Water Quality

You might also like

Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 21

WATER

CHEMISTRY

26 October 2017 PMI Revision 00 1


Presentation Outline

Qualities parameters of water requirement

Process of maintaining quality

26 October 2017 2
WATER QUALITY FOR SUPER CRITICAL
BOILERS
1. EFFECT OF SUPER CRITICAL PARAMETRS:

IMPROVEMENT IN FUEL EFFIENCY AND HEAT RATE

DECREASE IN SPECIFIC FUEL CONSUMPTION


&
REDUCTION IN EMISSION

THESE ARE THE DRIVING FACTORS FOR SUPER


CRITICAL CYCLE

26 October 2017 PMI Revision 00 3


2.CRITICAL PARAMETERS

SUPERCRITICAL BOILER
OERATE AT PRESSURE >200
BAR AND TEMPERATURE IS >600 deg.C
THEREFORE THE CONSTRUCTION OF
MATERIALSHOULD HAVE HIGH MECHANICAL
STRENGTH AND LOW CREEP.

AT
SUPER CRITICAL CONDITION THE MEDIUM IS
JUST A HOMOGENEOUS FLUID RATHER THAN
WATER OR STEAM.
THEREFORE USUALLY SUPERCRITICAL BOILER ARE
OF ONCE THROUGH TYPE.

26 October 2017 PMI Revision 00 4


3.DEFINITION OF SUPERCRITICAL CONDITION
CRITICAL CONDITION IS THERMODYNAMIC

EXPRESSION DESCRIBING THE STATE OF A

SUBSTANCE BEYOUND WHICH THERE IS NO

CLEAR DISTINCTION BETWEEN THE LIQUID

AND GASEOUS PHASE.

26 October 2017 PMI Revision 00 5


26 October 2017 PMI Revision 00 6
4.REQUIREMENT OF WATER QUALITY

THE CONTENTS OF DISSOLVED AND UNDISSOLVED


SOLIDS AND OTHER MATERIAL SHOULD BE PRACTICALLY
ZERO.
IN ORDER TO MAINTAIN ABOVE CONDITIONS
CONTINUOUS PURIFICATION OF THE RETURN
CONDENSATE BY MEANS OF CPU IS MANDETORY

IT EMPLOY THE USE OF ALL VOLATILE TREATMENT


IN ORDER TO MAINTAIN THE LOW TDS IN WATER.

O.T. IS RECENT METHOD EMPLOYED FOR THE TREATMENT


OF WATER/STEAM CYCLE

26 October 2017 PMI Revision 00 7


EFFECT OF CARBONIC ACID ON CORROSION RATE

10 ppm 8 ppm

26 October 2017 PMI Revision 00 8


5. MAKE UP WATER QUALITY

PARAMETERS SAMPLE TARGET


FREQUENCY VALUE
------------------------------------------------------------------
1. SODIUM , PPB C <3

2. CONDUCTIVITY C < 0.1


S/CM
3. SILICA , PPB C OR S < 10

4. CHLORIDE , PPB C OR S <3

5. SULPHATE ,PPB D <3


------------------------------------------------------------------
26 October 2017 PMI Revision 00 9
6.CONDENSATE PUMP DISCHARGE

PARAMETERS SAMPLE TARGET


FREQUENCY VALUE
---------------------------------------------------------------------------
1.SODIUM, PPB C <3

2.CATION CONDUCTIVITY C < 0.2


S/CM
3.OXYGEN, PPB C < 10
---------------------------------------------------------------------------

26 October 2017 PMI Revision 00 10


7. C.P.U OUTLET

PARAMETERS SAMPLE TARGET


FRQUENCY VALUE
---------------------------------------------------------------------------
1. SODIUM, PPB C <2

2.CAT.CONDUCTIVITY C < 0.1


S/CM
3. SILICA, PPB C OR S <5

4. CHLORIDE, PPB S <2

5. SULPHATE, PPB S <2


(VALUE BASED ON EPRI GUIDELINES)
---------------------------------------------------------------------------
26 October 2017 PMI Revision 00 11
8. FEED WATER
PARAMETERS SAMPLE AVT OT
FREQUENCY
----------------------------------------------------------------------------------------------------------------------
1. CATION CONDUCTIVITY C < 0.15 <0.15
S/CM
2.HYDRAZINE, PPB C 10-15 -----

3. pH C 9.0-9.5 7.0-8.5

4. DISSOLVED OXYGEN, PPB C <5 30-150

5. TOTAL IRON, PPB S <2 <2

6. SILICA, PPB S <5 <5

7.SODUIM, PPB S <2 <2

8.CHLORIDE, PPB S <2 <2


-----------------------------------------------------------------------------------------------
26 October 2017 PMI Revision 00 12
CONTD
MAGNETITE FORMATION IN ALL VOLATILE TREATMENT

26 October 2017 PMI Revision 00 13


OXIDE FORMATION IN OXYGENETED CONDITION

26 October 2017 PMI Revision 00 14


Cycle chemistry limit of boiler water during start up, normal operation and shutdown is shown
below: 2 a-b

S ta rtu p O p e r a t io n 1 H our Shut D ow n

> 9 .0

pH 8 .0 - 8 .5

N H 3 ppb (A s n e e d e d )

O 2 ppb 0 30-150
0
0
C a t io n
C o n d u c t iv it y 0 .2
u s /c m < 0 .1 5

F ig u r e 4 : S t a r t u p , o p e r a t io n & s h u t d o w n g u id a n c e f o r o x y g e n a t e d
c h e m is t r y in c lu d in g p a r a m e t r ic lim it s s h o w n .
D o t t e d lin e s r e p r e s e n t s o p t im u m s it u a t io n

26 October 2017 PMI Revision 00 15


PROCTECTION OF THE SYSTEM IN BOILER. BUT THE
RATE OF INCREASE IN PRESSURE DROP IS
CONSIDERABLE DUE TO DEPOSITION OF SCALE.
THIS WARRANT REGUALR CHEMICAL CLEANING.
THE ALL VOLATILE TREATMENT OFFER GOOD

OXYGENETED MODE OF TREATMENT OF FEED WATER


RESULTED IN PRACTICALLY NO DEPOSITION OF SCALE
IN BOILER SYSTEM.
THEREFORE LONGER PERIOD OFOPERATION WITHOUT
CLEANING.

26 October 2017 PMI Revision 00 16


9. RATIONALE FOR MONITORING TARGET PARAMETERS

MONITORING OF PARAMETERS ARE NECESSARY


BECAUSE:
(a) pH :
- CORROSION IS FUNCTION OF pH AND OXYGEN

- ALKALINE CONDITION INCREASES STABILITY OF


MAGNETITE IN ALL VOLATILE TREATMENT

- IN O.T. STABILITY OF FeOOH IS IN RANGE OF pH 7-8.5

(b) SODIUM/CHLORIDE/SULPHATE:

- ARE THE MAJOR CORRODANT FOR TURBINE AND


PRESSURE PARTS.
26 October 2017 PMI Revision 00 17
(c) DISSOLVEDOXYGEN:

- TO ENSURE THE FUNCTIONING OF DEAREATOR

- TO CONTROL THE AMOUNT OFHYDRAZINE


IN FEED WATER.

(d) IRON:
- THE CORROSION PRODUCT IN WATER/STEAM CYCLE

- INDICATES THE CORROSIVE CONDITIONS

(e) SP.CONDUCTIVITY/CATION CONDUCTIVITY:

- MOST IMPORTANT PARAMETER INDICATE THE LEVEL


OF TREATMENT CHEMICAL AND INDICATION OF
IMPURITIES.

26 October 2017 PMI Revision 00 18


10. INSTRUMENTATION FOR WATER/STEAM CYCLE

INSTRUMENTATION FOR CORE PARAMETERS

LOCATION PARAMETERS RANGE ALARM


-----------------------------------------------------------------------------------
1.MAKE UP WATER CONDUCTIVITY 0 - 1 S/CM YES

2.CEP DISCHARGE SP.CONDUCTIVITY 0 - 10 S/CM YES


CATION CONDUCTIVITY 0 - 1 S/CM YES
SODIUM 0 -1,0 - 100 ppb YES
D.O. 0 - 100 ppB YES

3.C.P.U.(OUTLET) AS IN S.No.2
CHLORIDE 0 -10 ppb YES
--------------------------------------------------------------------------------------------------------------

26 October 2017 PMI Revision 00 19


LOCATION PARAMETERS RANGE ALARM
-----------------------------------------------------------------------------------
4.FEED WATER pH 6 - 11 YES
SILICA 0 -20 - 100ppb YES
D.O. 0 -10 - 100 - 500ppb YES
HYDRAZINE 0 -50 -100Pppb YES
CAT.CONDUCTIVITY 0 -1 S/CM YES
SP.CONDUCTIVITY 0 -10 S/CM YES

5.BOILER DRUM pH 6 - 11 YES


(FOR DRUM TYPE) SILICA 0 -500 ppb YES
SP.CONDUCTIVITY 0 - 10 -20 S/CM YES
CAT.CONDUCTIVITY 0 -1 S/CM YES

6.STEAM SP.CONDUCTIVITY 0 - 10 S/CM YES


CAT.CONDUCTIVITY 0 -1 S/CM YES
SODIUM 0 -10 ppB YES
--------------------------------------------------------------------------------------------------------

26 October 2017 PMI Revision 00 20


THANK YOU

26 October 2017 PMI Revision 00 21

You might also like