ATS Popular Features and Accessories

John J. Stark
Marketing Services Coordinator, Russelectric Inc.
ATS Timing Features and Important Commonly Used Accessories

Utility/Gen. Time delay to override momentary source 1 power


outages to delay engine start signal and transfer switch operation
(delay for generator start). Programmable 0.0-259 min, factory
set at 3.0 seconds.

Utility/Utility. Time delay to override momentary source 1


power outages to delay transfer switch operation (time delay for
utility sag). Programmable 0.0-30.0 seconds, factory set at 0
seconds.
ATS Timing Features and Important Commonly Used Accessories

Time delay to control contact transition time from neutral to non-


preferred source. Programmable 0.0-10 min, factory set at 1
second.

Time delay to control contact transition time from neutral to


preferred source. Programmable 0.0-10 min, factory set at 1
second.

1 L

2
ATS Important Commonly Used Accessories

Load test function (internal) to simulate source 1 power failure.

Remote Load test function energized by 24 VDC signal from


generator control switchgear to simulate source 1 power failure.

Toggle operated load test switch to simulate


source 1 power failure.

Contact closure provided by customer to simulate


source 1 power failure.

Internal form “C” contact to initiate engine starting


or other customer functions (24 VDC Signal by
others)
ATS Timing Features and Important Commonly Used Accessories

Time delay on retransfer to preferred source Programmable 0.0-


259 min, factory set at 30 minutes.

Programmable function to bypass time delay on retransfer to source 1.

Pushbutton to bypass time delay on retransfer to source 1.

Engine overrun to provide unloaded engine operation after


retransfer to source 1 (delay for engine cool down),
programmable 0.0-60 min, factory set at 5 minutes.
ATS Timing Features and Important Commonly Used Accessories

Load shed function energized by 24 VDC signal from generator control


switchgear to disconnect the load from the source 2 source when an
overload condition occurs. An automatic load shed feature is provided.
Whenever LSF is enabled the source 2 frequency is compared to the load
ATS shed frequency pick-up and drop-out values. When the source 2
frequency is less than the load shed frequency drop-out value 93% (56
Hz) and the load shed timer has expired, then a load shed condition is
initiated. The load shed timer is adjustable from 0-9999 seconds and
factory set at 1 second. Once the source 2 frequency is greater than or
equal to the load shed frequency pick-up value 96% (58 Hz), then the
load shed condition is removed. Ancillary benefit: Dual operator is
beneficial with this design so ATS doesn’t have to load shed to a dead
source.

24 VDC
ATS Timing Features and Important Commonly Used Accessories

ATS
Block transfer function energized by 24 VDC signal from generator
control switchgear to block or allow transfer to source 2 (typically
generator), so as not to overload it. This accessory includes an
internal programmable function to bypass the block transfer
function, and is used for manual operation. A two-position key operated
selector switch to bypass the block transfer function, may
also be spec’d for manual operation. (Spring return from transfer to
auto.)

24 VDC
Arc Flash, Things to Consider

•External Manual Operator Can ATS also be manually


(EMO) transferred safely under load?

•All control
switches
•Barriered Compartments mounted on
(bypass/isolation switches) outside

•All pertinent
•CCDP labeling affixed
to the outside of
cabinet, including,
model #, Serial #,
and emergency
•Shutter (bus isolation) Assembly phone #