FIRE PROTECTION SYSTEM

AX 272 F
a.) SPINKLER SYSTEM 4 ZONE

b.) STANDPIPE SYSTEM

c.) PRE-ACTION SYSTEM


(For Electrical Substation)
SPRINKLER SYSTEM
4 ZONES
ALARM VALVE STATION
STANDPIPE SYSTEM
CLASS III SYSTEM IS
PROVIDED
Class III Systems Provided 1
hose stations to supply water for use
by trained building occupants and
2 hose connections to supply a
larger volume of water for use by
Fire Department.
FIRE HOSE STATION
ADVANTAGES
Quick Suppression
One Person Operation
Minimal Water Damage
Occupant Safety and Rescue
TYPICAL CLASS III FIRE HOSE STATION
OPERATION OF FIRE
HOSE STATIONS
THREE STEPS FOR OPERATION

1. Open valve completely


2. Pull hose entirely off rack
3. Open nozzle
1. Open valve completely.
2. Pull hose entirely off rack
(or else water will not flow)
3. Open nozzle. Water will flow when hose is
entirely off rack & nozzle is open.
PREACTION SYSTEM
FOR
ELECTRICAL SUBSTATION
PREACTION SYSTEM
COMPONENTS

Preaction System Control Panel


Smoke detectors
Manual Pull Station (Electric)
Alarm Bell
Sounder cum flasher
PREACTION SYSTEM
COMPONENTS

Deluge Valve w/ Double Interlock


Trim
Isolation Valve
Pressure Switch (Air)
Pressure Switch (Water)
Air Compressor
Air Maintenance Device
PREACTION SYSTEM

SEQUENCE OF OPERATION
Smoke Detectors (Zone-1) and Pressure Switch
(Zone-2) Monitoring the System Air Pressure in
the piping are wired in a cross zoned configuration
PREACTION SYSTEM
SEQUENCE OF OPERATION
Activation of smoke detector or operation
of a sprinkler causes following.

A visual indication on the System Control


Panel
Audible alarm from bell
Send Fire indication to the Fire Alarm
System
PREACTION SYSTEM
SEQUENCE OF OPERATION
Activation of smoke detector & operation
of a sprinkler causes following.

Visual indications on the System Control Panel


Audible alarm from bell & sounder cum flasher
Deluge valve operates
Water flows in to the system piping and
discharges through the opened sprinkler.
PREACTION SYSTEM
SEQUENCE OF OPERATION
Manual Operation

System can be operated manually by operating


the Pull Station (Electric or Hydraulic)
Visual indications on the System Control Panel
Audible alarm from bell & sounder cum flasher
Deluge valve operates
Water flows in to the system piping (if sprinkler is
not activated, piping will be filled with water)
PREACTION SYSTEM
SEQUENCE OF OPERATION

Operation of Air Compressor

Air compressor maintains constant air pressure


in the system piping.