A B 10 MVA C
166/33 kV
Zsec = Zpri * (CT ratio/ VT ratio)
Three zone impedance setting of transmission line
First zone covers up to 75% of first section
Second zone covers 100% of first and 50
% of second section
Third zone covers up to 100% of second section
For section AB, impedance seen by the relay is
= 21.435 + j 128.3 X
o
= 130 /80.5 Ω