

Activate extended blocking

ABB Automation
CHPAU / NSS-2 / Milltown/ F4 / 01-05-17 /Jan Schutter
function for bus tie breakers
ABB
Constraint : Less Selective

Not selective for these zones


ABB Automation
CHPAU / NSS-2 / Milltown/ F5 / 01-05-17 /Jan Schutter
ABB
Summary

+ Directional Criterion BBP does not block in


case of transverse current.

- Substation is protected less selective


during Isolator parallel.

ABB Automation
CHPAU / NSS-2 / Milltown/ F6 / 01-05-17 /Jan Schutter
ABB