Professional Documents
Culture Documents
9 Reb500 Lon Iec
9 Reb500 Lon Iec
SMS/SCS Configuration
REB500
ABB
Content
ABB
ABB Switzerland Ltd - 3
2002 ABB. All rights reserved.
LON
IEC 60870-5-103
Todays Supported IBB Protocols
ABB
Example of IEC addressing
Control
IEC 103 station address(on link layer) system
CAA MVB
1 2 59
BU 1 BU 2 BU BU 59
Common address of ASDU (CAA)
Bay 1 Bay 2 Bay Bay 59
Generated automatically in tool <6.10
2002 ABB. All rights reserved.
ABB
Example of LON addressing
Control
LON station address(Unit Address) system
50 51 52 53 54 55
RET.... REB500 REL... REL.... REL.... REL....
CU
MVB
BU 1 BU 2 BU BU 59
ABB
Example of IEC/LON addressing; HMI500 <6.10
ABB
Example of IEC/LON addressing; HMI500 6.10
Station address must be active for one protocol
2002 ABB. All rights reserved.
ABB Switzerland Ltd - 7
ABB
Example Exporting signals LON address-list
Module;Type of IBB;Station Addr.;REBWIN Version;REBCON Version;DB Version;DB Date;Export Date;Export Tool Version
REB500;LON; 1 ;5.00;5.00;V1.00 ;2001-10-23;02-01-25 ;AI 01-02-28 V5.00.01
Station Name;Bay Name;Device Name;4. Field;5. Field;Signal Name;Technical Signal Identifier;Event Text;Sign...
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;11765_General Start ;11765...
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;13740_Start BFP L1L2...
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;16705_Start DR_1;16705_St...
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;21110_TRIP;21110_TRIP; ...
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;21805_In service;21805_In ser..
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;23105_BFP TRIP;23105_BF.
CHA KWO LING ROAD 132KV;BBP1;1;;;EVENT;+R01+U20-F391.01 1 T500BU02_1;23110_BFP_REMOTE_TRI..
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;11765_General Start ;1.
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;13740_Start BFP L1L2;1.
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;16705_Start DR_1;16705_..
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;21110_TRIP;21110_TRI.
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;21805_In service;21805 .
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;23105_BFP TRIP;2310..
CHA KWO LING ROAD 132KV;BBP1;10;;;EVENT;+R02+U14-F391.10 1 T500BU02_1;23110_BFP_REMOTE_..
CHA KWO LING ROAD 132KV;BBP1;11;;;EVENT;+R02+U14-F391.11 1 T500BU02_1;11765_General Sta...
...
2002 ABB. All rights reserved.
ABB Switzerland Ltd - 9
ABB
Example Contents IEC address-list DRR signals
Common ABB Bay Bay Name Stations Signal Signal
Address Name Number ID Text
ADSU ; ; ; ;
0; =ABB00; - ; Null; Null; Null
1; =ABB01; FUTURE CABLE; 1 ; 1 ; 21110_TRIP
1; =ABB01; FUTURE CABLE; 1 ; 2 ; 23105_BFP TRIP
1; =ABB01; FUTURE CABLE; 1 ; 3 ; 23110_BFP_REMOTE_TRI
1; =ABB01; FUTURE CABLE; 1 ; 4 ; 13740_Start BFP L1L2
1; =ABB01; FUTURE CABLE; 1 ; 5 ; 13745_Start BFP L1L2
1; =ABB01; FUTURE CABLE; 1 ; 6 ; 11765_General Start
10; =ABB10; FUTURE CABLE; 10 ; 1 ; 13740_Start BFP L1L2
10; =ABB10; FUTURE CABLE; 10 ; 2 ; 13745_Start BFP L1L2
10; =ABB10; FUTURE CABLE; 10 ; 3 ; 21110_TRIP
10; =ABB10; FUTURE CABLE; 10 ; 4 ; 23105_BFP TRIP
10; =ABB10; FUTURE CABLE; 10 ; 5 ; 23110_BFP_REMOTE_TRI
10; =ABB10; FUTURE CABLE; 10 ; 6 ; 11765_General Start
2; =ABB02; TRANSFORMER1; 2 ; 1 ; 13740_Start BFP L1L2
2; =ABB02; TRANSFORMER1; 2 ; 2 ; 13745_Start BFP L1L2
2; =ABB02; TRANSFORMER1; 2 ; 3 ; 21110_TRIP
2; =ABB02; TRANSFORMER1; 2 ; 4 ; 23105_BFP TRIP
2; =ABB02; TRANSFORMER1; 2 ; 5 ; 23110_BFP_REMOTE_TRIP
2002 ABB. All rights reserved.
ABB Switzerland Ltd - 10
ABB
What can be visualised LON/IEC
LON IBB protocol:
Time synchronisation
Binary events (signals,trips and diagnostics)
Trip Reset command
Differential current of each protection zone
Disturbance recording data transfer (BU03 only)
IEC 60870-5-103 protocol
Time synchronisation
Subset of binary events as specified in IEC
Trip Reset command
2002 ABB. All rights reserved.
ABB