UW Goesgen

Protection
Technology and Solutions
Protection and Substation Automation
Concept
REB500
ABB Switzerland Ltd. - 1
Goesgen / 2003-02-12 /SJ

ABB
REB500 behaviour without CT Remote Station
Current Situation
A
B

Q2 Q1 Q62 Q2 Q1

Q0

Q9
ABB Switzerland Ltd. - 2

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

ABB
REB500 behaviour without CT Remote Station
ACA02 -Q1 Closed
A
B

Q2 Q1 Q62 Q2 Q1

Q0

Q9
ABB Switzerland Ltd. - 3

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

ABB
REB500 behaviour without CT Remote Station
ACA02 -Q2 Closed
A
B

Q2 Q1 Q62 Q2 Q1

Q0

Q9
ABB Switzerland Ltd. - 4

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

ABB
REB500 behaviour without CT Remote Station
ACA02 -Q0 Closed
A
B

Q2 Q1 Q62 Q2 Q1

Q0

Q9
Measurement active for both
zones
ABB Switzerland Ltd. - 5

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

ABB
REB500 behaviour without CT Remote Station
ACA0X Q62 Closed
A
B

Q2 Q1 Q62 Q2 Q1

Q0
Measurement
blocked because
Q9
of Breaker
Open
Diff. Protection Busbar A is automatically blocked
As feeder current ACA0X is not measured
ABB Switzerland Ltd. - 6

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

ABB
REB500 behaviour without CT Remote Station
ACA0X Q0 Open
A
B

Q2 Q1 Q62 Q2 Q1

Q0

Q9

Diff. Protection Busbar A is automatically blocked


As feeder current ACA0X is not measured
ABB Switzerland Ltd. - 7

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

ABB
REB500 behaviour without CT Remote Station
ACA0X Q9 Open
A
B

Q2 Q1 Q62 Q2 Q1

Q0

Q9

Diff. Protection Busbar A is automatically blocked


As feeder current ACA0X is not measured
ABB Switzerland Ltd. - 8

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

ABB
REB500 behaviour without CT Remote Station
ACA0X Q9 Open
A
B

Q2 Q1 Q62 Q2 Q1

Q0

Q9

Diff. Protection Busbar A is automatically blocked


As feeder current ACA0X is not measured
ABB Switzerland Ltd. - 9

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

ABB
REB500 behaviour with CT Remote Station
Situation
A
B

Q2 Q1 Q62 Q2 Q1

Q0

Q9

Max. Distance
approx.1.2 km
ABB Switzerland Ltd. - 10

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

Line protected by

ABB
REB500 Diff. Protection
REB500 behaviour with CT Remote Station
ACA02 -Q1 Closed
A
B

Q2 Q1 Q62 Q2 Q1

Q0

Q9
ABB Switzerland Ltd. - 11

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

ABB
REB500 behaviour with CT Remote Station
ACA02 -Q2 Closed
A
B

Q2 Q1 Q62 Q2 Q1

Q0

Q9
Measurement is blocked as related breaker is open
ABB Switzerland Ltd. - 12

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

ABB
REB500 behaviour with CT Remote Station
ACA02 -Q0 Closed
A
B

Q2 Q1 Q62 Q2 Q1

Q0

Measurement is active for both protection Q9


zones
ABB Switzerland Ltd. - 13

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

ABB
REB500 behaviour with CT Remote Station
ACA0X Q62 Closed
A
B

Q2 Q1 Q62 Q2 Q1

Q0
Measurement
blocked because
Q9
of Breaker
bypass
ABB Switzerland Ltd. - 14

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

REB500 Diff. Protection Busbar A active as Feedercurrent is

ABB
measured im remote station ACA0X.
REB500 behaviour with CT Remote Station
ACA0X Q0 Open
A
B

Q2 Q1 Q62 Q2 Q1

Q0
Measurement
blocked because
Q9
of Breaker
Open
ABB Switzerland Ltd. - 15

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

REB500 Diff. Protection Busbar A active as Feedercurrent is

ABB
measured im remote station ACA0X.
REB500 behaviour with CT Remote Station
ACA0X Q9 Open
A
B

Q2 Q1 Q62 Q2 Q1

Q0

Q9
ABB Switzerland Ltd. - 16

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

REB500 Diff. Protection Busbar A active as Feedercurrent is

ABB
measured im remote station ACA0X.
REB500 behaviour with CT Remote Station
ACA0X Q1 Open
A
B

Q2 Q1 Q62 Q2 Q1

Q0

Q9
ABB Switzerland Ltd. - 17

ACA02 ACA0X
Goesgen / 2003-02-12 /SJ

REB500 Diff. Protection Busbar A active as Feedercurrent is

ABB
measured im remote station ACA0X.