Limits
DS Agile Training Level 1
20/01/2016
3) Performances Page 5
4) EMC Page 5
L1-13-Limits - Rev J
© 2015 General Electric Company. Proprietary. All Rights Reserved.
1) DS Agile Limits
Based on PS01 Component Maximum authorized
OI Client 8
Screens per OI Client 4
OI Server 1+1 redundant
Printers at OI level 4 (x2 if redundant)
Station Bus equipments (C264 & IEDs) 150
Ethernet MiCOM switches 127
Site 1
Substation 20
Voltage Level 4 if ATCC used
Bays 512
Circuit breakers 512
Disconnectors 2048
Transformers 512
Digital Input Points 37500
Output Control Points 5000
Measurements 7500
Tap Position Indication 512
Counters 512
Setpoints (digital or analogue) 512
Animated objects in OI mimic 128
L1-13-Limits - Rev J
© 2015 General Electric Company. Proprietary. All Rights Reserved.
Summary
3) Performances Page 5
4) EMC Page 5
L1-13-Limits - Rev J
© 2015 General Electric Company. Proprietary. All Rights Reserved.
2) C264 Limits
Component Maximum authorized
Printers on C264 1 (only on rear port)
Communication port (TBUS and/or LBUS) 4
SCADA protocols (TBUS) 2
Master Legacy protocols (LBUS) 4
IED per Legacy Bus 16
SBUS Servers (C264 & IEDs) for a C264 Client 16
SBUS Clients for a C264 Server 10
Incoming GOOSE messages (UCA2 & IEC61850)/C264 96
UCA2 GOOSE per C264 88 Binary inputs
IEC61850 GOOSE per C264 130 Binary inputs / 50 Measurements
Voltage Level 4 if ATCC used
Bays 128 (12 bays can be displayed on LHMI)
Circuit breakers 128
Disconnectors 512
Transformers 128
Digital Input Points / Wired DI / System DI 5600 / 240 / 100
Output Control Points / Wired DO 1200 / 150
Measurements / Wired MV 1200 / 48
Tap Position Indication 128
Counters / Wired CT 128 / 8
Setpoints (digital or analogue) 128
PSL / Interlocking equation 768
PSL operations 256
Controllable devices per LHMI mimic 9
L1-13-Limits - Rev J
© 2015 General Electric Company. Proprietary. All Rights Reserved.
Summary
3) Performances Page 5
4) EMC Page 5
L1-13-Limits - Rev J
© 2015 General Electric Company. Proprietary. All Rights Reserved.
3) Example
Emission Reception
3) Performances Page 5
4) EMC Page 5
L1-13-Limits - Rev J
© 2015 General Electric Company. Proprietary. All Rights Reserved.
2.1) Environmental : Dielectric
Water protection
Front IP52 IEC 60529 x x x
Case IP30 IEC 60529
Rear IP20 IEC 60529
Temperature
Cold Operating (96h) IEC 60068-2-1 -25° -25° 0°
Cold Storage (include power-up) IEC 60068-2-1 -40° -40° -20°
Dry heat Operating (96h-10days DICOT) IEC 60068-2-2 55° 55° 40°
(24h) IEC 60068-2-2 70° 70°
Dry heat Storage (96h) IEC 60068-2-2 70° 70° 70°
Damp Heat 40°C/10d/93%Humid IEC 60068-2-3 x x
Variation variation 65°C/h IEC 60068-2-14
L1-13-Limits - Rev J
© 2015 General Electric Company. Proprietary. All Rights Reserved.
2.2) Environmental : Supply & Isolation
Consumption Watts 30 - -
Isolation
Dielectric Withstand 2kVCM 1kVDM 1mn IEC 60255-5 x x x
Insulation Resistance 100Mohms 500V IEC 60255-5 x x x
Impulse voltage 5kV CM, 3kV DM IEC 60255-5 x x x
L1-13-Limits - Rev J
© 2015 General Electric Company. Proprietary. All Rights Reserved.
2.3) Environmental : Electromagnetic
LVD (CE) x x x
EMC (CE) x x x
UL (US) x x x
L1-13-Limits - Rev J
© 2015 General Electric Company. Proprietary. All Rights Reserved.