Glanding: Glands Must Maintain Integrity of Enclosure

You might also like

Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 11

Glanding

Glands must maintain integrity of enclosure


FLAMEPROOF OTHER

Must be certified EEx d IIC Certification usually optional


Generally IP54

Glanding slide 1
Flameproof MICC gland

Potting compound

Swage ring

Glanding slide 2
Cable types
Solid cable Non-solid cable
(extruded bedded) (e.g. tape bedded)
solid filler

extruded bedding fillers: solid, hollow or non-existent


requires requires
compression gland barrier gland

Glanding slide 3
Flameproof compression gland

Inner seal clamps cable


and makes sealed joint

Glanding slide 4
Flameproof barrier gland
Epoxy resin filler
seals between cores

Glanding slide 5
Selection of flameproof glands
Cable entries: Start

Does the
YES enclosure NO
contain an
internal source
of ignition?
Does the
YES hazardous NO Use a
gas require suitable
Use a IIC flameproof
sealing apparatus? cable entry
device device with
(10.3.2 d) YES Is the area of NO a sealing
or e)) installation ring
Zone 1?

YES Is the volume NO


of the
enclosure
> 2dm3?

Glanding slide 6
When to use an Ex d barrier gland

• With a cable that is not sealed against gas,


e.g.
– tape-bedded cables
– some metal-sheathed cables
• With an enclosure containing a source of
ignition (e.g. switch, contactor) and
– hazard gas is IIC or
– enclosure is >2 litres and in a zone 1

Glanding slide 7
Conduit entry into Ex d
enclosures
• Conduit must be
– seam-welded or
– solid-drawn
• Conduit seals (‘stopper boxes’) are essential
– at or within 450 mm of Ex d enclosure wall
– when conduit passes from hazardous area to non-
hazardous area

Glanding slide 8
Glanding into non-flameproof
enclosures
For non-flameproof equipment….
use of a certified gland is not obligatory
but
gland usually should be IP54 minimum

Consider use of a certified gland for


• plastic glands into EEx e enclosures
• MICC glands in EEx e enclosures

Glanding slide 9
Adapters and reducers

These are permitted, but


– certified items only for Ex d
– good practice not to use more than one

Glanding slide 10
Gland features for different
applications
Gland type
Feature Ex d Ex e Industrial
Adequate mechanical strength   
Mechanically exposionproof   
Good electrical contact between gland   
& enclosure for proper earthing
Good electrical contact between gland   
& armour for proper earthing
Protected against dust ingress ?  ?
Protected against water ingress ?  ?
Cores sealed against explosion ?  
Certified   
Glanding slide 11